АЛ-1 AC overcurrent relay, settings 0.05-100 A in five ranges
The АЛ-1 relay detects an unacceptable rise of current in AC relay protection circuits. It comes in five rated currents from 0.4 to 16 A, operates in not more than 0.05 s, and has accuracy class 5.
- Rated current
- 0.4; 1.0; 5.0; 10; 16 A
- Trip setting ranges
- 0.05-0.40; 0.125-1.0; 0.5-4.0; 2.5-20; 12.5-100 A
- Setting step
- 0.005; 0.0125; 0.05; 0.25; 1.25 A
- Rated supply voltage
- =110, 220 V; ~100, 220 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The АЛ-1 is built into AC circuits of relay protection and emergency automation, where it responds to a rising current in the monitored circuit. In practice it flags a current that has grown past its permitted level.
Five versions exist by rated current: 0.4, 1.0, 5.0, 10 and 16 A. Their trip setting ranges are 0.05-0.40, 0.125-1.0, 0.5-4.0, 2.5-20 and 12.5-100 A, with setting steps of 0.005, 0.0125, 0.05, 0.25 and 1.25 A. Mean basic error of the trip current at any marked scale point is within 5 % of the setting, and the spread stays within 2.5 % of the mean.
Supply voltage is =110, 220 V or ~100, 220 V. Operate time is not more than 0.05 s at 1.2 times the setting and not more than 0.03 s at 3 times. The output has 1 make and 1 break contact. Accuracy class is 5 and the reset ratio is not less than 0.9.
Mechanical life is not less than 100000 cycles and switching life not less than 20000 cycles. The relay body is IP40 and the terminal block IP10. Climatic versions are У3 and Т3, for minus 40 to plus 55 °C. Mass is not more than 0.8 kg.
Fix the relay on a DIN rail. The operating diagram and connection diagram are in the product documentation.
Technical specifications
| Rated current | 0.4; 1.0; 5.0; 10; 16 A |
|---|---|
| Trip setting ranges | 0.05-0.40; 0.125-1.0; 0.5-4.0; 2.5-20; 12.5-100 A |
| Setting step | 0.005; 0.0125; 0.05; 0.25; 1.25 A |
| Rated supply voltage | =110, 220 V; ~100, 220 V |
| Operate time at 1.2 / 3 times the setting | not more than 0.05 s / not more than 0.03 s |
| Contacts | 1 make and 1 break |
| Accuracy class | 5 |
| Reset ratio | not less than 0.9 |
| Mechanical life | not less than 100000 cycles |
| Switching life | not less than 20000 cycles |
| Protection degree, relay / terminal block | IP40 / IP10 |
| Climatic versions | У3, Т3 |
| Operating temperature | from minus 40 to plus 55 °C |
| Mass | not more than 0.8 kg |
Part numbers
Show all part numbers (1)
АЛ-1
How it compares with similar models
| Parameter | АЛ-1 AC overcurrent relay, settings 0.05-100 A in five ranges | AL-4 earth-fault current relay (АЛ-4), settings 0.005-0.150 A | AL-4-1, AL-4-2 earth-fault current relays (АЛ-4-1, АЛ-4-2), 0.02-0.2 A | ВЛ-50 time relay for railway rolling stock, 2–200 s settings, 27–110 V DC supply |
|---|---|---|---|---|
| Setting step | 0.005; 0.0125; 0.05; 0.25; 1.25 A | 0.0015 A | 0.002 A | — |
| Rated supply voltage | =110, 220 V; ~100, 220 V | DC 110 V; 220 V, AC 110 V; 220 V (by version) | DC 110 V; 220 V, AC 110 V; 220 V | DC 27, 50, 75, 110 V |
| Accuracy class | 5 | 5 | 5 | 4/0.1 |
| Reset ratio | not less than 0.9 | not less than 0.93 | not less than 0.9 | — |
European equivalents
IPR-A / IPR-A2 / IPR-D / IPR96D overcurrent and earth fault protection relays for MV feeders
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
АЛ-1 AC overcurrent relay, settings 0.05-100 A in five ranges. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What setting ranges does the АЛ-1 offer?
Five ranges: 0.05-0.40, 0.125-1.0, 0.5-4.0, 2.5-20 and 12.5-100 A.
How fast does it operate?
Not more than 0.05 s at 1.2 times the setting and not more than 0.03 s at 3 times.
What contacts does the output have?
One make and one break contact.