The AGH520S extends the nominal voltage range of the ISOMETER® iso685, IRDH275 and IRDH375 to 3(N)AC 0…7.2 kV, 50…400 Hz. Online and offline modes, a resin-encapsulated block in a housing, degree of protection IP64.
- Nominal system voltage Un
- 3(N)AC 0…7.2 kV
- Un for UL applications
- AC 0…6.0 kV
- Frequency range of Un
- 50…400 Hz
- Rated insulation voltage
- AC 6.3 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The AGH520S links an ISOMETER® iso685, IRDH275 or IRDH375 to AC systems up to 7.2 kV in online mode. For 7.2 kV AC systems it can also be used in offline mode. The coupling device is to be used only together with an ISOMETER. It extends the nominal voltage range of the ISOMETER shown in the wiring diagram to 3(N)AC 50…400 Hz, 0…7.2 kV. It connects to the monitored system by one pole, and terminal 5 goes to terminal AK of the ISOMETER.
Nominal system voltage Un is AC 0…7.2 kV, or AC 0…6.0 kV for UL applications, at 50…400 Hz. Internal DC resistance Ri is at least 80 kΩ and impedance Zi at 7.2 kV and 50 Hz is at least 6 MΩ. Rated insulation voltage is AC 6.3 kV with overvoltage category III. Tests to IEC 60664-1 on basic insulation are an impulse of AC 35 kV, an AC voltage test of AC 17.5 kV and a partial discharge test at 12 kV.
Terminal 2 (medium voltage) and terminals 3-5 are screw type, accepting 0.2…4 mm² rigid or 0.2…2.5 mm² flexible conductors, AWG 24…12, with a tightening torque of 2.9 Nm. The housing contains a resin-encapsulated block fixed with four M5 screws (4 × M5), in any mounting position, for continuous operation. Protection is IP64, with IP20 for built-in components to DIN EN 60529. Flammability class is UL 94 HB, weight is 4500 g and dimensions are 220 x 190 x 76 mm.
Ambient temperature is −10…+55 °C in operation, −10…+45 °C for UL applications and −20…+70 °C in storage. Climatic class is 3K23 to IEC 60721, and mechanical classes are 3M11 for stationary use, 2M4 for transport and 1M12 for storage. The device was developed to DIN EN 61800-5-1 (VDE 0160-105-1). CE, UKCA and UL are listed, and the model is discontinued.
Technical specifications
| Nominal system voltage Un | 3(N)AC 0…7.2 kV |
|---|---|
| Un for UL applications | AC 0…6.0 kV |
| Frequency range of Un | 50…400 Hz |
| Rated insulation voltage | AC 6.3 kV |
| Overvoltage category | III |
| Voltage impulse test (basic insulation) | AC 35 kV |
| AC voltage test (basic insulation) | AC 17.5 kV |
| Partial discharge test | 12 kV |
| Internal DC resistance Ri | ≥ 80 kΩ |
| Impedance Zi at 7.2 kV and 50 Hz | ≥ 6 MΩ |
| Terminals 2 and 3-5 | screw type, 0.2…4 mm² / 0.2…2.5 mm², AWG 24…12, 2.9 Nm |
| Degree of protection | IP64, built-in components IP20 |
| Enclosure | resin-encapsulated block in housing, 4 × M5 |
| Flammability class | UL 94 HB |
| Ambient temperature, operation | −10…+55 °C (UL −10…+45 °C) |
| Storage temperature | −20…+70 °C |
| Dimensions | 220 x 190 x 76 mm |
| Weight | 4500 g |
Part numbers
Show all part numbers (1)
B913033
How it compares with similar models
| Parameter | AGH520S Coupling Device for ISOMETER® in 3(N)AC Systems up to 7.2 kV | AGH204S-4 Coupling Device for ISOMETER® in 3AC IT Systems up to 1650 V | AGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kV | AGH150W and AGH150W-4 Coupling Devices for ISOMETER® in AC 1150 V and DC up to 1760 V Systems |
|---|---|---|---|---|
| Nominal system voltage Un | 3(N)AC 0…7.2 kV | — | AC, 3(N)AC 0…12 kV | AC 0…1150 V, DC 0…1100 V (AGH150W); AC 0…1150 V, DC 0…1760 V (AGH150W-4) |
| Rated insulation voltage | AC 6.3 kV | AC 1500 V | AC 12 kV | AC 1000 V (AGH150W); AC 1600 V (AGH150W-4) |
| Overvoltage category | III | III | — | CAT III |
| Internal DC resistance Ri | ≥ 80 kΩ | — | ≥ 160 kΩ | 80 kΩ (AGH150W); 160 kΩ (AGH150W-4) |
| Degree of protection | IP64, built-in components IP20 | IP30, built-in components IP10 | IP64, built-in components IP20 | IP30, built-in components IP10 |
| Enclosure | resin-encapsulated block in housing, 4 × M5 | X112, halogen-free, UL 94 V-0 | cast resin encapsulated, M5 mounting | — |
Request a price and lead time
AGH520S Coupling Device for ISOMETER® in 3(N)AC Systems up to 7.2 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which ISOMETER® units can be used with the AGH520S?
The iso685, IRDH275 and IRDH375 in AC systems up to 7.2 kV in online mode; the coupling device is for use only together with an ISOMETER.
What voltage applies to UL applications?
For UL applications nominal system voltage Un is AC 0…6.0 kV and operating temperature is −10…+45 °C.
What tightening torque and conductor size apply to the terminals?
Tightening torque is 2.9 Nm, with 0.2…4 mm² rigid or 0.2…2.5 mm² flexible conductors, AWG 24…12.