AGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kV
The AGH675S-7 series extends the voltage range of the ISOMETER® IRDH275BM-7 to AC/DC 0…7.2 kV, and the AGH675S-7MV15 version to 0…15.5 kV. Cable length 500 mm or 2000 mm, resin-encapsulated enclosure.
- Nominal system voltage Un
- AC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15)
- Nominal frequency fn
- 0…460 Hz
- Cable length
- 500 mm / 2000 mm
- Rated insulation voltage
- AC 7.2 kV / AC 15.5 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The AGH675S-7 and AGH675S-7MV15 coupling devices extend the nominal voltage range of the ISOMETER® IRDH275BM-7 shown in the wiring diagram. With one AGH675S-7, the IRDH275BM-7 monitors the insulation resistance of IT medium-voltage systems up to 7.2 kV. With two AGH675S-7MV15 it monitors IT systems up to 15.5 kV, and the two AGH675S-7MV15 units are always needed as a pair for one IRDH275BM-7.
Three types are listed: AGH675S-7-500 (500 mm cable), AGH675S-7-2000 (2000 mm cable) and AGH675S-7MV15-500 (500 mm cable). Nominal system voltage Un of the AGH675S-7 is AC, 3(N)AC, DC 0…7.2 kV at 0…460 Hz, with an internal DC resistance Ri of at least 2.39 MΩ. For the AGH675S-7MV15, Un is AC, 3(N)AC, DC 0…15.5 kV at 0…460 Hz and Ri is at least 4.7 MΩ. Rated insulation voltage is AC 7.2 kV and AC 15.5 kV respectively.
Terminal 5 of the AGH675S-7 is connected to terminal AK of the IRDH275BM-7. With two AGH675S-7MV15, both terminals 5 are connected in parallel to terminal AK. The high-voltage cable is encapsulated on the device side, and terminals 3, 4 and 5 are screw type for 0.2…4 mm² rigid or 0.2…2.5 mm² flexible conductors. The housing is a resin-encapsulated block with screw mounting 6 x M5, and any mounting position is permitted.
Built-in components are rated IP64 and the terminals IP20 to DIN EN 60529; the flammability class is UL94 HB, weight is up to 5100 g and dimensions are 280 x 320 x 155 mm. Operating temperature is −10…+60 °C, or −10…+55 °C for continuous operation with an asymmetrical earth fault. Climatic classes to IEC 60721 are 3K5 for stationary use, 2K3 for transport and 1K4 for long-term storage. Insulation is coordinated to DIN EN 61800-5-1, and CE and UKCA declarations are listed.
Technical specifications
| Nominal system voltage Un | AC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15) |
|---|---|
| Nominal frequency fn | 0…460 Hz |
| Cable length | 500 mm / 2000 mm |
| Rated insulation voltage | AC 7.2 kV / AC 15.5 kV |
| Internal DC resistance Ri | ≥ 2.39 MΩ / ≥ 4.7 MΩ |
| Connection | high-voltage cable (encapsulated on the device side), screw type terminals 3, 4, 5 |
| Conductor cross-section at terminals | 0.2…4 mm² / 0.2…2.5 mm² |
| Degree of protection | IP64 (built-in components) / IP20 (terminals) |
| Enclosure | resin-encapsulated block, M5 mounting |
| Flammability class | UL94 HB |
| Operating temperature | −10…+60 °C (continuous operation with asymmetrical earth fault −10…+55 °C) |
| Storage temperature | -40…+70 °C |
| Dimensions | 280 x 320 x 155 mm |
| Weight | ≤ 5100 g |
Part numbers
Show all part numbers (3)
B913060 (AGH675S-7-500), B913061 (AGH675S-7-2000), B913058 (AGH675S-7MV15-500)
How it compares with similar models
| Parameter | AGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kV | AGH520S Coupling Device for ISOMETER® in 3(N)AC Systems up to 7.2 kV | AGH150W and AGH150W-4 Coupling Devices for ISOMETER® in AC 1150 V and DC up to 1760 V Systems | AGH676S-4 Coupling Device for ISOMETER® in AC/3(N)AC Systems up to 12 kV |
|---|---|---|---|---|
| Nominal system voltage Un | AC/DC 0…7.2 kV (AGH675S-7) / 0…15.5 kV (AGH675S-7MV15) | 3(N)AC 0…7.2 kV | AC 0…1150 V, DC 0…1100 V (AGH150W); AC 0…1150 V, DC 0…1760 V (AGH150W-4) | AC, 3(N)AC 0…12 kV |
| Rated insulation voltage | AC 7.2 kV / AC 15.5 kV | AC 6.3 kV | AC 1000 V (AGH150W); AC 1600 V (AGH150W-4) | AC 12 kV |
| Internal DC resistance Ri | ≥ 2.39 MΩ / ≥ 4.7 MΩ | ≥ 80 kΩ | 80 kΩ (AGH150W); 160 kΩ (AGH150W-4) | ≥ 160 kΩ |
| Degree of protection | IP64 (built-in components) / IP20 (terminals) | IP64, built-in components IP20 | IP30, built-in components IP10 | IP64, built-in components IP20 |
| Enclosure | resin-encapsulated block, M5 mounting | resin-encapsulated block in housing, 4 × M5 | — | cast resin encapsulated, M5 mounting |
| Flammability class | UL94 HB | UL 94 HB | UL94 V-0 | — |
Request a price and lead time
AGH675S-7 and AGH675S-7MV15 Coupling Devices for IRDH275BM-7, up to 7.2 kV and 15.5 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many AGH675S-7MV15 units are needed for 15.5 kV?
Two AGH675S-7MV15 per IRDH275BM-7, with both terminals 5 connected in parallel to terminal AK of the IRDH275BM-7.
What cable lengths are available?
AGH675S-7-500 and AGH675S-7MV15-500 have a 500 mm cable; AGH675S-7-2000 has a 2000 mm cable.
What protection class and operating temperature apply?
Built-in components are IP64 and terminals IP20; operation is −10…+60 °C, or −10…+55 °C in continuous operation with an asymmetrical earth fault.