CD14400 coupling device for NGR monitoring in HRG systems up to 14400 V
The CD14400 extends the range of an NGR monitor in high resistance grounding (HRG) systems up to a system voltage of 14400 V. Rated voltage is 8400 V, protection is IP54 and ground fault duty is limited to 60 s.
- System voltage ULL
- до 14400 V
- UNGR
- 8400 V
- Rated voltage
- 8400 V
- Rated insulation voltage
- 8400 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Coupling device CD14400 connects an NGR monitor, which watches the neutral grounding resistance, to high resistance grounding (HRG) systems with a system voltage up to 14400 V. It extends the monitor's range to these higher voltages.
Rated voltage is 8400 V, rated insulation voltage 8400 V and UNGR 8400 V, while system voltage ULL reaches 14400 V. The voltage range is DC, 50/60 Hz, 10…3200 Hz. Current is 84 mA, resistance 100 kΩ and temperature coefficient 20 ppm/K.
In case of a ground fault the operating mode is limited to a maximum of 60 s. There is no galvanic separation between the circuits. Overvoltage category is III and pollution degree 2.
The enclosure has protection IP54 and flammability class UL 94V-0, and weighs less than 4.4 kg. Ambient temperature is -40…+70 °C, or -40…+60 °C for UL, humidity up to 98 % and operating altitude up to 5000 m AMSL. It can be mounted in any position.
The device follows DIN EN 50178:1997 and DIN EN 60529, with environmental conditions per the IEC 60721-3 series. CE and UKCA declarations of conformity exist. Part number: B98039054.
Technical specifications
| System voltage ULL | до 14400 V |
|---|---|
| UNGR | 8400 V |
| Rated voltage | 8400 V |
| Rated insulation voltage | 8400 V |
| Overvoltage category | III |
| Pollution degree | 2 |
| Voltage range | DC, 50/60 Hz, 10…3200 Hz |
| Current | 84 mA |
| Resistance | 100 kΩ |
| Temperature coefficient | 20 ppm/K |
| Ambient temperature | -40…+70 °C |
| Ambient temperature for UL | -40…+60 °C |
| Humidity | ≤ 98 % |
| Degree of protection | IP54 |
| Operating altitude | up to 5000 m AMSL |
| Operating mode | in case of a ground fault maximum 60 s |
| Weight | < 4.4 kg |
Part numbers
Show all part numbers (1)
B98039054
How it compares with similar models
| Parameter | CD14400 coupling device for NGR monitoring in HRG systems up to 14400 V | CD25000 coupling device for NGR monitoring in HRG systems up to AC 25 kV and DC 14.5 kV | CD5000 coupling device for NGR monitoring in HRG systems up to AC 4300 V and DC 2500 V | CD1000-2 coupling device for NGR monitors in HRG systems up to 1000 V |
|---|---|---|---|---|
| Rated voltage | 8400 V | 14500 V | 2500 V | 600 V |
| Rated insulation voltage | 8400 V | 14500 V | 3 kV | — |
| Resistance | 100 kΩ | 100 kΩ | 20 kΩ | 20 kΩ |
| Weight | < 4.4 kg | < 11 kg | < 3800 g | < 700 g |
Request a price and lead time
CD14400 coupling device for NGR monitoring in HRG systems up to 14400 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the CD14400 used for?
It extends the range of an NGR monitor in HRG systems up to a system voltage ULL of 14400 V.
How long may a ground fault last?
In case of a ground fault the operating mode is limited to a maximum of 60 s.
What ambient temperature and altitude are permitted?
Ambient temperature is -40…+70 °C (-40…+60 °C for UL) and altitude up to 5000 m AMSL, with protection IP54.