
LINETRAXX® VMD423/VMD423H Voltage and Frequency Monitor for 3(N)AC up to 500 V
The LINETRAXX® VMD423 and VMD423H monitor voltage and frequency in 3(N)AC systems up to 500 V in line with DIN V VDE V 0126-1-1. Alarm relays switch within ≤ 80 ms; supply is separate or taken from the system.
- Type
- Voltage and frequency monitoring relay for 3(N)AC
- Nominal system voltage Un
- 0…500 V
- Supply voltage VMD423-D-1
- AC 16…72 V / DC 9,6…94 V
- Supply voltage VMD423-D-2
- AC/DC 70…300 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Where a private generator runs in parallel with the public low-voltage grid, an automatic switching point has to watch both voltage and frequency. The LINETRAXX® VMD423 and VMD423H do this in 3(N)AC systems with nominal voltages up to 500 V. Listed applications are photovoltaic systems, CHPs (combined heat and power plants), wind power and hydro power plants, including private generation systems above 30 kW.
The relay measures voltage and frequency continuously and compares them with set limits. It watches undervoltage, overvoltage, underfrequency and overfrequency, plus asymmetry, phase failure and phase sequence. When a limit is exceeded, the alarm relays switch within ≤ 80 ms. Start-up, response and release delays are adjustable. An LC display with measured value memory is fitted, together with two separate alarm relays K1 and K2, each with one changeover contact and an electrical endurance of 10000.
Three versions exist. The VMD423-D-1 takes AC 16…72 V / DC 9,6…94 V, the VMD423-D-2 takes AC/DC 70…300 V, and the VMD423H-D-3 draws its supply from the monitored system Un 3(N)AC 0…500 V. Measuring range is AC 0…288 V (L-N) and AC 0…500 V (L-L), rated frequency fn is 40…65 Hz and supply frequency is 15…460 Hz. Power consumption is up to 3,5 VA (VMD423-D) and 5 VA (VMD423H).
Rated insulation voltage is 400 V, rated impulse voltage 4 kV and pollution degree III. Dimensions are 93 x 70,5 x 66,5 mm for the VMD423-D and 93 x 74,5 x 66,5 mm for the VMD423H. Mounting is on a DIN rail or by screws, using clip B98060008 or frame XM420 (B990994), with push-wire or screw-type terminals.
A certificate of non objection exists under DIN V VDE V 0126-1-1:2006-02, and the relays follow EN 50438:2007, C10/11, IEC 60664-1, IEC 60664-3, IEC 61010-1 and IEC 60947-5-1. UKCA and CE declarations are available and the device is RoHS compliant.
Technical specifications
| Type | Voltage and frequency monitoring relay for 3(N)AC |
|---|---|
| Nominal system voltage Un | 0…500 V |
| Supply voltage VMD423-D-1 | AC 16…72 V / DC 9,6…94 V |
| Supply voltage VMD423-D-2 | AC/DC 70…300 V |
| Supply voltage VMD423H-D-3 | from the system Un 3(N)AC 0…500 V |
| Supply frequency range | 15…460 Hz |
| Rated frequency fn | 40…65 Hz |
| Measuring range (r.m.s.), L-N | AC 0…288 V |
| Measuring range (r.m.s.), L-L | AC 0…500 V |
| Rated insulation voltage | 400 V |
| Rated impulse voltage | 4 kV |
| Contacts | 2 x 1 changeover (K1, K2) |
| Electrical endurance | 10000 switching operations |
| Power consumption | ≤ 3,5 VA (VMD423-D), ≤ 5 VA (VMD423H) |
Part numbers
Show all part numbers (8)
B73010020, B93010020, B73010021, B93010021, B73010022, B93010022, B98060008, B990994
How it compares with similar models
| Parameter | LINETRAXX® VMD423/VMD423H Voltage and Frequency Monitor for 3(N)AC up to 500 V | LINETRAXX® GM420 PE Conductor Loop Monitoring Relay, 0…100 Ω | LINETRAXX® VMD421H voltage and frequency monitoring relay, 70…500 V | LINETRAXX® VMD420 voltage and frequency monitoring relay for 3(N)AC up to 500 V |
|---|---|---|---|---|
| Rated frequency fn | 40…65 Hz | — | 15…460 Hz | DC, 15…460 Hz |
| Measuring range (r.m.s.), L-N | AC 0…288 V | — | AC 0…288 V | AC/DC 0…288 V |
| Measuring range (r.m.s.), L-L | AC 0…500 V | — | AC 0…500 V | AC/DC 0…500 V |
| Power consumption | ≤ 3,5 VA (VMD423-D), ≤ 5 VA (VMD423H) | ≤ 3,5 VA | ≤ 6 VA | ≤ 4 VA |
Request a price and lead time
LINETRAXX® VMD423/VMD423H Voltage and Frequency Monitor for 3(N)AC up to 500 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How does the VMD423H differ from the VMD423?
The VMD423H-D-3 is supplied from the monitored system Un 3(N)AC 0…500 V and takes up to 5 VA; the VMD423-D has a separate supply and takes up to 3,5 VA.
Which grid parameters are monitored?
Undervoltage, overvoltage, underfrequency, overfrequency, asymmetry, phase failure and phase sequence.
How fast do the alarm relays switch?
Within ≤ 80 ms once a limit is exceeded.
Similar equipment from other manufacturers






