RCMB130 AC/DC sensitive residual current monitoring module, ±100 mA, up to 32 A
The RCMB130 series covers compact Type B residual current monitoring modules for building into power distribution equipment. They measure AC/DC up to ±100 mA on supplies to 300 V and loads to 32 A, with a Modbus RTU (RS-485) or PWM output.
- Rated voltage
- 300 V
- Supply voltage
- DC 12…24 V
- Measuring range
- AC/DC ±100 mA
- Nominal current
- 32 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Electrically earthed power supplies up to 300 V and connected loads up to a nominal 32 A are the field of the RCMB130 modules, which watch for leakage and fault currents as a basis for preventive maintenance. They are built into distribution equipment such as PDUs (Power Distribution Units), outlet boxes and multiple socket-outlets, and into machines and power distribution systems.
The measuring technique is AC/DC sensitive (Type B). The RMS value is formed from the DC component of the residual current and the AC component below 2000 Hz, within a range of AC/DC ±100 mA, and is refreshed every 180 ms. The module checks the connection of its internal measuring current transformer and the supply voltage on a continuous basis, and has an integrated test function.
There are three versions. RCMB131-01 sends the measured value and alarm over Modbus RTU (RS-485). RCMB131-02 gives the RMS value of the residual current on a PWM output. RCMB132-01 also uses Modbus RTU (RS-485) and can be daisy-chained. On the RCMB132-01 the default Modbus address is 100, outputs S1 (DC) and S2 (RMS) go to alarm state when a response value is exceeded or a malfunction occurs, and S1 switches whenever S2 does.
The module is mounted on a PCB and measures 52.7 x 42.7 x 34.2 mm, protection class IP 30. Supply is DC 12…24 V, ambient operating temperature -25…+70 °C, operating altitude up to 3000 m AMSL. A fully screened measuring current transformer keeps sensitivity to load current low. Protective conductors and low-resistance conductor loops must never be routed through the transformer, because the DC-sensitive technique could induce high currents in them. A MCCT20 mounting foot is available as an accessory. Standards: IEC 60664-1, IEC 60755, IEC 61010-1, DIN EN IEC 62020-1:2021-10.
Technical specifications
| Rated voltage | 300 V |
|---|---|
| Supply voltage | DC 12…24 V |
| Measuring range | AC/DC ±100 mA |
| Nominal current | 32 A |
| Frequency range | DC…2 kHz |
| Interfaces | Modbus RTU (RS-485) or PWM |
| Measured value update | 180 ms |
| Protection class | IP 30 |
| Operating temperature | -25…+70 °C |
| Operating altitude | up to 3000 m AMSL |
| Dimensions | 52.7 x 42.7 x 34.2 mm |
Part numbers
Show all part numbers (4)
B94042131, B94042132, B94042136, mounting foot MCCT20 B91080111
How it compares with similar models
| Parameter | RCMB130 AC/DC sensitive residual current monitoring module, ±100 mA, up to 32 A | LINETRAXX® RCMB330 AC/DC sensitive residual current monitoring module, 10…500 mA, RS-485 | RDC104-4 DC residual current monitoring module for AC charging stations to IEC 62955 | LINETRAXX® CEP410R-2 residual current monitor for the central earthing point |
|---|---|---|---|---|
| Rated voltage | 300 V | 800 V | 250 V | — |
| Supply voltage | DC 12…24 V | DC 24 V (19.2…28.8 V) | DC 5 V | DC 24 V; AC/DC 100…240 V |
| Measuring range | AC/DC ±100 mA | — | ±300 mA | 10 mA…30 A |
| Frequency range | DC…2 kHz | DC…100 kHz | — | 42…70 Hz |
| Operating temperature | -25…+70 °C | — | -30…80 °C | -25…+55 °C |
| Dimensions | 52.7 x 42.7 x 34.2 mm | 25 x 65.5 x 100.4 mm | — | 109 x 48.5 x 64 mm |
Request a price and lead time
RCMB130 AC/DC sensitive residual current monitoring module, ±100 mA, up to 32 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which versions does the RCMB130 series include?
RCMB131-01 with Modbus RTU (RS-485), RCMB131-02 with a PWM output for the RMS value, and RCMB132-01 with Modbus RTU (RS-485) and daisy-chain capability.
Which currents does the module measure?
AC and DC residual currents within AC/DC ±100 mA, over a frequency range of DC…2 kHz.
Can a PE conductor pass through the module's transformer?
No. Protective conductors and low-resistance loops must stay outside the measuring transformer, since high currents could be induced in them.