LINETRAXX® ES258 Backup Device for the VMD258 Voltage Relay
The LINETRAXX® ES258 keeps the VMD258 undervoltage/overvoltage relay powered when the mains supply fails. Storage capacity is at least 5 s, recovery time up to 60 s, operating temperature -20…+70 °C.
- Type
- Energy backup device (capacitor)
- For relay
- VMD258
- Rated insulation voltage
- DC 100 V
- Rated impulse voltage
- 800 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
When the supply of an undervoltage/overvoltage relay collapses, the set response delay can collapse with it. The LINETRAXX® ES258 is a supplementary device for the VMD258 that closes this gap: it holds the relay energised during a power failure so that the set response delay stays effective.
Energy is stored in a capacitor. After commissioning, the capacitor is charged from the connected relay. If the supply voltage fails, the ES258 feeds the stored energy to the VMD258. The storage capacity is at least 5 s (± 0.5 s), and recharging after a discharge takes no more than 60 s.
Supply voltage of the device is DC 42…47 V (±35 %). Rated insulation voltage is DC 100 V and rated impulse voltage 800 V. The operating temperature is -20…+70 °C and the weight is up to 160 g.
The 77 x 85 x 68 mm enclosure mounts on a DIN rail to IEC 60715 or is screwed down, and the connection uses screw-type terminals. Installation, connection and commissioning are reserved for qualified electricians.
Standards named for the device are IEC 60664-1, IEC 61000-6-2, IEC 61000-6-4, DIN IEC 60721-3-3 and DIN EN 60204-1, and a CE declaration of conformity exists. The part number is B93010068 (B 9301 0068). The ES258 has no use on its own, because it works only together with the VMD258 relay, which also charges it.
Technical specifications
| Type | Energy backup device (capacitor) |
|---|---|
| For relay | VMD258 |
| Rated insulation voltage | DC 100 V |
| Rated impulse voltage | 800 V |
| Supply voltage | DC 42…47 V (±35 %) |
| Storage capacity to supply the relay | min. 5 s (± 0.5 s) |
| Recovery time | ≤ 60 s |
| Operating temperature | -20…+70 °C |
| Weight | ≤ 160 g |
| Dimensions | 77 x 85 x 68 mm |
| Mounting | DIN rail to IEC 60715, screw mounting |
| Terminals | screw-type |
Part numbers
Show all part numbers (1)
B93010068
How it compares with similar models
| Parameter | LINETRAXX® ES258 Backup Device for the VMD258 Voltage Relay | LINETRAXX® VMD258 Undervoltage/Overvoltage Relay for 3AC Systems up to 690 V | LINETRAXX® CEP410R-2 residual current monitor for the central earthing point | LINETRAXX® VMD423/VMD423H Voltage and Frequency Monitor for 3(N)AC up to 500 V |
|---|---|---|---|---|
| Type | Energy backup device (capacitor) | Undervoltage/overvoltage relay, 3AC | A (AC and pulsed DC) | Voltage and frequency monitoring relay for 3(N)AC |
| Rated insulation voltage | DC 100 V | — | 250 V | 400 V |
| Rated impulse voltage | 800 V | — | 4 kV | 4 kV |
| Supply voltage | DC 42…47 V (±35 %) | from the monitored system | DC 24 V; AC/DC 100…240 V | — |
| Operating temperature | -20…+70 °C | -20…+70 °C | -25…+55 °C | — |
| Weight | ≤ 160 g | 825 g | ≤ 100 g | — |
Request a price and lead time
LINETRAXX® ES258 Backup Device for the VMD258 Voltage Relay. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which relay does the ES258 work with?
The VMD258 undervoltage/overvoltage relay, for which it is a supplementary device.
How long does the ES258 supply the relay after a power failure?
At least 5 s (± 0.5 s). Recharging the capacitor takes no more than 60 s.
What operating temperature range applies?
-20…+70 °C.