International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® VMD461 with CD440 Multifunction Voltage Monitoring Relay, up to 1200 V DC/3AC

The LINETRAXX® VMD461 monitors voltage and frequency in DC, AC and 3(N)AC systems. With the CD440 coupling device the range extends to DC/3AC 1200 V or 1AC/3NAC 690 V. Supply AC/DC 100…240 V.

Type
Multifunction voltage monitoring relay
Supply voltage Us
AC/DC 100…240 V
Monitoring range (with CD440)
DC/3AC 1200 V or 1AC/3NAC 690 V
Monitoring functions
3-stage voltage and frequency, ROCOF df/dt, vector shift, unbalance, phase sequence

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Grid-side voltage faults come in many shapes, from a lost phase to a frequency that drifts. The LINETRAXX® VMD461 is a multifunction voltage monitoring relay for DC, AC and 3(N)AC systems, and with the optional CD440 coupling device it covers systems up to DC/3AC 1200 V or 1AC/3NAC 690 V. The relay itself runs from AC/DC 100…240 V (version VMD461-D-2).

It measures phase and line-to-line voltages as r.m.s. values and displays them continuously. Available functions are 3-stage voltage and frequency monitoring, ROCOF df/dt monitoring, vector shift monitoring, unbalance monitoring and phase sequence monitoring. The alarm relays act after set delay times on undervoltage, overvoltage, frequency deviation, ROCOF, vector shift and unbalance, and each function corresponds to a specific ANSI code.

A backlit graphic LC display shows the measured values. The last 300 network faults are stored with a time stamp, and the settings are protected by a password. An RS-485 interface and the BMS bus handle data exchange.

Listed applications are monitoring of voltage-sensitive machines and installations, protection of three-phase motors against phase failure and phase open-circuit, islanding detection by ROCOF, and transformer protection.

The VMD461 measures 108 x 93 x 45 mm and the CD440 93 x 45 x 67.5 mm. Mounting is on a DIN rail or by screws. Optional items include COM465IP function modules, CP907-I and CP915-I Condition Monitors and an RS-485 repeater. Part numbers are B93010047 for the VMD461, B73010046 for the CD440 and B98060008 for the mounting clip. The device follows DIN EN 60255-1:2010-9, with CE and UKCA declarations.

Technical specifications

TypeMultifunction voltage monitoring relay
Supply voltage UsAC/DC 100…240 V
Monitoring range (with CD440)DC/3AC 1200 V or 1AC/3NAC 690 V
Monitoring functions3-stage voltage and frequency, ROCOF df/dt, vector shift, unbalance, phase sequence
InterfacesRS-485, BMS bus
Memorylast 300 network faults with time stamp
Dimensions VMD461108 x 93 x 45 mm
Dimensions CD44093 x 45 x 67.5 mm
MountingDIN rail, screw mounting

Part numbers

Show all part numbers (3)

B93010047 (VMD461), B73010046 (CD440), B98060008

How it compares with similar models

ParameterLINETRAXX® VMD461 with CD440 Multifunction Voltage Monitoring Relay, up to 1200 V DC/3ACLINETRAXX® RCM410R-24/-2 single-channel residual current monitoring relay, 10 mA…30 ALINETRAXX® CME420 Multifunction AC Current Relay, 0.1…16 ALINETRAXX® VMD258 Undervoltage/Overvoltage Relay for 3AC Systems up to 690 V
TypeMultifunction voltage monitoring relayA (AC and pulsed DC)Multifunction AC current relayUndervoltage/overvoltage relay, 3AC
MountingDIN rail, screw mountingDIN railDIN rail, M4 screws—

Request a price and lead time

LINETRAXX® VMD461 with CD440 Multifunction Voltage Monitoring Relay, up to 1200 V DC/3AC. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What does the CD440 do?

The CD440 coupling device extends the monitoring range to DC/3AC 1200 V or 1AC/3NAC 690 V.

Which grid protection functions does the VMD461 offer?

Voltage and frequency monitoring, ROCOF df/dt, vector shift, unbalance and phase sequence, so it can be used for islanding detection.

What supply voltage does the relay need?

AC/DC 100…240 V.