AGH150W and AGH150W-4 Coupling Devices for ISOMETER® in AC 1150 V and DC up to 1760 V Systems
Used with an ISOMETER®, the AGH150W and AGH150W-4 monitor the insulation resistance of AC and DC IT systems. Nominal voltage is AC 0…1150 V with DC 0…1100 V (AGH150W) or DC 0…1760 V (AGH150W-4), on a DIN rail.
- Nominal system voltage Un
- AC 0…1150 V, DC 0…1100 V (AGH150W); AC 0…1150 V, DC 0…1760 V (AGH150W-4)
- Un for UL applications (AGH150W-4)
- DC 0…1600 V
- Rated insulation voltage
- AC 1000 V (AGH150W); AC 1600 V (AGH150W-4)
- Rated impulse voltage
- ≥ 8 kV (AGH150W); ≥ 11 kV (AGH150W-4)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The AGH150W or AGH150W-4 coupling device, combined with an ISOMETER®, monitors the insulation resistance of AC and DC IT systems (unearthed systems). It extends the nominal voltage range of the ISOMETER iso685xx and IRDH… series to AC 0…1150 V with DC 0…1100 V (AGH150W) and AC 0…1150 V with DC 0…1760 V (AGH150W-4). The device is connected to the monitored system by two poles and, via terminal AK160, to terminal AK or terminals L1/L2/L3 of the ISOMETER. For safe operation, all PE connections of the ISOMETER must be connected to the protective earth conductor.
The AGH150W has an internal DC resistance Ri of 80 kΩ (tolerance ±2 kΩ), a rated impulse voltage of at least 8 kV and a rated insulation voltage of AC 1000 V. The AGH150W-4 has Ri of 160 kΩ (tolerance ±4 kΩ), at least 11 kV rated impulse voltage and AC 1600 V rated insulation voltage. The Ri tolerance affects the value measured by the ISOMETER and must be taken into account. UL approval applies only to the AGH150W-4, which is rated DC 0…1600 V for UL applications.
The frequency range of Un (sine) is DC 1…460 Hz, overvoltage category is CAT III, pollution degree is 2 and operating altitude is up to 2000 m AMSL. Nominal power consumption is up to 10 W at DC 1760 V. The terminals are flat type for 0.2…4 mm² rigid or 0.2…2.5 mm² flexible conductors. The device mounts on a DIN rail to DIN EN 60715 / IEC 60715 in any position and runs in continuous operation.
Protection is IP30, with IP10 for built-in components, flammability class is UL94 V-0 and weight is up to 900 g. Ambient temperature is −40…+70 °C in operation, −10…+55 °C for UL applications and −40…+70 °C in storage. Climatic classes are 3K22 (max 98 % humidity), 2K11 for transport and 1K22 for storage. The device was developed to DIN EN 45545-2 and DIN EN 50155, and CE and UKCA declarations are listed.
Technical specifications
| Nominal system voltage Un | AC 0…1150 V, DC 0…1100 V (AGH150W); AC 0…1150 V, DC 0…1760 V (AGH150W-4) |
|---|---|
| Un for UL applications (AGH150W-4) | DC 0…1600 V |
| Rated insulation voltage | AC 1000 V (AGH150W); AC 1600 V (AGH150W-4) |
| Rated impulse voltage | ≥ 8 kV (AGH150W); ≥ 11 kV (AGH150W-4) |
| Internal DC resistance Ri | 80 kΩ (AGH150W); 160 kΩ (AGH150W-4) |
| Tolerance of Ri | ±2 kΩ (AGH150W); ±4 kΩ (AGH150W-4) |
| Frequency range of Un (sine) | DC 1…460 Hz |
| Overvoltage category | CAT III |
| Pollution degree | 2 |
| Operating altitude | ≤ 2000 m AMSL |
| Nominal power consumption | ≤ 10 W at DC 1760 V |
| Terminals | flat terminals, 0.2…4 mm² / 0.2…2.5 mm² |
| Mounting | DIN rail DIN EN 60715 / IEC 60715, any position |
| Degree of protection | IP30, built-in components IP10 |
| Flammability class | UL94 V-0 |
| Ambient temperature, operation | −40…+70 °C (UL −10…+55 °C) |
| Storage temperature | −40…+70 °C |
| Weight | ≤ 900 g |
Part numbers
Show all part numbers (2)
B915576 (AGH150W), B98018006 (AGH150W-4)
How it compares with similar models
| Parameter | AGH150W and AGH150W-4 Coupling Devices for ISOMETER® in AC 1150 V and DC up to 1760 V Systems | AGH204S-4 Coupling Device for ISOMETER® in 3AC IT Systems up to 1650 V | AGH520S Coupling Device for ISOMETER® in 3(N)AC Systems up to 7.2 kV | AGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kV |
|---|---|---|---|---|
| Nominal system voltage Un | AC 0…1150 V, DC 0…1100 V (AGH150W); AC 0…1150 V, DC 0…1760 V (AGH150W-4) | — | 3(N)AC 0…7.2 kV | AC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15) |
| Rated insulation voltage | AC 1000 V (AGH150W); AC 1600 V (AGH150W-4) | AC 1500 V | AC 6.3 kV | AC 7.2 kV / AC 15.5 kV |
| Internal DC resistance Ri | 80 kΩ (AGH150W); 160 kΩ (AGH150W-4) | — | ≥ 80 kΩ | ≥ 2.39 MΩ / ≥ 4.7 MΩ |
| Overvoltage category | CAT III | III | III | — |
| Degree of protection | IP30, built-in components IP10 | IP30, built-in components IP10 | IP64, built-in components IP20 | IP64 (built-in components) / IP20 (terminals) |
| Flammability class | UL94 V-0 | — | UL 94 HB | UL94 HB |
Request a price and lead time
AGH150W and AGH150W-4 Coupling Devices for ISOMETER® in AC 1150 V and DC up to 1760 V Systems. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the AGH150W and AGH150W-4 differ?
The AGH150W is rated DC 0…1100 V without UL approval; the AGH150W-4 is rated DC 0…1760 V with UL approval and has Ri of 160 kΩ instead of 80 kΩ.
How is the device connected?
By two poles to the monitored system and via terminal AK160 to terminal AK or L1/L2/L3 of the ISOMETER, with all PE connections of the ISOMETER tied to the protective earth conductor.
What operating temperature range applies?
−40…+70 °C, or −10…+55 °C for UL applications, at an operating altitude of up to 2000 m AMSL.
Similar equipment from other manufacturers