РЗЛ-05.ЦС microprocessor central signalling unit, 40 inputs, 9 relays
The РЗЛ-05.ЦС is a section-wide central signalling unit for substations and power stations. It has 40 discrete inputs, 9 output relays, and USB and RS-485 interfaces with the Modbus RTU protocol. The supply is 90–254 V DC/AC and power consumption is 9 W.
- Operating supply voltage, DC/AC
- 90 - 254 V
- Power consumption
- 9 W
- Readiness time, max
- 1 s
- Supply interruption ride-through, min
- 0.5 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РЗЛ-05.ЦС serves as a section-wide central signalling unit in electrical substations and power stations fitted with digital or electromechanical relay protection and automation. It receives emergency and warning signals with an adjustable time delay, takes position signals, handles group signalling and keeps an event log. It integrates into SCADA systems, logic programming is available to order, and the Монитор-2 software is used for setting up.
There are 40 discrete inputs with a rated voltage of 220 V, an operating threshold of 132–176 V and a minimum input signal duration of 40 ms. Input current is 20 mA on switching on and 4 mA when on. Time delays are set from 0.01 to 99.00 s for both operation and reset. The analogue current inputs for group signalling sensors have a rated input current of 50 mA and a measuring range of 0.03–2.0 A, and the maximum number of signals at 50 mA is 30.
Nine output relays are fitted. Switching voltage is 300 V DC and 400 V AC, the AC making and breaking current is 8 A, and for relay К1 it is 16 A. Communication is through USB and two RS-485 ports using Modbus RTU at 9600, 19200 or 38400 bit/s. Indication is by 48 LEDs.
The supply is 90–254 V DC/AC from a single channel, readiness time is up to 1 s, and the unit rides through a supply interruption of at least 0.5 s. The case is recessed-mounting, 300x240x128 mm, with a mass of up to 5 kg. Operating temperature is -40...+55 °C, permissible humidity is 98 % at 25 °C, insulation resistance is at least 50 MΩ and insulation strength is 5 / 2 kV.
Technical specifications
| Operating supply voltage, DC/AC | 90 - 254 V |
|---|---|
| Power consumption | 9 W |
| Readiness time, max | 1 s |
| Supply interruption ride-through, min | 0.5 s |
| Rated input current | 50 mA |
| Measuring range | 0.03 - 2.0 A |
| Maximum number of signals (for I=50 mA) | 30 |
| Number of discrete inputs | 40 |
| Input operating voltage level | 132 - 176 V |
| Input time delay setting range | 0.01 - 99.00 s |
| Number of output relays | 9 |
| Switching voltage | DC 300 V, AC 400 V |
| AC making and breaking current | 8 A, relay К1 - 16 A |
| Interfaces | USB 1 pc, RS-485 2 pcs |
| RS-485 protocol | Modbus RTU |
| Data rate | 9600, 19200, 38400 bit/s |
| Dimensions (WxHxD) | 300х240х128 mm |
| Mass, max | 5 kg |
| Operating temperature range | -40... +55 °C |
| Insulation resistance, min | 50 MΩ |
How it compares with similar models
| Parameter | РЗЛ-05.ЦС microprocessor central signalling unit, 40 inputs, 9 relays | РЗЛ-05.РПН on-load tap-changer control device for transformers, 12 output relays, 2 supply channels | РЗЛ-05.АЕ protection and automation unit for 6–35 kV feeders, 24 output relays | РЗЛ-01.03 microprocessor protection and automation relay for 6-35 kV distribution networks |
|---|---|---|---|---|
| Power consumption | 9 W | 8 W | 2x13 W max. | — |
| Interfaces | USB 1 pc, RS-485 2 pcs | USB 1 pc, RS-485 2 pcs | RS-485 – 2 pcs, Ethernet; USB (front port) | RS485, RS232 |
| Operating temperature range | -40... +55 °C | -40... +55 °C | −40…+60 °C | — |
European equivalents
BELplus OZE, IRV MV feeder protection terminal (V platform)
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РЗЛ-05.ЦС microprocessor central signalling unit, 40 inputs, 9 relays. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many discrete inputs and output relays does the РЗЛ-05.ЦС have?
40 discrete inputs and 9 output relays.
Which interfaces and protocol does the unit have?
One USB port and two RS-485 ports with the Modbus RTU protocol at 9600, 19200 or 38400 bit/s.
What are the operating temperature range and dimensions?
Operating temperature is -40 to +55 °C, dimensions are 300x240x128 mm and the mass is up to 5 kg.