International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® VME420 voltage and frequency monitoring relay for AC/DC 0…300 V

Relay for undervoltage, overvoltage, underfrequency and overfrequency monitoring in AC/DC systems of 0…300 V, 15…460 Hz. It needs a separate supply voltage Us, available in two versions. Two alarm relays, 36 mm wide enclosure, suitable for railway vehicles per DIN EN 45545-2:2016.

Supply voltage Us VME420-D-1
DC 9.6…94 V / AC 16…72 V
Supply voltage Us VME420-D-2
DC 70…300 V / AC 70…300 V
Frequency range Us
15…460 Hz
Measuring range (r.m.s.)
AC/DC 0…300 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

AC/DC systems with nominal voltages up to 300 V and frequencies from 15 to 460 Hz are monitored by the LINETRAXX® VME420. The functions < U, > U, < f and > f are selectable, and start-up, response and release delays are adjustable.

This relay requires a separate supply voltage Us. VME420-D-1 takes DC 9.6…94 V / AC 16…72 V; VME420-D-2 takes DC 70…300 V / AC 70…300 V. The supply frequency range is 15…460 Hz and power consumption is ≤ 4 VA.

The measuring range (r.m.s.) is AC/DC 0…300 V and the rated frequency fn is DC, 15…460 Hz. A Preset function assigns parameters automatically. Measured values appear on a digital LC display with a measured value memory, settings are password protected, and the operating principle of the alarm relays (N/C or N/O) can be selected.

The two alarm relays K1 and K2 each have one changeover contact (2 x 1). Electrical endurance is 10000 switching operations, utilisation categories are AC-13/AC-14/DC-12/DC-12/DC-12, rated operational voltage 230 V/230 V/24 V/110 V/220 V, rated operational current 5 A/3 A/1 A/0.2 A/0.1 A, and the minimum contact rating 1 mA at AC/DC ≥ 10 V.

Rated insulation voltage is 250 V, rated impulse voltage 4 kV with overvoltage category III, and pollution degree 3. Standards: IEC 60664-1, IEC 60664-3, IEC 60947-5-1 and DIN EN 45545-2:2016.

The enclosure is 36 mm wide, 93 x 70.5 x 45 mm overall. Mounting is on a DIN rail or by screws, with the clip B98060008; the frame XM420 (B990994) is also listed. Push-wire terminals: B73010001, B73010002. Screw-type terminals: B93010001, B93010002.

Uses include single-phase voltage and frequency monitoring of machines and installations, earth fault monitoring in medium-voltage systems through voltage transformers, battery systems, switching at a certain voltage level, and railway vehicles.

Technical specifications

Supply voltage Us VME420-D-1DC 9.6…94 V / AC 16…72 V
Supply voltage Us VME420-D-2DC 70…300 V / AC 70…300 V
Frequency range Us15…460 Hz
Measuring range (r.m.s.)AC/DC 0…300 V
Rated frequency fnDC, 15…460 Hz
Power consumption≤ 4 VA
Rated insulation voltage250 V
Rated impulse voltage/overvoltage category4 kV/III
Pollution degree3
Number of changeover contacts2 x 1 (K1, K2)
Electrical endurance10000 switching operations
Rated operational voltage230 V/230 V/24 V/110 V/220 V
Rated operational current5 A/3 A/1 A/0.2 A/0.1 A
Dimensions93 x 70.5 x 45 mm (36 mm width)

Part numbers

Show all part numbers (6)

B73010001, B93010001, B73010002, B93010002, B98060008, B990994

How it compares with similar models

ParameterLINETRAXX® VME420 voltage and frequency monitoring relay for AC/DC 0…300 VLINETRAXX® VME421H voltage and frequency monitoring relay for AC/DC, no separate supplyLINETRAXX® VMD421H voltage and frequency monitoring relay, 70…500 VLINETRAXX® VMD420 voltage and frequency monitoring relay for 3(N)AC up to 500 V
Rated frequency fnDC, 15…460 HzDC, 15…460 Hz15…460 HzDC, 15…460 Hz
Power consumption≤ 4 VA≤ 6 VA≤ 6 VA≤ 4 VA
Rated insulation voltage250 V250 V400 V400 V
Pollution degree33IIIIII
Dimensions93 x 70.5 x 45 mm (36 mm width)93 x 90 x 66.5 mm93 x 90 x 66.5 mm93 x 70.5 x 74.5 mm

Request a price and lead time

LINETRAXX® VME420 voltage and frequency monitoring relay for AC/DC 0…300 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the VME420 need a separate supply voltage?

Yes. Us is DC 9.6…94 V / AC 16…72 V for D-1 and DC 70…300 V / AC 70…300 V for D-2.

What are the measuring and frequency ranges?

The measuring range is AC/DC 0…300 V and the rated frequency fn is DC, 15…460 Hz.

Is it suitable for railway vehicles?

Yes, application in railway vehicles per DIN EN 45545-2:2016 is listed.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides