LINETRAXX® MRCDB423 Type B modular residual current device, 30 mA…3 A

The LINETRAXX® MRCDB423 gives additional protection against indirect contact in earthed TN and TT systems. This Type B module measures the r.m.s. residual current, has prewarning and alarm outputs and can drive a disconnecting switching element.

Rated residual operating current IΔn2
30 mA…3 A
Rated residual operating current IΔn1
50…100 % of IΔn2
Rated frequency
0…2 kHz
Response delay ton1, ton2
0…10 s

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Additional protection (protection against indirect contact) in earthed TN and TT systems is the job of the LINETRAXX® MRCDB423, a modular residual current device Type B that responds to AC and DC (MRCD, IEC 60947-2 Annex M). It serves protection of persons, fire protection and plant protection, including loads with six-pulse rectifiers, one-way rectifiers with smoothing, converters, battery chargers and construction site equipment with frequency-controlled drives.

External measuring current transformers (CTUB101-CTBC…) detect the residual current, and their connection is monitored. The device evaluates the r.m.s. value. Rated residual operating current IΔn2 is 30 mA…3 A, the prewarning value IΔn1 is 50…100 % of IΔn2, and the rated frequency is 0…2 kHz. Response delays ton1 and ton2 are adjustable from 0…10 s, with a start-up delay of 1 s. Operating time is up to 180 ms at 1 x IΔn and up to 23 ms at 5 x IΔn, and recovery time up to 300 ms.

LEDs show alarm and prewarning, and relays K1/K2, each with a changeover contact (2 x 1), output them. The relays can drive a switching element with isolating properties to disconnect the circuit. A fault memory is included, and the measured value display covers AC/DC 0…6 A. Contact ratings are AC-13230 V / 3 A, AC-14230 V / 1 A and DC-12220 V / 0.1 A, with a minimum of 1 mA at AC/DC ≥ 10 V.

The MRCDB423-D-1 has a supply range of AC 24…60 V / DC 24…78 V and the MRCDB423-D-2 AC/DC 100…250 V, with power consumption up to 6.5 VA. Overvoltage category III, pollution degree 2. It fits a DIN rail or is screw mounted, and measures 93 x 74 x 36 mm. Mounting clip B98060008, mounting frame XM420 B990994 and connecting cables CTX-… are options.

Technical specifications

Rated residual operating current IΔn230 mA…3 A
Rated residual operating current IΔn150…100 % of IΔn2
Rated frequency0…2 kHz
Response delay ton1, ton20…10 s
Start-up delay1 s
Operating time at 1 x IΔn1/2≤ 180 ms
Operating time at 5 x IΔn1/2≤ 23 ms
Recovery time≤ 300 ms
Display range AC/DC0…6 A
Supply voltage range US (D-1)AC 24…60 V / DC 24…78 V
Supply voltage range US (D-2)AC/DC 100…250 V
Switching elements2 x 1 changeover contact
Power consumption≤ 6.5 VA
Overvoltage category / pollution degreeIII/2
Dimensions93 x 74 x 36 mm

Part numbers

Show all part numbers (2)

B94043055 (D-1), B94043056 (D-2)

Request a price and lead time

LINETRAXX® MRCDB423 Type B modular residual current device, 30 mA…3 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the MRCDB423 used for?

Additional protection against indirect contact in earthed TN and TT systems, and protection of persons, plant and against fire.

What are the response range and delays?

IΔn2 is 30 mA…3 A and the delays ton1 and ton2 are adjustable from 0…10 s.

Can the device disconnect the circuit?

Yes. Relays K1/K2 can drive a switching element with isolating properties.