International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® CMD420/CMD421 AC Current Monitoring Relays for x/1A and x/5A Transformers

The LINETRAXX® CMD420 and CMD421 monitor three AC currents through standard current transformers, x/1A and x/5A respectively. Overcurrent, undercurrent or window function; transformation ratio n up to 2000.

Type
AC current monitoring relay
CMD420 input
via current transformer x/1A
CMD421 input
via current transformer x/5A
Response value CMD420
0,1…1 A x n

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The CMD420 and CMD421 pair of LINETRAXX® current monitoring relays is built around three measuring inputs. They read AC currents as r.m.s. values from standard current transformers, the CMD420 on x/1A and the CMD421 on x/5A, and check them for overcurrent, undercurrent or a window discriminator band.

The transformation ratio n is adjustable from 1…2000. Response values are 0,1…1 A x n on the CMD420 and 0,5…5 A x n on the CMD421. A digital LC display shows the measured values, and the front carries LEDs for Power On, Alarm 1 and Alarm 2, a Test/Reset button and menu buttons. A fault memory is included.

Two separate alarm relays, K1 and K2, each have one changeover contact. Start-up, response and release delays can be set, and so can the switching hysteresis. The minimum contact rating is 1 mA at AC/DC ≥ 10 V.

A separate supply voltage is needed. The D-1 version takes AC 16…72 V / DC 9,6…94 V and the D-2 version takes AC/DC 70…300 V, both at 15…460 Hz. Rated insulation voltage is AC 250 V, rated impulse voltage 6 kV at pollution degree III, and the voltage test is 3,536 kV.

Listed uses include current consumption of motors such as pumps, elevators and cranes, lighting and heating circuits, charging stations, emergency lighting, screw conveyors in sewage plants, dust removal in wood working, and the 70 % agreement under EEG 2012 for PV inverters.

The 93 x 70,5 x 45 mm enclosure (36 mm wide) mounts on a DIN rail or is screwed down with clip B98060008; frame XM420 (B990994) is optional. Terminals are push-wire (B7…) or screw-type (B9…). The relays follow IEC 60664-1, IEC 60664-3, IEC 61010-1 and IEC 60947-5-1, with UKCA and CE declarations of conformity.

Technical specifications

TypeAC current monitoring relay
CMD420 inputvia current transformer x/1A
CMD421 inputvia current transformer x/5A
Response value CMD4200,1…1 A x n
Response value CMD4210,5…5 A x n
Transformation ratio n1…2000
Supply voltage D-1AC 16…72 V / DC 9,6…94 V
Supply voltage D-2AC/DC 70…300 V
Supply frequency range15…460 Hz
Rated insulation voltageAC 250 V
Rated impulse voltage / pollution degree6 kV / III
Contacts2 x 1 changeover (K1, K2)
Minimum contact rating1 mA at AC/DC ≥ 10 V
Dimensions93 x 70,5 x 45 mm (36 mm width)

Part numbers

Show all part numbers (10)

B73060006, B93060006, B73060007, B93060007, B73060008, B93060008, B73060009, B93060009, B98060008, B990994

How it compares with similar models

ParameterLINETRAXX® CMD420/CMD421 AC Current Monitoring Relays for x/1A and x/5A TransformersLINETRAXX® VMD423/VMD423H Voltage and Frequency Monitor for 3(N)AC up to 500 VLINETRAXX® RCM410R-24/-2 single-channel residual current monitoring relay, 10 mA…30 ALINETRAXX® GM420 PE Conductor Loop Monitoring Relay, 0…100 Ω
TypeAC current monitoring relayVoltage and frequency monitoring relay for 3(N)ACA (AC and pulsed DC)PE conductor loop monitoring relay
Rated insulation voltageAC 250 V400 V—400 V

Request a price and lead time

LINETRAXX® CMD420/CMD421 AC Current Monitoring Relays for x/1A and x/5A Transformers. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What separates the CMD420 from the CMD421?

The transformer input. The CMD420 works with x/1A (response 0,1…1 A x n) and the CMD421 with x/5A (0,5…5 A x n).

Which monitoring functions are available?

Overcurrent, undercurrent and window discriminator. Start-up, response and release delays are adjustable.

Does it need its own supply?

Yes. The D-1 version runs from AC 16…72 V / DC 9,6…94 V and the D-2 version from AC/DC 70…300 V.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides