International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® CEP410R-2 residual current monitor for the central earthing point

The CEP410R-2 watches the central earthing point (CEP) of TN systems. It senses AC and pulsed DC residual current from 10 mA to 30 A and detects PEN bridges and N conductor connections between separate TN systems.

Measuring range
10 mA…30 A
Type
A (AC and pulsed DC)
Frequency range
42…70 Hz
Supply voltage
DC 24 V; AC/DC 100…240 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The CEP410R-2 is a residual current monitor for the central earthing point (CEP) of TN systems. It is type A, sensing AC and pulsed DC residual current, and it detects PEN bridges as well as N conductor connections between separate TN systems.

The measuring range is 10 mA…30 A at 42…70 Hz. The main alarm response value is adjustable from 10 mA to 30 A, and the prewarning is set at 50…100 % x IΔn. It runs on DC 24 V or AC/DC 100…240 V. Settings are made over NFC (13.56 MHz), and data go out over RS-485 with Modbus RTU at up to 115.2 kbits/s.

The compact enclosure is polycarbonate, rated UL94 V-0, with IP20 protection and DIN rail mounting to IEC 60715. It measures 109 x 48.5 x 64 mm and weighs no more than 100 g. Operating temperature is -25…+55 °C and operating altitude up to 2000 m above sea level.

Rated impulse voltage is 4 kV, rated insulation voltage 250 V and pollution degree 2. Rated surge current is 6.0 kA / 40 ms and rated thermal short-term current 2.4 kA / 1 s. Electrical endurance is 10000 switching cycles.

The device follows DIN EN IEC 62020-1, IEC 60664-1, IEC 61010-1 and IEC 60947-5-1. A declaration of conformity under Directive 2014/53/EU covers the NFC radio interface. A sealable transparent cover, part number B80609199, is supplied as a spare part.

Technical specifications

Measuring range10 mA…30 A
TypeA (AC and pulsed DC)
Frequency range42…70 Hz
Supply voltageDC 24 V; AC/DC 100…240 V
Main alarm response value10 mA…30 A
Prewarning50…100 % x IΔn
InterfacesRS-485 (Modbus RTU), NFC
Max. baud rate115.2 kbits/s
Operating temperature-25…+55 °C
Dimensions109 x 48.5 x 64 mm
Weight≤ 100 g
Degree of protectionIP20
MountingDIN rail to IEC 60715
Enclosure materialPolycarbonate, UL94 V-0
Rated impulse voltage4 kV
Rated insulation voltage250 V
Rated surge current6.0 kA / 40 ms
Rated thermal short-term current2.4 kA / 1 s

Part numbers

Show all part numbers (2)

B74603008, B80609199

How it compares with similar models

ParameterLINETRAXX® CEP410R-2 residual current monitor for the central earthing pointLINETRAXX® SmartDetect MRCD410R single-channel modular residual current deviceLINETRAXX® SmartDetect MRCDB425 AC/DC sensitive modular residual current deviceLINETRAXX® RCM410R-24/-2 single-channel residual current monitoring relay, 10 mA…30 A
Frequency range42…70 Hz42…70 HzDC, 15 Hz…20 kHz—
Supply voltageDC 24 V; AC/DC 100…240 VDC 24 V; AC/DC 100…240 V (MRCD410R-2 only)DC 24 V; AC/DC 100…240 V—
MountingDIN rail to IEC 60715DIN rail—DIN rail

Request a price and lead time

LINETRAXX® CEP410R-2 residual current monitor for the central earthing point. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What does the CEP410R-2 detect in a TN system?

It detects PEN bridges and N conductor connections between separate TN systems by monitoring residual current at the central earthing point.

What supply does it need and how is it configured?

The supply is DC 24 V or AC/DC 100…240 V. Parameters are set over NFC and data are read over RS-485 with Modbus RTU.

What response values can be set?

The main alarm is adjustable from 10 mA to 30 A, and the prewarning from 50 to 100 % x IΔn.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides