LINETRAXX® VMD460-NA Network and System Protection Relay (NS Protection)

The LINETRAXX® VMD460-NA disconnects a power generation system from the grid through coupling switches when voltage or frequency leave permissible limits. Range 0…300 V (L-N) and 0…520 V (L-L), supply AC/DC 100…240 V.

Type
Network and system protection relay (NS protection)
Supply voltage
AC/DC 100…240 V
Monitoring voltage range
0…300 (L-N) / 0…520 (L-L) V
Monitoring frequency range
45…65 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

A generating plant running in parallel with the public grid must drop off the moment the grid goes out of tolerance. The LINETRAXX® VMD460-NA is an external network and system protection (NS protection) relay that does this: it disconnects the power generation system from the grid through coupling switches on inadmissible voltage or frequency values. Listed uses are central NS protection (VDE-AR-N 4105), protective disconnection (VDE-AR-N 4110, BDEW), Interface Protection (IP) and the automatic disconnection device between a generating plant in parallel with the network and the public network.

The relay continuously monitors phase voltage and line-to-line voltage over 0…300 V (L-N) and 0…520 V (L-L), and frequency over 45…65 Hz. When measurements fall outside the thresholds required by standards such as G99, G98 and VDE-AR-N 4105, the relays switch and disconnect the generator. Island network detection works by df/dt and vector shift, and remote shutdown is possible through a ripple control signal receiver.

Preset basic settings for national standards are stored, including G99/1-4:2019 and G98/1-4:2019. The relay is single-fault tolerant, has a backlit graphic LC display and keeps the last 300 distribution network faults with a time stamp. Data exchange and parameter setting use the RS-485 interface.

The supply is AC/DC 100…240 V with a supply frequency range of 0 / 40…70 Hz (version VMD460-NA-D-2, part number B93010045).

Standards and requirements listed are VDE-AR-N 4105:2018-11, VDE-AR-N 4110:2023-09, BDEW technical guideline 2008, G99/1:2019, G59/2, G59/3, G98/1:2019, G83/2, CEI 0-21, C10/11:2012-06 and DIN V VDE V 0126-1-1. CE and UKCA declarations exist.

Technical specifications

TypeNetwork and system protection relay (NS protection)
Supply voltageAC/DC 100…240 V
Monitoring voltage range0…300 (L-N) / 0…520 (L-L) V
Monitoring frequency range45…65 Hz
Supply frequency range0 / 40…70 Hz
Island network detectiondf/dt, vector shift
InterfaceRS-485
Memorylast 300 network faults with time stamp
Main standardsG99/1-4:2019, G98/1-4:2019, VDE-AR-N 4105:2018-11, VDE-AR-N 4110:2023-09

Part numbers

Show all part numbers (1)

B93010045

Request a price and lead time

LINETRAXX® VMD460-NA Network and System Protection Relay (NS Protection). We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which standards are preset in the relay?

Basic settings for G99/1-4:2019 and G98/1-4:2019. VDE-AR-N 4105, VDE-AR-N 4110, the BDEW guideline 2008, CEI 0-21 and C10/11 are also listed.

How is an island network detected?

By the rate of change of frequency df/dt and by vector shift.

What voltage range is monitored?

0…300 V phase to neutral (L-N) and 0…520 V line to line (L-L).