LINETRAXX® CMS460-D 12-Channel Load Current Evaluator, 100 mA…125 A
The LINETRAXX® CMS460-D reads measuring current transformers on 12 channels in TN, TT and IT systems. Response ranges 100 mA…125 A; up to 90 evaluators on one BMS bus give 1080 channels.
- Type
- Multichannel load current evaluator
- Measuring channels
- 12
- Maximum evaluators on the bus
- 90
- Maximum channels in a system
- 1080
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Sub-circuit currents in a distribution system are easy to miss until a fault has grown. The LINETRAXX® CMS460-D evaluates load currents in earthed and unearthed supplies from the signals of separate measuring current transformers, and it handles AC and pulsed DC currents in TN, TT and IT systems.
Each unit has 12 measuring channels with response ranges of 100 mA…125 A over 42…2000 Hz. The frequency response can be set for fire protection or for plant protection, and measured currents can be analysed for harmonics and THD. A history memory with date and time stamp holds 300 data records per channel.
Up to 90 evaluators can be linked on the BMS bus (RS-485 interface, BMS protocol), which makes 1080 monitored channels, or sub-circuits. Two alarm relays with changeover contact, a backlit graphical display, alarm LEDs and password protection of the settings are built in.
Typical duties are monitoring of loads and installations for load currents, monitoring of currents regarded as fire hazards in flammable atmospheres, EMC monitoring of TN systems for stray currents and additional N-PE connections, monitoring of N conductors for overload caused by harmonics, and monitoring of PE and equipotential bonding conductors.
The CMS460-D-1 takes AC 16…72 V, 42…460 Hz / DC 16…94 V (B94053017); the CMS460-D-2 takes AC 70…276 V, 42…460 Hz / DC 70…276 V (B94053018). Transformers come from the CTAC (closed), WR (rectangular), WS (split-core) and WF (flexible) series. For wider integration there are the DI-1DL interface repeater, the COM465IP gateway and the CP907-I and CP915-I protocol converters.
The relay mounts in DIN 43871 distribution boxes or on a rail to IEC 60715, or is screwed down with M4 screws. Standards listed are IEC 60664-1, IEC 60664-3, IEC 61010-1, IEC 60947-5-1, DIN VDE 0100-710, ÖVE/ÖNORM E 8007 and IEC 60364-7-710, and the device is RoHS compliant.
Technical specifications
| Type | Multichannel load current evaluator |
|---|---|
| Measuring channels | 12 |
| Maximum evaluators on the bus | 90 |
| Maximum channels in a system | 1080 |
| Response ranges | 100 mA…125 A |
| Frequency range | 42…2000 Hz |
| Supply voltage CMS460-D-1 | AC 16…72 V, 42…460 Hz / DC 16…94 V |
| Supply voltage CMS460-D-2 | AC 70…276 V, 42…460 Hz / DC 70…276 V |
| Interface | RS-485 |
| Protocol | BMS |
| Alarm relays | 2, changeover contact |
| History memory | 300 data records per channel |
| Mounting | DIN 43871, IEC 60715 |
Part numbers
Show all part numbers (2)
B94053017, B94053018
How it compares with similar models
| Parameter | LINETRAXX® CMS460-D 12-Channel Load Current Evaluator, 100 mA…125 A | LINETRAXX® RCMS490-L 12-channel residual current monitor for AC, pulsed DC and AC/DC | LINETRAXX® SmartDetect LCM410 Four-Channel Load Current Monitor, 6 mA…50 A | LINETRAXX® RCMS460-L 12-channel residual current monitoring relay for AC, pulsed DC and AC/DC |
|---|---|---|---|---|
| Response ranges | 100 mA…125 A | 10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz) | — | 10 mA…10 A (0…2000 Hz); 6 mA…20 A (42…2000 Hz); 100 mA…125 A (42…2000 Hz) |
| Alarm relays | 2, changeover contact | 2 changeover + one contact per channel | — | 2, one changeover contact each |
Request a price and lead time
LINETRAXX® CMS460-D 12-Channel Load Current Evaluator, 100 mA…125 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many channels can one bus carry?
Each CMS460-D has 12 channels, and up to 90 evaluators on the BMS bus give up to 1080 channels.
Which measuring current transformers fit?
The CTAC (closed), WR (rectangular), WS (split-core) and WF (flexible) series.
How do the CMS460-D-1 and CMS460-D-2 differ?
By supply voltage. The D-1 takes AC 16…72 V / DC 16…94 V (B94053017); the D-2 takes AC 70…276 V / DC 70…276 V (B94053018).
Similar equipment from other manufacturers