ПЕ45А, ПЕ45А-1 electromagnetic intermediate relay with off-delay of 0,05 - 3,0 s
The ПЕ45А and ПЕ45А-1 are monostable electromagnetic intermediate relays with an adjustable off-delay of 0,05 to 3,0 s. They run on 220 V DC or 50 Hz AC and switch 12-250 V, with 4 contacts in the ПЕ45А and 2 in the ПЕ45А-1.
- Type
- monostable, off-delay
- Rated supply voltage
- DC 220 V; AC 50 Hz 220 V
- Maximum supply voltage
- 1,2 Unom
- Output contacts (independent changeover)
- ПЕ45А 4; ПЕ45А-1 2
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ПЕ45А and ПЕ45А-1 are monostable electromagnetic relays with a delay on drop-out. They serve as auxiliary relays in DC and AC circuits at 50 and 60 Hz, in protection, control and automation schemes of power and industrial equipment.
The drop-out time is set within 0,05 – 3,0 s in steps of 0,05 s, and the spread of drop-out time is not more than 10%. The rated supply is 220 V DC or 220 V AC at 50 Hz, with a maximum permitted supply of 1,2 Unom. Pick-up voltage is (0,60 - 0,75) Unom, drop-out voltage is (0,4 - 0,5) Unom and the operate time at Unom is not more than 0,05 s. Consumption is 3,5 W on DC and 3,5 VA on AC, with a pulse current of not more than 0,3 A.
The outputs are independent changeover contacts, four in the ПЕ45А and two in the ПЕ45А-1. Switched voltage is 12-250 V AC/DC and switched current is from 0,1 to 5 A, up to 1 A at 60 V and up to 0,25 A at 250 V. Switched power is 450 VA on AC and 50 W on DC. Mechanical endurance is not less than 500000 cycles and switching endurance is not less than 100000 cycles.
The relay operates from minus 40 to plus 55 °C and up to 98% relative humidity at 25 °C, climatic version У3. Protection is IP30 for the housing and IP10 for the terminals to ГОСТ 14254-96. Weight is 0,3 kg.
Technical specifications
| Type | monostable, off-delay |
|---|---|
| Rated supply voltage | DC 220 V; AC 50 Hz 220 V |
| Maximum supply voltage | 1,2 Unom |
| Output contacts (independent changeover) | ПЕ45А 4; ПЕ45А-1 2 |
| Power consumption | 3,5 W (DC), 3,5 VA (AC) |
| Pulse current | not more than 0,3 A |
| Pick-up voltage | (0,60 - 0,75) Unom |
| Drop-out voltage | (0,4 - 0,5) Unom |
| Operate time at Unom | not more than 0,05 s |
| Drop-out time (setting) | 0,05 – 3,0 s, resolution 0,05 s, spread 10% |
| Switched voltages AC/DC | 12-250 V |
| Switched currents AC/DC | from 0,1 to 5 A; up to 1 A (60 V), up to 0,25 A (250 V) |
| Switched power | AC 450 VA; DC 50 W |
| Mechanical endurance | not less than 500000 cycles |
| Switching endurance | not less than 100000 cycles |
| Protection degree | IP30 (housing), IP10 (terminals) |
| Air temperature | from minus 40 to plus 55 °C |
| Weight | 0,3 kg |
Part numbers
Show all part numbers (2)
ПЕ45А, ПЕ45А-1
How it compares with similar models
| Parameter | ПЕ45А, ПЕ45А-1 electromagnetic intermediate relay with off-delay of 0,05 - 3,0 s | ПЕ45Н electromagnetic intermediate relay with off-delay of 0,05 - 1,0 s and neutral relay | ПЕ45 electromagnetic intermediate relay with off-delay of 0,05 - 0,5 s and 0,4 - 2,5 s | ПЕ44, ПЕ44-М electromagnetic intermediate relay with on-delay of 0,05 - 0,253 s |
|---|---|---|---|---|
| Type | monostable, off-delay | off-delay, with neutral relay | off-delay, with bistable relay | on-delay, 2 or 3 holding current windings |
| Mechanical endurance | not less than 500000 cycles | 100000 cycles | 100000 cycles | 100000 cycles |
| Switching endurance | not less than 100000 cycles | 50000 cycles | 50000 cycles | 50000 cycles |
| Protection degree | IP30 (housing), IP10 (terminals) | IP40 (relay), IP10 (screw terminals) | IP40 (relay), IP10 (screw terminals) | IP40 (relay), IP10 (screw terminals) |
European equivalents
Auxiliary, bistable and contactor relays for substations
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
ПЕ45А, ПЕ45А-1 electromagnetic intermediate relay with off-delay of 0,05 - 3,0 s. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the off-delay range?
It is set from 0,05 to 3,0 s in steps of 0,05 s, with a spread of not more than 10%.
How do the ПЕ45А and ПЕ45А-1 differ?
They differ in the number of independent changeover output contacts, four in the ПЕ45А and two in the ПЕ45А-1.
What load can the contacts carry?
They switch 12-250 V AC/DC at 0,1 to 5 A, up to 1 A at 60 V and up to 0,25 A at 250 V, with 450 VA (AC) and 50 W (DC) switched power.