PE41, PE41-M fast intermediate relay, 24-230 V DC and 24-400 V AC
Electromagnetic intermediate relays ПЕ41 and ПЕ41-М switch DC loads at 24-230 V and AC loads at 24-400 V, 50 and 60 Hz. Operate time is up to 0.011 s and the relay carries up to 6 contact groups.
- Rated circuit voltage, DC
- 24-230 V
- Rated circuit voltage, AC
- 24-400 V, 50 and 60 Hz
- Operate time
- up to 0.011 s
- Contact groups
- up to 6
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ПЕ41 range is made for protection, control and automation circuits of power-engineering equipment, where it switches electrical loads. It handles DC circuits rated from 24 to 230 V and AC circuits rated from 24 to 400 V at 50 and 60 Hz. Operate time is up to 0.011 s, which places it among the fast-acting intermediate relays.
The relay is electromagnetic and has up to 6 contact groups. Two versions exist: the basic ПЕ41 and the ПЕ41-М, which has a module in a transparent case. Add-on modules cover shunting, an RC circuit, indication and surge protection. Coil consumption is not more than 6 W on DC and not more than 10 VA on AC.
Minimum contact current is 0.02 A at 24 V and 0.01 A at 110 V and above. Insulation withstands 2500 V between independent circuits and between circuits and case. Insulation resistance is 20 MOhm cold and 6 MOhm when heated. Mechanical life is not less than 500000 operating cycles and switching life is not less than 100000 cycles.
Climatic versions are У3 and Т3, with an operating temperature from minus 40 to plus 55 °C. The relay tolerates vibration up to 15 Hz at 3g and from 15 to 100 Hz at 1g. Protection to ГОСТ 14254-96 is IP40 for the relay body and IP10 for the screw terminals.
The design follows ГОСТ 14254-96 and НП 306.2.141-2008, and the relay is used at nuclear power plants (classes 3Н and 4Н). It is fixed with a screw or on a DIN rail, the DIN-rail fixing needing an extra module. Wires go to screw terminals, connected from the front or the rear.
Technical specifications
| Rated circuit voltage, DC | 24-230 V |
|---|---|
| Rated circuit voltage, AC | 24-400 V, 50 and 60 Hz |
| Operate time | up to 0.011 s |
| Contact groups | up to 6 |
| Minimum contact current | 0.02 A at 24 V; 0.01 A at 110 V and above |
| Coil power, DC | not more than 6 W |
| Coil power, AC | not more than 10 VA |
| Insulation test voltage | 2500 V |
| Insulation resistance, cold | 20 MOhm |
| Insulation resistance, heated | 6 MOhm |
| Mechanical life | not less than 500000 cycles |
| Switching life | not less than 100000 cycles |
| Protection degree | IP40 (relay), IP10 (terminals) |
| Operating temperature | from minus 40 to plus 55 °C |
| Climatic versions | У3, Т3 |
| Vibration | up to 15 Hz at 3g; 15-100 Hz at 1g |
How it compares with similar models
| Parameter | PE41, PE41-M fast intermediate relay, 24-230 V DC and 24-400 V AC | PE40, PE40-M instantaneous intermediate relay, 24-230 V DC and 24-400 V AC | ПЕ46, ПЕ46-1 two-position electromagnetic intermediate relay for 24-230 V DC and 24-400 V AC | ПЕ43, ПЕ43-М fast-acting DC electromagnetic intermediate relay, operate time up to 0,011 s |
|---|---|---|---|---|
| Operate time | up to 0.011 s | up to 0.03 s | — | up to 0,011 s |
| Minimum contact current | 0.02 A at 24 V; 0.01 A at 110 V and above | 0.02 A at 24 V; 0.01 A at 110 V and above | 0,02 A at 24 V; 0,01 A at 110 V and above | 0,02 A at 24 V; 0,01 A at 110 V and above |
| Insulation test voltage | 2500 V | — | 2500 V between independent circuits and case; 1000 V between open contacts; 550 V between coils | 2500 V between independent circuits and case and between independent circuits |
| Protection degree | IP40 (relay), IP10 (terminals) | IP40 (relay), IP30 (ПЕ40-10 with soldering lugs), IP10 (screw terminals), IP00 (soldering lugs) | IP40 (relay), IP10 (screw terminals) | IP40 (relay), IP10 (screw terminals) |
| Vibration | up to 15 Hz at 3g; 15-100 Hz at 1g | up to 15 Hz at 3g; 15-100 Hz at 1g | up to 15 Hz at 3g, 15 to 100 Hz at 1g | up to 15 Hz at 3g, 15 to 100 Hz at 1g |
European equivalents
Auxiliary, bistable and contactor relays for substations
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
PE41, PE41-M fast intermediate relay, 24-230 V DC and 24-400 V AC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the operate time of the ПЕ41 relay?
Operate time is up to 0.011 s, so the relay is classed as fast-acting.
Which circuit voltages can it switch?
DC circuits from 24 to 230 V and AC circuits from 24 to 400 V at 50 and 60 Hz.
How many operating cycles do the contacts last?
Mechanical life is not less than 500000 cycles and switching life is not less than 100000 cycles.
Similar equipment from other manufacturers