WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A
WS50x80S, WS80x80S, WS80x120S and WS80x160S are highly sensitive split-core transformers that turn residual currents of 10 mA…100 A into RCM signals. They can be retrofitted where the installation must stay energised.
- Type
- Split-core measuring current transformer
- Internal dimensions
- 50 x 80 mm; 80 x 80 mm; 80 x 120 mm; 80 x 160 mm
- Residual current range
- 10 mA…100 A
- Rated transformation ratio
- 600/1
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Residual currents from 10 mA to 100 A are converted by these split-core transformers into signals that RCM devices can evaluate. They are added to existing installations that must not be disconnected. Two wires link the transformer to the evaluator, and the distance may be up to 40 m, depending on the lead used.
They serve residual current monitors (RCM) and residual current monitoring systems (RCMS). All live conductors must be routed through the transformer and must not be shielded. A PE conductor is never routed through it.
Four types differ by internal opening: WS50x80S (50 x 80 mm, 900 g), WS80x80S (80 x 80 mm, 1050 g), WS80x120S (80 x 120 mm, 1250 g) and WS80x160S (80 x 160 mm, 2550 g). Rated transformation ratio is 600/1, rated burden 180 Ω, rated primary current ≤ 10 A (100 A) / ≥ 10 mA, rated frequency 50…400 Hz, internal resistance 5…8 Ω and accuracy class 5.
Highest system voltage Um is AC 720 V and rated impulse withstand voltage Uisol 3 kV. Rated continuous thermal current is 100 A, short-time 14 kA/1 s and dynamic 35 kA/30 ms. The operating temperature is -10…+50 °C, storage -40…+70 °C, climatic class 3K22 to IEC 60721-3-3.
Shock resistance is 15 g/11 ms and vibration resistance in operation 1 g/10…150 Hz. Protection is IP40 for internal components and IP20 for terminals, with flammability class UL94 V-0. Fixing is by screws. The transformers comply with IEC 60044-1.
Technical specifications
| Type | Split-core measuring current transformer |
|---|---|
| Internal dimensions | 50 x 80 mm; 80 x 80 mm; 80 x 120 mm; 80 x 160 mm |
| Residual current range | 10 mA…100 A |
| Rated transformation ratio | 600/1 |
| Rated burden | 180 Ω |
| Rated primary current | ≤ 10 A (100 A) / ≥ 10 mA |
| Nominal power | 50 mVA |
| Rated frequency | 50…400 Hz |
| Internal resistance | 5…8 Ω |
| Accuracy class | 5 |
| Highest system voltage Um | AC 720 V |
| Rated impulse withstand voltage Uisol | 3 kV |
| Rated continuous thermal current | 100 A |
| Rated short-time thermal current | 14 kA/1 s |
| Rated dynamic current | 35 kA/30 ms |
| Ambient temperature (operation) | -10…+50 °C |
| Degree of protection | IP40 (internal components), IP20 (terminals) |
| Weight | 900 g (WS50x80S), 1050 g (WS80x80S), 1250 g (WS80x120S), 2550 g (WS80x160S) |
Part numbers
Show all part numbers (4)
B911741 (WS50x80S), B911742 (WS80x80S), B911743 (WS80x120S), B911755 (WS80x160S)
How it compares with similar models
| Parameter | WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A | WR70x175S(P)…WR200x500S(P) rectangular measuring current transformers | W0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 A | LINETRAXX® CTAS50, CTAS80, CTAS120 and CTAS…/01 divisible measuring current transformers |
|---|---|---|---|---|
| Type | Split-core measuring current transformer | Rectangular measuring current transformer | Measuring current transformer | Divisible measuring current transformer |
| Rated burden | 180 Ω | 180 Ω | 180 Ω (18 Ω at 100 A) | — |
| Rated frequency | 50…400 Hz | 50…400 Hz | 15…400 Hz | — |
| Accuracy class | 5 | 5 | 3 | — |
| Rated short-time thermal current | 14 kA/1 s | 14 kA/1 s | 14 kA 1 s | — |
Request a price and lead time
WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How far may the transformer be from the evaluator?
Up to 40 m, depending on the lead used. Two wires make the connection.
Which conductors go through the transformer?
All live conductors, unshielded. A PE conductor is never routed through it.
What internal openings does the series offer?
50 x 80 mm, 80 x 80 mm, 80 x 120 mm and 80 x 160 mm for the WS50x80S, WS80x80S, WS80x120S and WS80x160S.