LINETRAXX® RCMS460-D residual current monitor for earthed systems, 12 channels
Residual current monitor with 12 channels for detecting fault, residual and operating currents in earthed power supplies. It works with Type A and Type B current transformers and has an adjustable frequency response. Up to 90 monitors and 1080 channels on one BMS bus.
- Measuring channels
- 12
- Max. monitors in system
- 90
- Max. channels in system
- 1080
- Interface
- RS-485
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Earthed power supplies are the field of the LINETRAXX® RCMS460-D, which detects and evaluates fault, residual and operating currents. Measuring current transformers connected to its 12 channels supply the signals. Depending on the transformer selected, it handles alternating, pulsating or AC/DC sensitive residual currents (Type A and Type B of IEC/TR 60755).
The frequency response can be set for personnel protection, fire protection or plant protection, either 0…2000 Hz or 42…2000 Hz. Response ranges are 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz) and 100 mA…125 A (42…2000 Hz). The history memory keeps 300 data records and the data logger 300 data records per channel.
Two alarm relays are fitted, each with one changeover contact. An RS-485 interface with the BMS protocol links up to 90 monitors, which means up to 1080 channels in a system.
Versions: RCMS460-D-1 and RCMS460-D4-1 with supply DC 16…94 V / AC 16…72 V, 42…460 Hz; RCMS460-D-2 and RCMS460-D4-2 with supply DC 70…276 V / AC 70…276 V, 42…460 Hz. Codes: B94053001, B94053009, B94053002, B94053010. Reference standards are IEC/TR 60755 Type A and Type B and DGUV V3.
Accessories listed with the monitor are measuring current transformers of the CTUB100, CTBS25, CTAC, WR, WS and WF series, STEP-PS power supply units, COM465IP, CP907-I and CP915-I devices, the RS-485 repeater DI-1PSM (B95012044), MK2430-11 (B95100001) and MK2430-12 (B95100002) alarm indicators, and the frames XM460 (B990995) and XM490 (B990996).
Applications: personnel, fire and plant protection, monitoring of N conductors, monitoring of PE and equipotential bonding conductors, stationary electrical equipment, flammable atmospheres and EMC monitoring of TN-S systems.
Technical specifications
| Measuring channels | 12 |
|---|---|
| Max. monitors in system | 90 |
| Max. channels in system | 1080 |
| Interface | RS-485 |
| Bus protocol | BMS |
| Response ranges | 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz) |
| Frequency range | 0…2000 Hz, 42…2000 Hz |
| Alarm relays | Two relays with one changeover contact each |
| History memory | 300 data records |
| Data logger | 300 data records/channel |
| Supply D-1 / D4-1 | DC 16…94 V / AC 16…72 V, 42…460 Hz |
| Supply D-2 / D4-2 | DC 70…276 V / AC 70…276 V, 42…460 Hz |
| Transformer types | IEC/TR 60755: Type A, Type B |
Part numbers
Show all part numbers (4)
B94053001, B94053009, B94053002, B94053010
How it compares with similar models
| Parameter | LINETRAXX® RCMS460-D residual current monitor for earthed systems, 12 channels | LINETRAXX® RCMS490-D multi-channel residual current monitor, 12 channels | LINETRAXX® RCMS460-L 12-channel residual current monitoring relay for AC, pulsed DC and AC/DC | ISOSCAN® EDS440 insulation fault locator for IT systems, 12 channels |
|---|---|---|---|---|
| Interface | RS-485 | BMS bus (RS-485, BMS protocol) | — | RS-485 |
| Response ranges | 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz) | 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz) | 10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz) | — |
| Alarm relays | Two relays with one changeover contact each | Two relays with one changeover contact each | 2, one changeover contact each | — |
| Data logger | 300 data records/channel | 300 data records/channel | 300 data records per channel | — |
Request a price and lead time
LINETRAXX® RCMS460-D residual current monitor for earthed systems, 12 channels. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many channels does the RCMS460-D have?
12 measuring channels per device; up to 90 monitors on one BMS bus give up to 1080 channels.
Which interface and bus protocol are used?
RS-485 with the BMS protocol.
What is the adjustable frequency response for?
It is set for personnel, fire or plant protection, with ranges of 0…2000 Hz or 42…2000 Hz.