International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® VMD421H voltage and frequency monitoring relay, 70…500 V

Multi-functional voltage and frequency relay for 3(N)AC systems of 70…500 V. It watches undervoltage, overvoltage, frequency, asymmetry, phase failure and phase sequence. Two alarm relays, 36 mm wide enclosure, DIN rail or screw mounting.

Nominal system voltage Un
70…500 V
Rated frequency fn
15…460 Hz
Measuring range (r.m.s.), L-N
AC 0…288 V
Measuring range (r.m.s.), L-L
AC 0…500 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The VMD421H of the LINETRAXX® range supervises 3(N)AC systems with a nominal system voltage Un of 70…500 V and a rated frequency fn of 15…460 Hz. It responds to undervoltage and overvoltage as well as to frequency deviations. Asymmetry, phase failure and phase sequence monitoring can be selected, and a window function is available.

Voltages are measured as r.m.s. values, with a measuring range of AC 0…288 V line to neutral (L-N) and AC 0…500 V line to line (L-L). No separate supply voltage is needed, because the relay has an integrated energy backup. Start-up, response and release delays are adjustable. Measured values appear on a digital LC display and are stored in a measured value memory. Further functions are the Preset function for automatic parameter setting, automatic and manual self test, a fault memory and password protection.

Alarms are assigned to two relays, K1 and K2, each with one changeover contact (2 x 1). The contacts are rated for 10000 switching operations in utilisation categories AC-13/AC-14/DC-12, at rated operational voltages of 230 V/230 V/24 V/110 V/220 V and rated operational currents of 5 A/3 A/1 A/0.2 A/0.1 A. The minimum contact rating is 1 mA at AC/DC ≥ 10 V. Power consumption is ≤ 6 VA.

Rated insulation voltage is 400 V, rated impulse voltage 4 kV, pollution degree III. The design follows IEC 60664-1, IEC 60664-3, IEC 61010-1 and IEC 60947-5-1.

The enclosure is 36 mm wide and measures 93 x 90 x 66.5 mm. It is fitted on a DIN rail or screwed to a surface using the mounting clip B98060008; the mounting frame XM420 (B990994) is also listed. Terminals come as push-wire (B73010007) or screw-type (B93010007).

Typical uses are voltage-sensitive machines and electrical installations, switching equipment on and off at a set voltage level, stand-by and emergency supply systems, supply voltage monitoring of portable loads, protection of three-phase motors against phase failure, and transformer protection.

Technical specifications

Nominal system voltage Un70…500 V
Rated frequency fn15…460 Hz
Measuring range (r.m.s.), L-NAC 0…288 V
Measuring range (r.m.s.), L-LAC 0…500 V
Rated insulation voltage400 V
Rated impulse voltage4 kV
Pollution degreeIII
Power consumption≤ 6 VA
Number of changeover contacts2 x 1 (K1, K2)
Electrical endurance10000 switching operations
Utilisation categoryAC-13/AC-14/DC-12
Rated operational voltage230 V/230 V/24 V/110 V/220 V
Rated operational current5 A/3 A/1 A/0.2 A/0.1 A
Enclosure width36 mm
Dimensions93 x 90 x 66.5 mm

Part numbers

Show all part numbers (4)

B73010007, B93010007, B98060008, B990994

How it compares with similar models

ParameterLINETRAXX® VMD421H voltage and frequency monitoring relay, 70…500 VLINETRAXX® VME421H voltage and frequency monitoring relay for AC/DC, no separate supplyLINETRAXX® VMD420 voltage and frequency monitoring relay for 3(N)AC up to 500 VLINETRAXX® VME420 voltage and frequency monitoring relay for AC/DC 0…300 V
Rated frequency fn15…460 HzDC, 15…460 HzDC, 15…460 HzDC, 15…460 Hz
Rated insulation voltage400 V250 V400 V250 V
Pollution degreeIII3III3
Power consumption≤ 6 VA≤ 6 VA≤ 4 VA≤ 4 VA
Dimensions93 x 90 x 66.5 mm93 x 90 x 66.5 mm93 x 70.5 x 74.5 mm93 x 70.5 x 45 mm (36 mm width)

Request a price and lead time

LINETRAXX® VMD421H voltage and frequency monitoring relay, 70…500 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What voltage and frequency range does the VMD421H monitor?

Nominal system voltage Un is 70…500 V and rated frequency fn is 15…460 Hz. The measuring range is AC 0…288 V (L-N) and AC 0…500 V (L-L).

Does the relay need a separate supply voltage?

No. It has an integrated energy backup, so no external supply voltage is required.

Which terminal versions are listed?

Push-wire terminals (B73010007) and screw-type terminals (B93010007). Mounting is on a DIN rail or with screws.