AGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kV

The AGH675S-7 series extends the voltage range of the ISOMETER® IRDH275BM-7 to AC/DC 0…7.2 kV, and the AGH675S-7MV15 version to 0…15.5 kV. Cable length 500 mm or 2000 mm, resin-encapsulated enclosure.

Nominal system voltage Un
AC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15)
Nominal frequency fn
0…460 Hz
Cable length
500 mm / 2000 mm
Rated insulation voltage
AC 7.2 kV / AC 15.5 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The AGH675S-7 and AGH675S-7MV15 coupling devices extend the nominal voltage range of the ISOMETER® IRDH275BM-7 shown in the wiring diagram. With one AGH675S-7, the IRDH275BM-7 monitors the insulation resistance of IT medium-voltage systems up to 7.2 kV. With two AGH675S-7MV15 it monitors IT systems up to 15.5 kV, and the two AGH675S-7MV15 units are always needed as a pair for one IRDH275BM-7.

Three types are listed: AGH675S-7-500 (500 mm cable), AGH675S-7-2000 (2000 mm cable) and AGH675S-7MV15-500 (500 mm cable). Nominal system voltage Un of the AGH675S-7 is AC, 3(N)AC, DC 0…7.2 kV at 0…460 Hz, with an internal DC resistance Ri of at least 2.39 MΩ. For the AGH675S-7MV15, Un is AC, 3(N)AC, DC 0…15.5 kV at 0…460 Hz and Ri is at least 4.7 MΩ. Rated insulation voltage is AC 7.2 kV and AC 15.5 kV respectively.

Terminal 5 of the AGH675S-7 is connected to terminal AK of the IRDH275BM-7. With two AGH675S-7MV15, both terminals 5 are connected in parallel to terminal AK. The high-voltage cable is encapsulated on the device side, and terminals 3, 4 and 5 are screw type for 0.2…4 mm² rigid or 0.2…2.5 mm² flexible conductors. The housing is a resin-encapsulated block with screw mounting 6 x M5, and any mounting position is permitted.

Built-in components are rated IP64 and the terminals IP20 to DIN EN 60529; the flammability class is UL94 HB, weight is up to 5100 g and dimensions are 280 x 320 x 155 mm. Operating temperature is −10…+60 °C, or −10…+55 °C for continuous operation with an asymmetrical earth fault. Climatic classes to IEC 60721 are 3K5 for stationary use, 2K3 for transport and 1K4 for long-term storage. Insulation is coordinated to DIN EN 61800-5-1, and CE and UKCA declarations are listed.

Technical specifications

Nominal system voltage UnAC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15)
Nominal frequency fn0…460 Hz
Cable length500 mm / 2000 mm
Rated insulation voltageAC 7.2 kV / AC 15.5 kV
Internal DC resistance Ri≥ 2.39 MΩ / ≥ 4.7 MΩ
Connectionhigh-voltage cable (encapsulated on the device side), screw type terminals 3, 4, 5
Conductor cross-section at terminals0.2…4 mm² / 0.2…2.5 mm²
Degree of protectionIP64 (built-in components) / IP20 (terminals)
Enclosureresin-encapsulated block, M5 mounting
Flammability classUL94 HB
Operating temperature−10…+60 °C (continuous operation with asymmetrical earth fault −10…+55 °C)
Storage temperature-40…+70 °C
Dimensions280 x 320 x 155 mm
Weight≤ 5100 g

Part numbers

Show all part numbers (3)

B913060 (AGH675S-7-500), B913061 (AGH675S-7-2000), B913058 (AGH675S-7MV15-500)

How it compares with similar models

ParameterAGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kVAGH520S Coupling Device for ISOMETER® in 3(N)AC Systems up to 7.2 kVAGH150W and AGH150W-4 Coupling Devices for ISOMETER® in AC 1150 V and DC up to 1760 V SystemsAGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kV
Nominal system voltage UnAC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15)3(N)AC 0…7.2 kVAC 0…1150 V, DC 0…1100 V (AGH150W); AC 0…1150 V, DC 0…1760 V (AGH150W-4)AC, 3(N)AC 0…12 kV
Rated insulation voltageAC 7.2 kV / AC 15.5 kVAC 6.3 kVAC 1000 V (AGH150W); AC 1600 V (AGH150W-4)AC 12 kV
Internal DC resistance Ri≥ 2.39 MΩ / ≥ 4.7 MΩ≥ 80 kΩ80 kΩ (AGH150W); 160 kΩ (AGH150W-4)≥ 160 kΩ
Degree of protectionIP64 (built-in components) / IP20 (terminals)IP64, built-in components IP20IP30, built-in components IP10IP64, built-in components IP20
Enclosureresin-encapsulated block, M5 mountingresin-encapsulated block in housing, 4 × M5—cast resin encapsulated, M5 mounting
Flammability classUL94 HBUL 94 HBUL94 V-0—

Request a price and lead time

AGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many AGH675S-7MV15 units are needed for 15.5 kV?

Two AGH675S-7MV15 per IRDH275BM-7, with both terminals 5 connected in parallel to terminal AK of the IRDH275BM-7.

What cable lengths are available?

AGH675S-7-500 and AGH675S-7MV15-500 have a 500 mm cable; AGH675S-7-2000 has a 2000 mm cable.

What protection class and operating temperature apply?

Built-in components are IP64 and terminals IP20; operation is −10…+60 °C, or −10…+55 °C in continuous operation with an asymmetrical earth fault.