AGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kV
The AGH676S-4 extends the nominal voltage range of ISOMETER® insulation monitoring devices to AC/3(N)AC 0…12 kV, 50…460 Hz. Cast resin enclosure, 2000 mm high-voltage cable, degree of protection IP64.
- Nominal system voltage Un
- AC, 3(N)AC 0…12 kV
- Nominal frequency fn
- 50…460 Hz
- Cable length
- 2000 mm
- Rated insulation voltage
- AC 12 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This coupling device connects an ISOMETER® to unearthed AC and 3(N)AC systems rated 0…12 kV. It widens the nominal voltage range of the ISOMETERs shown in the wiring diagram to AC/3(N)AC 50…460 Hz, 0…12 kV. The compatible units named include the IR420-D64 and the iso685 series. Coupling devices are intended only for use together with ISOMETERs; any other use is regarded as improper.
Two monitoring modes are possible, offline and online, each with its own wiring diagram. First terminals E and KE of the ISOMETER and terminals 3 and 4 of the coupling device go to PE; terminal 5 of the coupling device then goes to terminal AK of the ISOMETER, and terminal 2 is connected to the system being monitored.
The medium-voltage side is a high-voltage cable of 2000 mm, encapsulated on the device side. Terminals 3-5 are screw type, 0.2…4 mm² rigid or 0.2…2.5 mm² flexible, tightened to 0.5 Nm. The enclosure is cast resin encapsulated with M5 screw mounting and degree of protection IP64, with IP20 for built-in components to DIN EN 60529. Weight is up to 8400 g and the dimensions are 320 x 280 x 220 mm.
Insulation is coordinated to DIN EN 61800-5-1 (VDE 0160-105-1) with a rated insulation voltage of AC 12 kV. Operating mode is continuous and any mounting position is permitted. Ambient temperature is −10…+55 °C in operation and −20…+70 °C in storage, with climatic class 3K23 to IEC 60721-3-3. UKCA is listed for the product, and the model is discontinued.
Technical specifications
| Nominal system voltage Un | AC, 3(N)AC 0…12 kV |
|---|---|
| Nominal frequency fn | 50…460 Hz |
| Cable length | 2000 mm |
| Rated insulation voltage | AC 12 kV |
| Voltage impulse test (basic insulation) | ≥ AC 75 kV |
| AC voltage test (basic insulation) | ≥ AC 45 kV |
| Partial discharge test | ≥ 16.5 kVeff |
| Internal DC resistance Ri | ≥ 160 kΩ |
| Impedance Zi at 12 kV and 50 Hz | ≥ 12 MΩ |
| Connection | high-voltage cable (encapsulated on the device side) |
| Terminals 3-5 | screw type, 0.2…4 mm² / 0.2…2.5 mm² |
| Degree of protection | IP64, built-in components IP20 |
| Enclosure | cast resin encapsulated, M5 mounting |
| Ambient temperature | −10…+55 °C (storage −20…+70 °C) |
| Shock resistance | 15 g / 11 ms |
| Vibration resistance to IEC 60068-2-6 | 1 g / 10…150 Hz |
| Weight | ≤ 8400 g |
Part numbers
Show all part numbers (1)
B913055
How it compares with similar models
| Parameter | AGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kV | AGH520S Coupling Device for ISOMETER® in 3(N)AC Systems up to 7.2 kV | AGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kV | AGH204S-4 Coupling Device for ISOMETER® in 3AC IT Systems up to 1650 V |
|---|---|---|---|---|
| Nominal system voltage Un | AC, 3(N)AC 0…12 kV | 3(N)AC 0…7.2 kV | AC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15) | — |
| Rated insulation voltage | AC 12 kV | AC 6.3 kV | AC 7.2 kV / AC 15.5 kV | AC 1500 V |
| Internal DC resistance Ri | ≥ 160 kΩ | ≥ 80 kΩ | ≥ 2.39 MΩ / ≥ 4.7 MΩ | — |
| Degree of protection | IP64, built-in components IP20 | IP64, built-in components IP20 | IP64 (built-in components) / IP20 (terminals) | IP30, built-in components IP10 |
| Enclosure | cast resin encapsulated, M5 mounting | resin-encapsulated block in housing, 4 × M5 | resin-encapsulated block, M5 mounting | X112, halogen-free, UL 94 V-0 |
| Weight | ≤ 8400 g | 4500 g | ≤ 5100 g | ≤ 1350 g |
Request a price and lead time
AGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which ISOMETER® units work with the AGH676S-4?
The IR420-D64 and the iso685 series are named as compatible; the coupling device is intended only for use together with ISOMETERs.
What is the highest system voltage?
Nominal system voltage Un is AC, 3(N)AC 0…12 kV at 50…460 Hz, and the rated insulation voltage is AC 12 kV.
What temperature range and protection class apply?
Operation is −10…+55 °C, storage −20…+70 °C, protection is IP64 and the mounting position is arbitrary.