LINETRAXX® SmartDetect MRCDB425 AC/DC sensitive modular residual current device

The MRCDB425 is used in MRCD arrangements on earthed TN and TT networks. The main alarm response value spans 30 mA to 3 A, the frequency range is DC, 15 Hz…20 kHz, and the display is either TFT or an LED strip.

Frequency range
DC, 15 Hz…20 kHz
Measuring range (peak)
3 mA…28 A
Measuring range rms
2 mA…20 A
Response value main alarm IΔn (Type B)
30 mA…3 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

For MRCD applications on earthed TN and TT networks, the MRCDB425 is an AC/DC sensitive modular residual current device. The MRCDB425-D carries a TFT display and the MRCDB425-L an LED strip for measured values. Both run on DC 24 V or AC/DC 100…240 V.

Detection is type B and B+ over DC, 15 Hz…20 kHz. The peak measuring range is 3 mA…28 A and the rms range is 2 mA…20 A. The main alarm response value IΔn is 30 mA…3 A, the prewarning 10…100 % x IΔn, operating uncertainty ±10 % and hysteresis -50…0 %. Permissible continuous residual current is 30 A.

Start-up delay is 0…900 s. Response delay ton is 0 s for IΔn up to 30 mA and 0…10 s above 30 mA, and delay on release toff is 0…900 s. Response time tae is at most 180 ms at 1 x IΔn, 130 ms at 2 x IΔn and 20 ms at 5 x and 10 x IΔn, with recovery time tb at most 500 ms. Fault-memory alarm messages can be switched on or off.

Terminals comprise alarm relays K1 and K2, a digital input I, a digital input/output Q and a multifunctional digital/analogue output M+. RS-485 with Modbus RTU runs at up to 115.2 kbits/s with device addresses 1…247 and cable up to 1200 m at 9.6 kbits/s; NFC is also provided.

The polycarbonate enclosure is rated UL94 V-0, IP20, for DIN rail mounting to IEC 60715, and weighs at most 125 g. Operating temperature is -25…+55 °C, transport -40…+85 °C and long-term storage -40…+70 °C. Overvoltage category is III, pollution degree 2 and altitude up to 2000 m. Standards include IEC 60947-2 Annex M, IEC 60755, VDE 0664-400, IEC 60364-4-41, IEC 60364-4-42, IEC 60364-4-43, IEC 60364-5-53 and UL508.

Technical specifications

Frequency rangeDC, 15 Hz…20 kHz
Measuring range (peak)3 mA…28 A
Measuring range rms2 mA…20 A
Response value main alarm IΔn (Type B)30 mA…3 A
Prewarning10…100 % x IΔn
Operating uncertainty±10 %
Hysteresis-50…0 %
Supply voltageDC 24 V; AC/DC 100…240 V
Start-up delay t0…900 s
Response delay ton0 s at IΔn ≤ 30 mA; 0…10 s at IΔn > 30 mA
Delay on release toff0…900 s
Response time tae≤ 180 ms (1 x IΔn); ≤ 130 ms (2 x IΔn); ≤ 20 ms (5 x and 10 x IΔn)
Recovery time tb≤ 500 ms
InterfacesRS-485 (Modbus RTU), NFC
Max. baud rate115.2 kbits/s
Device address1…247
Operating temperature-25…+55 °C
Degree of protectionIP20
Weight≤ 125 g

Part numbers

Show all part numbers (16)

B84606030, B84605030, B80609299, B94053110, B94053111, B94053112, B78120011, B78120021, B78120013, B78120023, B78120015, B78120025, B78120017, B78120027, B78120019, B78120029

How it compares with similar models

ParameterLINETRAXX® SmartDetect MRCDB425 AC/DC sensitive modular residual current deviceLINETRAXX® CEP410R-2 residual current monitor for the central earthing pointLINETRAXX® SmartDetect MRCD410R single-channel modular residual current deviceLINETRAXX® SmartDetect RCMS410/RCMS425 four-channel residual current monitor
Frequency rangeDC, 15 Hz…20 kHz42…70 Hz42…70 Hz15 Hz…20 kHz
Supply voltageDC 24 V; AC/DC 100…240 VDC 24 V; AC/DC 100…240 VDC 24 V; AC/DC 100…240 V (MRCD410R-2 only)DC 24 V; AC/DC 100…240 V
Operating temperature-25…+55 °C-25…+55 °C-25…+55 °C-40…+70 °C
Weight≤ 125 g≤ 100 g—≤ 55 g

Request a price and lead time

LINETRAXX® SmartDetect MRCDB425 AC/DC sensitive modular residual current device. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do the MRCDB425-D and MRCDB425-L differ?

The MRCDB425-D has a TFT display and the MRCDB425-L an LED strip for measured values. Both run on DC 24 V or AC/DC 100…240 V.

What response values and delays can be set?

The main alarm is 30 mA…3 A and the prewarning 10…100 % x IΔn. Start-up delay and delay on release are 0…900 s, and response delay reaches 10 s above 30 mA.

How fast does the device respond?

Response time tae is at most 180 ms at 1 x IΔn, 130 ms at 2 x IΔn and 20 ms at 5 x and 10 x IΔn.