CD1000 coupling device for NGR monitors in HRG systems up to AC 690 V

The CD1000 couples an NGR monitor to an HRG system up to AC 690 V and DC 400 V. It presents 20 kΩ at 30 mA, works at altitudes up to 2000 m, weighs under 190 g and has IP30 protection.

System voltage
up to 690 V (AC), 400 V (DC)
UNGR
400 V
Operating altitude
up to 2000 m
Resistance
20 kΩ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Use the CD1000 where a high-resistance grounded (HRG) system runs at up to AC 690 V and DC 400 V and an NGR monitor must be attached. The device is wired to the star point of the system and to the sensing and earth terminals of the monitor. It presents a fixed resistance of 20 kΩ with a current of 30 mA, and its duty time is unlimited.

The housing is 105 x 89 x 41.5 mm and weighs under 190 g. Connections are screw type and the unit can be mounted in any position. Operating altitude is up to 2000 m, ambient temperature -40…+70 °C, humidity up to 98 %, protection degree IP30 and flammability class UL94 HB.

Nominal system voltage Un reaches ULL = 690 V (UNGR = 400 V). The voltage range is stated as DC, 50/60 Hz, 10…3200 Hz 400 V. Overload capacity is 1.15 x Un for less than 30 minutes. Insulation is coordinated to DIN EN 50178:1997, with overvoltage category III and pollution degree 2.

At the maximum voltage the unit sheds heat through an earthed metal plate of at least 300 x 300 mm, to which it is fixed. Environmental classes follow IEC 60721-3-3 for use, IEC 60721-3-2 for transport and IEC 60721-3-1 for storage, and the enclosure rating is assessed to DIN EN 60529 and IEC 60529.

The CD1000 belongs to the same series as the CD1000-2 but covers a lower voltage and lower altitude, so the choice depends on ULL and UNGR of the installation. Ordering number B98039010. Fitting and wiring are for electrically skilled persons.

Technical specifications

System voltageup to 690 V (AC), 400 V (DC)
UNGR400 V
Operating altitudeup to 2000 m
Resistance20 kΩ
Current30 mA
Overload capacity1.15 x Un, < 30 min
Overvoltage categoryIII
Pollution degree2
Ambient temperature-40…+70 °C
Humidity≤ 98 %
Protection degreeIP30
Flammability classUL94 HB
Weight< 190 g
Dimensions105 x 89 x 41.5 mm

Part numbers

Show all part numbers (1)

B98039010

How it compares with similar models

ParameterCD1000 coupling device for NGR monitors in HRG systems up to AC 690 VCD1000-2 coupling device for NGR monitors in HRG systems up to 1000 VCD5000 coupling device for NGR monitoring in HRG systems up to AC 4300 V and DC 2500 VCD14400 coupling device for NGR monitoring in HRG systems up to 14400 V
Operating altitudeup to 2000 mup to 5000 m AMSLup to 5000 m AMSLup to 5000 m AMSL
Resistance20 kΩ20 kΩ20 kΩ100 kΩ
Flammability classUL94 HBUL 94V-0UL 94V-0—
Weight< 190 g< 700 g< 3800 g< 4.4 kg

Request a price and lead time

CD1000 coupling device for NGR monitors in HRG systems up to AC 690 V. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What voltage is the CD1000 rated for?

Up to AC 690 V and DC 400 V, with ULL up to 690 V at UNGR = 400 V.

What resistance does the device present?

20 kΩ at a current of 30 mA.

Does it need extra cooling?

At the maximum voltage ULL = 690 V it should be fixed to an earthed metal plate of at least 300 x 300 mm.