LINETRAXX® VMD460-NA Network and System Protection Relay (NS Protection)
The LINETRAXX® VMD460-NA disconnects a power generation system from the grid through coupling switches when voltage or frequency leave permissible limits. Range 0…300 V (L-N) and 0…520 V (L-L), supply AC/DC 100…240 V.
- Type
- Network and system protection relay (NS protection)
- Supply voltage
- AC/DC 100…240 V
- Monitoring voltage range
- 0…300 (L-N) / 0…520 (L-L) V
- Monitoring frequency range
- 45…65 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A generating plant running in parallel with the public grid must drop off the moment the grid goes out of tolerance. The LINETRAXX® VMD460-NA is an external network and system protection (NS protection) relay that does this: it disconnects the power generation system from the grid through coupling switches on inadmissible voltage or frequency values. Listed uses are central NS protection (VDE-AR-N 4105), protective disconnection (VDE-AR-N 4110, BDEW), Interface Protection (IP) and the automatic disconnection device between a generating plant in parallel with the network and the public network.
The relay continuously monitors phase voltage and line-to-line voltage over 0…300 V (L-N) and 0…520 V (L-L), and frequency over 45…65 Hz. When measurements fall outside the thresholds required by standards such as G99, G98 and VDE-AR-N 4105, the relays switch and disconnect the generator. Island network detection works by df/dt and vector shift, and remote shutdown is possible through a ripple control signal receiver.
Preset basic settings for national standards are stored, including G99/1-4:2019 and G98/1-4:2019. The relay is single-fault tolerant, has a backlit graphic LC display and keeps the last 300 distribution network faults with a time stamp. Data exchange and parameter setting use the RS-485 interface.
The supply is AC/DC 100…240 V with a supply frequency range of 0 / 40…70 Hz (version VMD460-NA-D-2, part number B93010045).
Standards and requirements listed are VDE-AR-N 4105:2018-11, VDE-AR-N 4110:2023-09, BDEW technical guideline 2008, G99/1:2019, G59/2, G59/3, G98/1:2019, G83/2, CEI 0-21, C10/11:2012-06 and DIN V VDE V 0126-1-1. CE and UKCA declarations exist.
Technical specifications
| Type | Network and system protection relay (NS protection) |
|---|---|
| Supply voltage | AC/DC 100…240 V |
| Monitoring voltage range | 0…300 (L-N) / 0…520 (L-L) V |
| Monitoring frequency range | 45…65 Hz |
| Supply frequency range | 0 / 40…70 Hz |
| Island network detection | df/dt, vector shift |
| Interface | RS-485 |
| Memory | last 300 network faults with time stamp |
| Main standards | G99/1-4:2019, G98/1-4:2019, VDE-AR-N 4105:2018-11, VDE-AR-N 4110:2023-09 |
Part numbers
Show all part numbers (1)
B93010045
Request a price and lead time
LINETRAXX® VMD460-NA Network and System Protection Relay (NS Protection). We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which standards are preset in the relay?
Basic settings for G99/1-4:2019 and G98/1-4:2019. VDE-AR-N 4105, VDE-AR-N 4110, the BDEW guideline 2008, CEI 0-21 and C10/11 are also listed.
How is an island network detected?
By the rate of change of frequency df/dt and by vector shift.
What voltage range is monitored?
0…300 V phase to neutral (L-N) and 0…520 V line to line (L-L).