International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ВЛ-85 three-channel microprocessor time relay, 0.1 s to 9.99 h delay range

The ВЛ-85 switches electrical circuits after preset time delays in protection, anti-emergency and industrial automation equipment of power systems. It has three output contact groups 1п + 1п + 1п, a digital display, button setting and DIN-35 rail mounting.

Time setting ranges
0.1–99.9 s; 0.01–9.99 min; 0.1–99.9 min; 0.01–9.99 h
Setting resolution
0.1 s; 0.01 min; 0.1 min; 0.01 h
Start action
Application of supply voltage
Output contacts
1п + 1п + 1п

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The ВЛ-85 is a microprocessor time relay that switches electrical circuits after preset delays. It is used in protection devices and in anti-emergency and industrial automation of power systems. The manufacturer describes it as a full analogue of the ВЛ-81М relay, built in a modular housing for a DIN-35 rail.

Unlike the ВЛ-81М, this relay is digital. Settings are entered through a menu with navigation buttons, and the display shows the running delay count. Within one version the settings run from 0.1 s to 9.99 h. The ranges are 0.1–99.9 s, 0.01–9.99 min, 0.1–99.9 min and 0.01–9.99 h, with resolution of 0.1 s, 0.01 min, 0.1 min and 0.01 h respectively. Timing starts when supply voltage is applied. The relay is rated for continuous duty, and each of the three channels has its own delay.

Output contacts are three groups 1п + 1п + 1п with a maximum switching current of 5 A. Switching voltage is 12–250 V DC or 12–400 V AC, and switching power is 30 W DC or 400 VA AC. Re-ready time and return time are 0.1 s maximum. Power consumption is 7 VA maximum.

Four supply versions are made: 24 V DC; 110/115 V AC (50 Hz) or 110 V DC; 220/230 V AC (50 Hz) or 220 V DC; and 380/400 V AC (50 Hz).

The housing is 4 DIN (72 mm) with dimensions of 53 × 90 × 65 mm and a weight of 0.25 kg maximum. Wires connect at the front under a screw. Protection is IP40 for the housing and IP20 for the terminal block, per ДСТУ EN 60529. The climatic version is У, category 3 to ГОСТ 15150-69, for closed unheated rooms. Operating temperature is minus 30 to plus 55 °C up to 1000 m altitude and minus 30 to plus 50 °C up to 2000 m. Service life is at least 12 years.

Technical specifications

Time setting ranges0.1–99.9 s; 0.01–9.99 min; 0.1–99.9 min; 0.01–9.99 h
Setting resolution0.1 s; 0.01 min; 0.1 min; 0.01 h
Start actionApplication of supply voltage
Output contacts1п + 1п + 1п
DC supply24, 110, 220 V
AC supply, 50 Hz110, 115, 220, 230, 380, 400 V
Power consumption7 VA max.
Switching voltage12–250 V (DC); 12–400 V (AC)
Switching power30 W (DC); 400 VA (AC)
Maximum switching current5 A
Re-ready time / return time0.1 s max. / 0.1 s max.
Dimensions53 × 90 × 65 mm
Weight0.25 kg max.
MountingDIN-35 rail
Protection degreeIP40 (housing); IP20 (terminal block)
Operating temperature−30 to +55 °C (altitude up to 1000 m)
Service lifeat least 12 years

How it compares with similar models

ParameterВЛ-85 three-channel microprocessor time relay, 0.1 s to 9.99 h delay rangeВЛ-100М (VL-100M) microprocessor three-circuit time relay with digital display, 0.05 s - 99.9 minВЛ-81М (VL-81M) compact three-circuit time relay, 0.1 s - 99 hВЛ-159М-4 (VL-159M-4) multifunction time relay, 8 functions, pulse counter, 0.1 s - 9999 min
Output contacts1п + 1п + 1п3 changeover (1 + 1 + 1)1 changeover per circuit2 changeover
Power consumption7 VA max.up to 7 VAup to 5 VA (W)up to 5 VA (W)
Switching voltage12–250 V (DC); 12–400 V (AC)up to 250 V DC, up to 400 V AC—24...250 V
Switching power30 W (DC); 400 VA (AC)30 W DC, 400 VA AC30 W (DC-11); 400 VA (AC-22)—
Dimensions53 × 90 × 65 mm53 × 90 × 65 mmup to 70x90x65 mm70x90x65 mm
Weight0.25 kg max.up to 0.25 kgup to 0.5 kgup to 0.25 kg

Request a price and lead time

ВЛ-85 three-channel microprocessor time relay, 0.1 s to 9.99 h delay range. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What delay ranges does the ВЛ-85 cover?

There are four ranges: 0.1–99.9 s, 0.01–9.99 min, 0.1–99.9 min and 0.01–9.99 h. Resolution is 0.1 s, 0.01 min, 0.1 min and 0.01 h respectively.

How does the ВЛ-85 differ from the ВЛ-81М?

The manufacturer calls it a full analogue of the ВЛ-81М. It adds digital setting by buttons, a display of the running count and a modular housing for a DIN-35 rail.

What supply and contact ratings apply?

Supply runs from 24 V DC to 400 V AC across four versions. The contacts switch up to 5 A at 12–250 V DC or 12–400 V AC.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00