LINETRAXX® VMD420 voltage and frequency monitoring relay for 3(N)AC up to 500 V
Voltage and frequency monitoring relay for 3(N)AC systems with nominal voltages up to 500 V. It measures r.m.s. values of AC and DC and covers undervoltage, overvoltage, underfrequency, overfrequency, asymmetry, phase failure and phase sequence. Two supply voltage versions; suitable for railway vehicles per DIN EN 45545-2:2016.
- Nominal system voltage
- up to 500 V, 3(N)AC
- Measuring range (r.m.s.), L-N
- AC/DC 0…288 V
- Measuring range (r.m.s.), L-L
- AC/DC 0…500 V
- Rated frequency fn
- DC, 15…460 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Systems of 3(N)AC with nominal voltages up to 500 V are the field of the LINETRAXX® VMD420. The relay detects undervoltage, overvoltage, underfrequency and overfrequency, and the monitoring of asymmetry, phase failure and phase sequence can be selected.
R.m.s. values are measured for both AC and DC. The measuring range is AC/DC 0…288 V (L-N) and AC/DC 0…500 V (L-L); the rated frequency fn is DC, 15…460 Hz and the frequency range is 10…500 Hz. Readings are shown on an LC display. Response values, start-up delay, response delay and release delay are adjustable, a Preset function assigns parameters automatically from the nominal voltage, and a fault memory and password protection are included.
Two versions differ in supply voltage: VMD420-D-1 takes AC 16…72 V / DC 9.6…94 V, VMD420-D-2 takes AC/DC 70…300 V. Power consumption is ≤ 4 VA.
Alarm relays K1 and K2 each have one changeover contact (2 x 1), with an electrical endurance of 10000 switching operations. Rated insulation voltage is 400 V, rated impulse voltage 4 kV and pollution degree III. Standards: IEC 60664-1, IEC 60664-3, IEC 61010-1, IEC 60947-5-1 and DIN EN 45545-2:2016.
The unit measures 93 x 70.5 x 74.5 mm and mounts on a DIN rail or with screws, using the clip B98060008; the frame XM420 (B990994) is also listed. Terminals are push-wire or screw-type: B73010005, B73010005(W), B93010005, B93010005(W), B73010006, B93010006. In railway vehicles, the distance to adjacent components must follow DIN EN 45545-2.
Applications include voltage-sensitive machines and electrical installations, switching on and off at a certain voltage level, stand-by and emergency supply systems, supply voltage monitoring of portable loads and transformer protection.
Technical specifications
| Nominal system voltage | up to 500 V, 3(N)AC |
|---|---|
| Measuring range (r.m.s.), L-N | AC/DC 0…288 V |
| Measuring range (r.m.s.), L-L | AC/DC 0…500 V |
| Rated frequency fn | DC, 15…460 Hz |
| Frequency range | 10…500 Hz |
| Supply voltage VMD420-D-1 | AC 16…72 V / DC 9.6…94 V |
| Supply voltage VMD420-D-2 | AC/DC 70…300 V |
| Power consumption | ≤ 4 VA |
| Rated insulation voltage | 400 V |
| Rated impulse voltage | 4 kV |
| Pollution degree | III |
| Number of changeover contacts | 2 x 1 (K1, K2) |
| Electrical endurance | 10000 switching operations |
| Dimensions | 93 x 70.5 x 74.5 mm |
Part numbers
Show all part numbers (7)
B73010005, B73010005(W), B93010005, B93010005(W), B73010006, B93010006, B98060008
How it compares with similar models
| Parameter | LINETRAXX® VMD420 voltage and frequency monitoring relay for 3(N)AC up to 500 V | LINETRAXX® VMD421H voltage and frequency monitoring relay, 70…500 V | LINETRAXX® VME421H voltage and frequency monitoring relay for AC/DC, no separate supply | LINETRAXX® VME420 voltage and frequency monitoring relay for AC/DC 0…300 V |
|---|---|---|---|---|
| Rated frequency fn | DC, 15…460 Hz | 15…460 Hz | DC, 15…460 Hz | DC, 15…460 Hz |
| Power consumption | ≤ 4 VA | ≤ 6 VA | ≤ 6 VA | ≤ 4 VA |
| Rated insulation voltage | 400 V | 400 V | 250 V | 250 V |
| Pollution degree | III | III | 3 | 3 |
| Dimensions | 93 x 70.5 x 74.5 mm | 93 x 90 x 66.5 mm | 93 x 90 x 66.5 mm | 93 x 70.5 x 45 mm (36 mm width) |
Request a price and lead time
LINETRAXX® VMD420 voltage and frequency monitoring relay for 3(N)AC up to 500 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the VMD420 versions differ?
In supply voltage: VMD420-D-1 takes AC 16…72 V / DC 9.6…94 V and VMD420-D-2 takes AC/DC 70…300 V.
Can the relay measure DC voltage?
Yes. The measuring range is AC/DC 0…288 V (L-N) and AC/DC 0…500 V (L-L), with a rated frequency fn of DC, 15…460 Hz.
Is the VMD420 suitable for railway vehicles?
Yes, application in railway vehicles is covered by DIN EN 45545-2:2016, with attention to the distance from adjacent components.