AL-4 earth-fault current relay (АЛ-4), settings 0.005-0.150 A
The АЛ-4 (AL-4) is an instantaneous earth-fault current relay with one current circuit and high sensitivity. Settings run from 0.005 to 0.150 A, and operate time is not more than 0.06 s at 1.2 times the setting and 0.04 s at 3 times.
- Rated current
- 0.16 A
- Trip current setting range
- 0.005-0.150 A
- Setting step
- 0.0015 A
- Operate time at 1.2 / 3 times the setting
- not more than 0.06 s / not more than 0.04 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The АЛ-4 monitors earth-fault current through a single current circuit and trips without intentional delay. It is used with a zero-sequence current transformer to protect generators, motors and lines with low earth-fault currents, and in other relay protection, emergency and industrial automation devices.
Rated current is 0.16 A. The trip current is set from 0.005 to 0.150 A in 0.0015 A steps. Mean basic error of the trip current at any marked scale point is within 10 % of the setting, and the spread of trip current stays within 2.5 % of the mean. Accuracy class is 5 and the reset ratio is not less than 0.93.
Operate time is not more than 0.06 s at 1.2 times the setting and not more than 0.04 s at 3 times. The output is one changeover contact. Burden is not more than 0.1 VA at minimum setting current and 0.2 VA at rated current in the current circuits, and not more than 6.5 VA (10 W) in the supply circuit. Supply is DC 110 V or 220 V, or AC 110 V or 220 V, depending on the version.
Mechanical life is not less than 100000 cycles and switching life not less than 20000 cycles. The relay is IP40 and the terminal block IP10. The climatic version is УХЛ4, for minus 40 to plus 55 °C, and the mass is not more than 0.8 kg.
Mounting is on a DIN rail. The operating diagram and the connection diagram are given in the product documentation.
Technical specifications
| Rated current | 0.16 A |
|---|---|
| Trip current setting range | 0.005-0.150 A |
| Setting step | 0.0015 A |
| Operate time at 1.2 / 3 times the setting | not more than 0.06 s / not more than 0.04 s |
| Rated supply voltage | DC 110 V; 220 V, AC 110 V; 220 V (by version) |
| Burden in current circuits | not more than 0.1 VA (I = Іmin); 0.2 VA (I = Іном) |
| Burden in supply circuit | not more than 6.5 VA (10 W) |
| Contacts | 1 changeover |
| Accuracy class | 5 |
| Reset ratio | not less than 0.93 |
| Mechanical life | not less than 100000 cycles |
| Switching life | not less than 20000 cycles |
| Protection degree, relay / terminal block | IP40 / IP10 |
| Climatic version | УХЛ4 |
| Operating temperature | from minus 40 to plus 55 °C |
| Mass | not more than 0.8 kg |
Part numbers
Show all part numbers (1)
АЛ-4
How it compares with similar models
| Parameter | AL-4 earth-fault current relay (АЛ-4), settings 0.005-0.150 A | АЛ-1 AC overcurrent relay, settings 0.05-100 A in five ranges | AL-4-1, AL-4-2 earth-fault current relays (АЛ-4-1, АЛ-4-2), 0.02-0.2 A | ВЛ-50 time relay for railway rolling stock, 2–200 s settings, 27–110 V DC supply |
|---|---|---|---|---|
| Setting step | 0.0015 A | 0.005; 0.0125; 0.05; 0.25; 1.25 A | 0.002 A | — |
| Rated supply voltage | DC 110 V; 220 V, AC 110 V; 220 V (by version) | =110, 220 V; ~100, 220 V | DC 110 V; 220 V, AC 110 V; 220 V | DC 27, 50, 75, 110 V |
| Accuracy class | 5 | 5 | 5 | 4/0.1 |
| Reset ratio | not less than 0.93 | not less than 0.9 | not less than 0.9 | — |
European equivalents
Earth Fault Locator selective detection of the feeder with an earth fault, Earth 4.0 / Earth Zero / Earth Zero Flag earth fault indicators with a sum current sensor
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
AL-4 earth-fault current relay (АЛ-4), settings 0.005-0.150 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What setting range does the АЛ-4 have?
0.005-0.150 A in steps of 0.0015 A.
How fast does it operate?
Not more than 0.06 s at 1.2 times the setting and not more than 0.04 s at 3 times.
Where is the АЛ-4 used?
In earth-fault protection of generators, motors and lines with low earth-fault currents, together with a zero-sequence current transformer.
Similar equipment from other manufacturers