CD5000 coupling device for NGR monitoring in HRG systems up to AC 4300 V and DC 2500 V

The CD5000 links an NGR monitor to high resistance grounding (HRG) systems with a system voltage up to AC 4300 V and/or DC 2500 V. Rated voltage is 2500 V, resistance 20 kΩ, and operation is continuous.

System voltage
до AC 4300 V / DC 2500 V
Rated voltage
2500 V
Rated current
125 mA
Resistance
20 kΩ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Designed for use with NGR monitors in high resistance grounding (HRG) systems, the CD5000 coupling device suits system voltages up to AC 4300 V and/or DC 2500 V. It is rated for continuous operation.

Rated voltage is 2500 V, rated current 125 mA, resistance 20 kΩ and rated insulation voltage 3 kV. The voltage range is DC, 50/60 Hz, 10…3200 Hz, and overload capacity is 1.15 x Un for less than 5 minutes. Temperature coefficient is ± 1 % / 20 ppm/K, overvoltage category III and pollution degree 2.

Terminals G1 and G take a cable lug with a conductor of at least 1.5 mm². PE takes a cable lug M6 or M10 with at least 2.5 mm². Tightening torque is 0.5…0.6 Nm and conductor sizes are AWG 24-12.

The device mounts in any position on a grounded metal plate of at least 600 x 300 mm. Operating altitude is up to 5000 m AMSL, ambient temperature -40…+70 °C (-40…+60 °C for UL) and humidity up to 98 %. Internal components are IP0, flammability class is UL 94V-0 and weight is under 3800 g.

It follows DIN EN 50178:1997 and DIN EN 60529, with environmental conditions per the IEC 60721-3 series. Part number: B98039011.

Technical specifications

System voltageдо AC 4300 V / DC 2500 V
Rated voltage2500 V
Rated current125 mA
Resistance20 kΩ
Rated insulation voltage3 kV
Voltage rangeDC, 50/60 Hz, 10…3200 Hz
Overload capacity1.15 x Un for < 5 minutes
Overvoltage categoryIII
Pollution degree2
Ambient temperature-40…+70 °C
Ambient temperature for UL-40…+60 °C
Humidity≤ 98 %
Tightening torque0.5…0.6 Nm
Conductor sizesAWG 24-12
Operating altitudeup to 5000 m AMSL
Flammability classUL 94V-0
Weight< 3800 g

Part numbers

Show all part numbers (1)

B98039011

How it compares with similar models

ParameterCD5000 coupling device for NGR monitoring in HRG systems up to AC 4300 V and DC 2500 VCD14400 coupling device for NGR monitoring in HRG systems up to 14400 VCD25000 coupling device for NGR monitoring in HRG systems up to AC 25 kV and DC 14.5 kVCD1000-2 coupling device for NGR monitors in HRG systems up to 1000 V
Rated voltage2500 V8400 V14500 V600 V
Resistance20 kΩ100 kΩ100 kΩ20 kΩ
Rated insulation voltage3 kV8400 V14500 V—
Flammability classUL 94V-0—UL 94 V-0UL 94V-0
Weight< 3800 g< 4.4 kg< 11 kg< 700 g

Request a price and lead time

CD5000 coupling device for NGR monitoring in HRG systems up to AC 4300 V and DC 2500 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which systems is the CD5000 intended for?

HRG systems with a system voltage up to AC 4300 V and/or DC 2500 V that use an NGR monitor.

How is the CD5000 mounted?

In any position on a grounded metal plate of at least 600 x 300 mm.

What is its overload capacity?

1.15 x Un for less than 5 minutes, at a rated voltage of 2500 V.