International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

АЛ-1 AC overcurrent relay, settings 0.05-100 A in five ranges

The АЛ-1 relay detects an unacceptable rise of current in AC relay protection circuits. It comes in five rated currents from 0.4 to 16 A, operates in not more than 0.05 s, and has accuracy class 5.

Rated current
0.4; 1.0; 5.0; 10; 16 A
Trip setting ranges
0.05-0.40; 0.125-1.0; 0.5-4.0; 2.5-20; 12.5-100 A
Setting step
0.005; 0.0125; 0.05; 0.25; 1.25 A
Rated supply voltage
=110, 220 V; ~100, 220 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The АЛ-1 is built into AC circuits of relay protection and emergency automation, where it responds to a rising current in the monitored circuit. In practice it flags a current that has grown past its permitted level.

Five versions exist by rated current: 0.4, 1.0, 5.0, 10 and 16 A. Their trip setting ranges are 0.05-0.40, 0.125-1.0, 0.5-4.0, 2.5-20 and 12.5-100 A, with setting steps of 0.005, 0.0125, 0.05, 0.25 and 1.25 A. Mean basic error of the trip current at any marked scale point is within 5 % of the setting, and the spread stays within 2.5 % of the mean.

Supply voltage is =110, 220 V or ~100, 220 V. Operate time is not more than 0.05 s at 1.2 times the setting and not more than 0.03 s at 3 times. The output has 1 make and 1 break contact. Accuracy class is 5 and the reset ratio is not less than 0.9.

Mechanical life is not less than 100000 cycles and switching life not less than 20000 cycles. The relay body is IP40 and the terminal block IP10. Climatic versions are У3 and Т3, for minus 40 to plus 55 °C. Mass is not more than 0.8 kg.

Fix the relay on a DIN rail. The operating diagram and connection diagram are in the product documentation.

Technical specifications

Rated current0.4; 1.0; 5.0; 10; 16 A
Trip setting ranges0.05-0.40; 0.125-1.0; 0.5-4.0; 2.5-20; 12.5-100 A
Setting step0.005; 0.0125; 0.05; 0.25; 1.25 A
Rated supply voltage=110, 220 V; ~100, 220 V
Operate time at 1.2 / 3 times the settingnot more than 0.05 s / not more than 0.03 s
Contacts1 make and 1 break
Accuracy class5
Reset rationot less than 0.9
Mechanical lifenot less than 100000 cycles
Switching lifenot less than 20000 cycles
Protection degree, relay / terminal blockIP40 / IP10
Climatic versionsУ3, Т3
Operating temperaturefrom minus 40 to plus 55 °C
Massnot more than 0.8 kg

Part numbers

Show all part numbers (1)

АЛ-1

How it compares with similar models

ParameterАЛ-1 AC overcurrent relay, settings 0.05-100 A in five rangesAL-4 earth-fault current relay (АЛ-4), settings 0.005-0.150 AAL-4-1, AL-4-2 earth-fault current relays (АЛ-4-1, АЛ-4-2), 0.02-0.2 AВЛ-50 time relay for railway rolling stock, 2–200 s settings, 27–110 V DC supply
Setting step0.005; 0.0125; 0.05; 0.25; 1.25 A0.0015 A0.002 A—
Rated supply voltage=110, 220 V; ~100, 220 VDC 110 V; 220 V, AC 110 V; 220 V (by version)DC 110 V; 220 V, AC 110 V; 220 VDC 27, 50, 75, 110 V
Accuracy class5554/0.1
Reset rationot less than 0.9not less than 0.93not less than 0.9—

European equivalents

IPR-A / IPR-A2 / IPR-D / IPR96D overcurrent and earth fault protection relays for MV feeders

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

АЛ-1 AC overcurrent relay, settings 0.05-100 A in five ranges. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What setting ranges does the АЛ-1 offer?

Five ranges: 0.05-0.40, 0.125-1.0, 0.5-4.0, 2.5-20 and 12.5-100 A.

How fast does it operate?

Not more than 0.05 s at 1.2 times the setting and not more than 0.03 s at 3 times.

What contacts does the output have?

One make and one break contact.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides