RCMB130 AC/DC sensitive residual current monitoring module, ±100 mA, up to 32 A

The RCMB130 series covers compact Type B residual current monitoring modules for building into power distribution equipment. They measure AC/DC up to ±100 mA on supplies to 300 V and loads to 32 A, with a Modbus RTU (RS-485) or PWM output.

Rated voltage
300 V
Supply voltage
DC 12…24 V
Measuring range
AC/DC ±100 mA
Nominal current
32 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Electrically earthed power supplies up to 300 V and connected loads up to a nominal 32 A are the field of the RCMB130 modules, which watch for leakage and fault currents as a basis for preventive maintenance. They are built into distribution equipment such as PDUs (Power Distribution Units), outlet boxes and multiple socket-outlets, and into machines and power distribution systems.

The measuring technique is AC/DC sensitive (Type B). The RMS value is formed from the DC component of the residual current and the AC component below 2000 Hz, within a range of AC/DC ±100 mA, and is refreshed every 180 ms. The module checks the connection of its internal measuring current transformer and the supply voltage on a continuous basis, and has an integrated test function.

There are three versions. RCMB131-01 sends the measured value and alarm over Modbus RTU (RS-485). RCMB131-02 gives the RMS value of the residual current on a PWM output. RCMB132-01 also uses Modbus RTU (RS-485) and can be daisy-chained. On the RCMB132-01 the default Modbus address is 100, outputs S1 (DC) and S2 (RMS) go to alarm state when a response value is exceeded or a malfunction occurs, and S1 switches whenever S2 does.

The module is mounted on a PCB and measures 52.7 x 42.7 x 34.2 mm, protection class IP 30. Supply is DC 12…24 V, ambient operating temperature -25…+70 °C, operating altitude up to 3000 m AMSL. A fully screened measuring current transformer keeps sensitivity to load current low. Protective conductors and low-resistance conductor loops must never be routed through the transformer, because the DC-sensitive technique could induce high currents in them. A MCCT20 mounting foot is available as an accessory. Standards: IEC 60664-1, IEC 60755, IEC 61010-1, DIN EN IEC 62020-1:2021-10.

Technical specifications

Rated voltage300 V
Supply voltageDC 12…24 V
Measuring rangeAC/DC ±100 mA
Nominal current32 A
Frequency rangeDC…2 kHz
InterfacesModbus RTU (RS-485) or PWM
Measured value update180 ms
Protection classIP 30
Operating temperature-25…+70 °C
Operating altitudeup to 3000 m AMSL
Dimensions52.7 x 42.7 x 34.2 mm

Part numbers

Show all part numbers (4)

B94042131, B94042132, B94042136, mounting foot MCCT20 B91080111

How it compares with similar models

ParameterRCMB130 AC/DC sensitive residual current monitoring module, ±100 mA, up to 32 ALINETRAXX® RCMB330 AC/DC sensitive residual current monitoring module, 10…500 mA, RS-485RDC104-4 DC residual current monitoring module for AC charging stations to IEC 62955LINETRAXX® CEP410R-2 residual current monitor for the central earthing point
Rated voltage300 V800 V250 V—
Supply voltageDC 12…24 VDC 24 V (19.2…28.8 V)DC 5 VDC 24 V; AC/DC 100…240 V
Measuring rangeAC/DC ±100 mA—±300 mA10 mA…30 A
Frequency rangeDC…2 kHzDC…100 kHz—42…70 Hz
Operating temperature-25…+70 °C—-30…80 °C-25…+55 °C
Dimensions52.7 x 42.7 x 34.2 mm25 x 65.5 x 100.4 mm—109 x 48.5 x 64 mm

Request a price and lead time

RCMB130 AC/DC sensitive residual current monitoring module, ±100 mA, up to 32 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which versions does the RCMB130 series include?

RCMB131-01 with Modbus RTU (RS-485), RCMB131-02 with a PWM output for the RMS value, and RCMB132-01 with Modbus RTU (RS-485) and daisy-chain capability.

Which currents does the module measure?

AC and DC residual currents within AC/DC ±100 mA, over a frequency range of DC…2 kHz.

Can a PE conductor pass through the module's transformer?

No. Protective conductors and low-resistance loops must stay outside the measuring transformer, since high currents could be induced in them.