CD1000 coupling device for NGR monitors in HRG systems up to AC 690 V
The CD1000 couples an NGR monitor to an HRG system up to AC 690 V and DC 400 V. It presents 20 kΩ at 30 mA, works at altitudes up to 2000 m, weighs under 190 g and has IP30 protection.
- System voltage
- up to 690 V (AC), 400 V (DC)
- UNGR
- 400 V
- Operating altitude
- up to 2000 m
- Resistance
- 20 kΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Use the CD1000 where a high-resistance grounded (HRG) system runs at up to AC 690 V and DC 400 V and an NGR monitor must be attached. The device is wired to the star point of the system and to the sensing and earth terminals of the monitor. It presents a fixed resistance of 20 kΩ with a current of 30 mA, and its duty time is unlimited.
The housing is 105 x 89 x 41.5 mm and weighs under 190 g. Connections are screw type and the unit can be mounted in any position. Operating altitude is up to 2000 m, ambient temperature -40…+70 °C, humidity up to 98 %, protection degree IP30 and flammability class UL94 HB.
Nominal system voltage Un reaches ULL = 690 V (UNGR = 400 V). The voltage range is stated as DC, 50/60 Hz, 10…3200 Hz 400 V. Overload capacity is 1.15 x Un for less than 30 minutes. Insulation is coordinated to DIN EN 50178:1997, with overvoltage category III and pollution degree 2.
At the maximum voltage the unit sheds heat through an earthed metal plate of at least 300 x 300 mm, to which it is fixed. Environmental classes follow IEC 60721-3-3 for use, IEC 60721-3-2 for transport and IEC 60721-3-1 for storage, and the enclosure rating is assessed to DIN EN 60529 and IEC 60529.
The CD1000 belongs to the same series as the CD1000-2 but covers a lower voltage and lower altitude, so the choice depends on ULL and UNGR of the installation. Ordering number B98039010. Fitting and wiring are for electrically skilled persons.
Technical specifications
| System voltage | up to 690 V (AC), 400 V (DC) |
|---|---|
| UNGR | 400 V |
| Operating altitude | up to 2000 m |
| Resistance | 20 kΩ |
| Current | 30 mA |
| Overload capacity | 1.15 x Un, < 30 min |
| Overvoltage category | III |
| Pollution degree | 2 |
| Ambient temperature | -40…+70 °C |
| Humidity | ≤ 98 % |
| Protection degree | IP30 |
| Flammability class | UL94 HB |
| Weight | < 190 g |
| Dimensions | 105 x 89 x 41.5 mm |
Part numbers
Show all part numbers (1)
B98039010
How it compares with similar models
| Parameter | CD1000 coupling device for NGR monitors in HRG systems up to AC 690 V | CD1000-2 coupling device for NGR monitors in HRG systems up to 1000 V | CD5000 coupling device for NGR monitoring in HRG systems up to AC 4300 V and DC 2500 V | CD14400 coupling device for NGR monitoring in HRG systems up to 14400 V |
|---|---|---|---|---|
| Operating altitude | up to 2000 m | up to 5000 m AMSL | up to 5000 m AMSL | up to 5000 m AMSL |
| Resistance | 20 kΩ | 20 kΩ | 20 kΩ | 100 kΩ |
| Flammability class | UL94 HB | UL 94V-0 | UL 94V-0 | — |
| Weight | < 190 g | < 700 g | < 3800 g | < 4.4 kg |
Request a price and lead time
CD1000 coupling device for NGR monitors in HRG systems up to AC 690 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What voltage is the CD1000 rated for?
Up to AC 690 V and DC 400 V, with ULL up to 690 V at UNGR = 400 V.
What resistance does the device present?
20 kΩ at a current of 30 mA.
Does it need extra cooling?
At the maximum voltage ULL = 690 V it should be fixed to an earthed metal plate of at least 300 x 300 mm.
Similar equipment from other manufacturers