ПЕ45Н electromagnetic intermediate relay with off-delay of 0,05 - 1,0 s and neutral relay
The ПЕ45Н is an electromagnetic intermediate relay for DC and AC, built with a neutral relay, with an off-delay of 0,05 to 1,0 s. Turn-on time is not more than 0,05 s, and it switches 24-230 V DC and 24-400 V AC.
- Type
- off-delay, with neutral relay
- Switched circuits
- DC 24 - 230 V; AC 24 - 400 V, 50 and 60 Hz
- Turn-on time
- not more than 0,05 s
- Drop-out time (delay)
- from 0,05 to 1,0 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ПЕ45Н has a release delay of 0,05 to 1,0 s and a turn-on time of not more than 0,05 s. It works on DC and AC and is built with a neutral relay. It is used in protection, control and automation circuits of power equipment to switch DC loads rated 24 to 230 V and AC loads rated 24 to 400 V at 50 and 60 Hz.
On DC the pick-up voltage is 0,6-0,7 Unom and the drop-out voltage is 0,3 Unom. The relay carries up to 6 contact groups, with a minimum contact current of 0,02 A at 24 V and 0,01 A at 110 V and above. Coils draw not more than 6 W on DC and 10 VA on AC. Mechanical endurance is 100000 cycles and switching endurance is 50000 cycles.
The insulation test voltage is 2500 V between all electrically independent circuits and the case and between independent circuits, 1000 V between the open contacts of each group and 550 V between coils. The insulation resistance of a dry, clean relay is not less than 20 MOhm cold and 6 MOhm heated.
The relays are made in У3 and Т3 versions for ambient temperatures from minus 40 to plus 55 °C. Vibration is tolerated up to 15 Hz at 3g and from 15 to 100 Hz at 1g. Protection is IP40 for the relay and IP10 for screw terminals to ГОСТ 14254-96. Wire cross-section is 0,12‑1,5 mm² for soldering and 0,75‑2,5 mm² for screw terminals. DIN rail mounting needs an additional module.
Technical specifications
| Type | off-delay, with neutral relay |
|---|---|
| Switched circuits | DC 24 - 230 V; AC 24 - 400 V, 50 and 60 Hz |
| Turn-on time | not more than 0,05 s |
| Drop-out time (delay) | from 0,05 to 1,0 s |
| Pick-up voltage (DC) | 0,6-0,7 Unom |
| Drop-out voltage (DC) | 0,3 Unom |
| Minimum contact current | 0,02 A at 24 V; 0,01 A at 110 V and above |
| Coil power consumption | DC not more than 6 W; AC not more than 10 VA |
| Insulation test voltage | 2500 V between independent circuits and case; 1000 V between open contacts; 550 V between coils |
| Insulation resistance | 20 MOhm (cold), 6 MOhm (heated) |
| Protection degree | IP40 (relay), IP10 (screw terminals) |
| Ambient temperature | from minus 40 to plus 55 °C |
| Vibration | up to 15 Hz at 3g, 15 to 100 Hz at 1g |
| Wire cross-section | soldering 0,12‑1,5 mm²; screw 0,75‑2,5 mm² |
| Number of contacts | up to 6 groups |
| Mechanical endurance | 100000 cycles |
| Switching endurance | 50000 cycles |
How it compares with similar models
| Parameter | ПЕ45Н electromagnetic intermediate relay with off-delay of 0,05 - 1,0 s and neutral relay | ПЕ45 electromagnetic intermediate relay with off-delay of 0,05 - 0,5 s and 0,4 - 2,5 s | ПЕ44, ПЕ44-М electromagnetic intermediate relay with on-delay of 0,05 - 0,253 s | ПЕ46, ПЕ46-1 two-position electromagnetic intermediate relay for 24-230 V DC and 24-400 V AC |
|---|---|---|---|---|
| Type | off-delay, with neutral relay | off-delay, with bistable relay | on-delay, 2 or 3 holding current windings | two-position, DC and AC |
| Turn-on time | not more than 0,05 s | not more than 0,05 s | — | not more than 0,03 s |
| Number of contacts | up to 6 groups | up to 6 groups | up to 6 groups | up to 6 groups, normally open and normally closed |
European equivalents
Auxiliary, bistable and contactor relays for substations
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
ПЕ45Н electromagnetic intermediate relay with off-delay of 0,05 - 1,0 s and neutral relay. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What release delay does the ПЕ45Н offer?
The delay is 0,05 to 1,0 s, and the turn-on time is not more than 0,05 s.
What are the pick-up and drop-out voltages on DC?
Pick-up is at 0,6-0,7 Unom and drop-out is at 0,3 Unom.
How many contact groups and what endurance?
Up to 6 contact groups, with a mechanical endurance of 100000 cycles and a switching endurance of 50000 cycles.