International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

AGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kV

The AGH676S-4 extends the nominal voltage range of ISOMETER® insulation monitoring devices to AC/3(N)AC 0…12 kV, 50…460 Hz. Cast resin enclosure, 2000 mm high-voltage cable, degree of protection IP64.

Nominal system voltage Un
AC, 3(N)AC 0…12 kV
Nominal frequency fn
50…460 Hz
Cable length
2000 mm
Rated insulation voltage
AC 12 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

This coupling device connects an ISOMETER® to unearthed AC and 3(N)AC systems rated 0…12 kV. It widens the nominal voltage range of the ISOMETERs shown in the wiring diagram to AC/3(N)AC 50…460 Hz, 0…12 kV. The compatible units named include the IR420-D64 and the iso685 series. Coupling devices are intended only for use together with ISOMETERs; any other use is regarded as improper.

Two monitoring modes are possible, offline and online, each with its own wiring diagram. First terminals E and KE of the ISOMETER and terminals 3 and 4 of the coupling device go to PE; terminal 5 of the coupling device then goes to terminal AK of the ISOMETER, and terminal 2 is connected to the system being monitored.

The medium-voltage side is a high-voltage cable of 2000 mm, encapsulated on the device side. Terminals 3-5 are screw type, 0.2…4 mm² rigid or 0.2…2.5 mm² flexible, tightened to 0.5 Nm. The enclosure is cast resin encapsulated with M5 screw mounting and degree of protection IP64, with IP20 for built-in components to DIN EN 60529. Weight is up to 8400 g and the dimensions are 320 x 280 x 220 mm.

Insulation is coordinated to DIN EN 61800-5-1 (VDE 0160-105-1) with a rated insulation voltage of AC 12 kV. Operating mode is continuous and any mounting position is permitted. Ambient temperature is −10…+55 °C in operation and −20…+70 °C in storage, with climatic class 3K23 to IEC 60721-3-3. UKCA is listed for the product, and the model is discontinued.

Technical specifications

Nominal system voltage UnAC, 3(N)AC 0…12 kV
Nominal frequency fn50…460 Hz
Cable length2000 mm
Rated insulation voltageAC 12 kV
Voltage impulse test (basic insulation)≥ AC 75 kV
AC voltage test (basic insulation)≥ AC 45 kV
Partial discharge test≥ 16.5 kVeff
Internal DC resistance Ri≥ 160 kΩ
Impedance Zi at 12 kV and 50 Hz≥ 12 MΩ
Connectionhigh-voltage cable (encapsulated on the device side)
Terminals 3-5screw type, 0.2…4 mm² / 0.2…2.5 mm²
Degree of protectionIP64, built-in components IP20
Enclosurecast resin encapsulated, M5 mounting
Ambient temperature−10…+55 °C (storage −20…+70 °C)
Shock resistance15 g / 11 ms
Vibration resistance to IEC 60068-2-61 g / 10…150 Hz
Weight≤ 8400 g

Part numbers

Show all part numbers (1)

B913055

How it compares with similar models

ParameterAGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kVAGH520S Coupling Device for ISOMETER® in 3(N)AC Systems up to 7.2 kVAGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kVAGH204S-4 Coupling Device for ISOMETER® in 3AC IT Systems up to 1650 V
Nominal system voltage UnAC, 3(N)AC 0…12 kV3(N)AC 0…7.2 kVAC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15)—
Rated insulation voltageAC 12 kVAC 6.3 kVAC 7.2 kV / AC 15.5 kVAC 1500 V
Internal DC resistance Ri≥ 160 kΩ≥ 80 kΩ≥ 2.39 MΩ / ≥ 4.7 MΩ—
Degree of protectionIP64, built-in components IP20IP64, built-in components IP20IP64 (built-in components) / IP20 (terminals)IP30, built-in components IP10
Enclosurecast resin encapsulated, M5 mountingresin-encapsulated block in housing, 4 × M5resin-encapsulated block, M5 mountingX112, halogen-free, UL 94 V-0
Weight≤ 8400 g4500 g≤ 5100 g≤ 1350 g

Request a price and lead time

AGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which ISOMETER® units work with the AGH676S-4?

The IR420-D64 and the iso685 series are named as compatible; the coupling device is intended only for use together with ISOMETERs.

What is the highest system voltage?

Nominal system voltage Un is AC, 3(N)AC 0…12 kV at 50…460 Hz, and the rated insulation voltage is AC 12 kV.

What temperature range and protection class apply?

Operation is −10…+55 °C, storage −20…+70 °C, protection is IP64 and the mounting position is arbitrary.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00