LINETRAXX® GM420 PE Conductor Loop Monitoring Relay, 0…100 Ω
The LINETRAXX® GM420 checks the resistance of PE conductor connections in AC and de-energised systems and reads extraneous voltage up to AC 50 V. Two alarm relays; supply versions AC 16…72 V / DC 9,6…94 V and AC/DC 70…300 V.
- Type
- PE conductor loop monitoring relay
- Supply voltage GM420-D-1
- AC 16…72 V / DC 9,6…94 V
- Supply voltage GM420-D-2
- AC/DC 70…300 V
- Supply frequency range
- 15…460 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A broken protective conductor often goes unnoticed until someone needs it. The LINETRAXX® GM420 loop monitor watches the ohmic resistance of PE conductor connections in AC systems and in de-energised systems, and flags a wire interruption in an electrical installation. Typical jobs are loop monitoring of motors and monitoring of earthing systems.
The relay measures loop resistance over 0…100 Ω with a measuring current of DC 20 mA and a measuring voltage of up to DC 24 V. It also reads any AC extraneous voltage Uf in the range AC 0…50 V. Both values appear on a multi-function LC display. When the resistance rises above the set response value, the alarm is activated and stored in the fault memory.
Two separate alarm relays, each with one changeover contact, are fitted, with an electrical endurance of 10000 switching operations. Start-up, response and release delays are adjustable, as is the switching hysteresis, and the settings can be locked with a password.
Two supply versions exist. The GM420-D-1 runs from AC 16…72 V / DC 9,6…94 V and the GM420-D-2 from AC/DC 70…300 V, both at 15…460 Hz with a power consumption of up to 3,5 VA. Rated insulation voltage is 400 V, overvoltage category 4 kV, pollution degree III. Extraneous voltage of up to 440 V is permitted.
The 36 mm wide enclosure clips onto a DIN rail or is screwed down with mounting clip B98060008. Mounting frame XM420 (B990994) is available as an option. Commissioning and periodic verification are work for a qualified electrician. The design follows IEC 60664-1, IEC 60664-3, IEC 61010-1, IEC 60947-5-1 and IEC 60364-6, and the device is RoHS compliant.
Technical specifications
| Type | PE conductor loop monitoring relay |
|---|---|
| Supply voltage GM420-D-1 | AC 16…72 V / DC 9,6…94 V |
| Supply voltage GM420-D-2 | AC/DC 70…300 V |
| Supply frequency range | 15…460 Hz |
| Power consumption | ≤ 3,5 VA |
| Loop resistance measuring range | 0…100 Ω |
| Measuring current | DC 20 mA |
| Measuring voltage | ≤ DC 24 V |
| Extraneous voltage measuring range | AC 0…50 V |
| Permissible extraneous voltage | ≤ 440 V |
| Rated insulation voltage | 400 V |
| Switching elements | 2 x 1 changeover contact |
| Electrical endurance | 10000 switching operations |
| Enclosure width | 36 mm |
Part numbers
Show all part numbers (6)
B73082001, B93082001, B73082002, B93082002, B98060008, B990994
How it compares with similar models
| Parameter | LINETRAXX® GM420 PE Conductor Loop Monitoring Relay, 0…100 Ω | LINETRAXX® VMD423/VMD423H Voltage and Frequency Monitor for 3(N)AC up to 500 V | LINETRAXX® VMD258 Undervoltage/Overvoltage Relay for 3AC Systems up to 690 V | LINETRAXX® CMD420/CMD421 AC Current Monitoring Relays for x/1A and x/5A Transformers |
|---|---|---|---|---|
| Type | PE conductor loop monitoring relay | Voltage and frequency monitoring relay for 3(N)AC | Undervoltage/overvoltage relay, 3AC | AC current monitoring relay |
| Supply frequency range | 15…460 Hz | 15…460 Hz | 45…66 Hz | 15…460 Hz |
| Power consumption | ≤ 3,5 VA | ≤ 3,5 VA (VMD423-D), ≤ 5 VA (VMD423H) | ≤ 10 VA | — |
| Rated insulation voltage | 400 V | 400 V | — | AC 250 V |
| Electrical endurance | 10000 switching operations | 10000 switching operations | 10000 | — |
Request a price and lead time
LINETRAXX® GM420 PE Conductor Loop Monitoring Relay, 0…100 Ω. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What loop resistance range does the GM420 cover?
It measures 0…100 Ω and also displays extraneous voltage in the range AC 0…50 V.
How do the GM420-D-1 and GM420-D-2 differ?
Only in supply voltage. The D-1 takes AC 16…72 V / DC 9,6…94 V and the D-2 takes AC/DC 70…300 V; both measure 0…100 Ω.
How many alarm outputs does it have?
Two separate alarm relays, each with one changeover contact. Start-up, response and release delays are set independently.