International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A

WS50x80S, WS80x80S, WS80x120S and WS80x160S are highly sensitive split-core transformers that turn residual currents of 10 mA…100 A into RCM signals. They can be retrofitted where the installation must stay energised.

Type
Split-core measuring current transformer
Internal dimensions
50 x 80 mm; 80 x 80 mm; 80 x 120 mm; 80 x 160 mm
Residual current range
10 mA…100 A
Rated transformation ratio
600/1

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Residual currents from 10 mA to 100 A are converted by these split-core transformers into signals that RCM devices can evaluate. They are added to existing installations that must not be disconnected. Two wires link the transformer to the evaluator, and the distance may be up to 40 m, depending on the lead used.

They serve residual current monitors (RCM) and residual current monitoring systems (RCMS). All live conductors must be routed through the transformer and must not be shielded. A PE conductor is never routed through it.

Four types differ by internal opening: WS50x80S (50 x 80 mm, 900 g), WS80x80S (80 x 80 mm, 1050 g), WS80x120S (80 x 120 mm, 1250 g) and WS80x160S (80 x 160 mm, 2550 g). Rated transformation ratio is 600/1, rated burden 180 Ω, rated primary current ≤ 10 A (100 A) / ≥ 10 mA, rated frequency 50…400 Hz, internal resistance 5…8 Ω and accuracy class 5.

Highest system voltage Um is AC 720 V and rated impulse withstand voltage Uisol 3 kV. Rated continuous thermal current is 100 A, short-time 14 kA/1 s and dynamic 35 kA/30 ms. The operating temperature is -10…+50 °C, storage -40…+70 °C, climatic class 3K22 to IEC 60721-3-3.

Shock resistance is 15 g/11 ms and vibration resistance in operation 1 g/10…150 Hz. Protection is IP40 for internal components and IP20 for terminals, with flammability class UL94 V-0. Fixing is by screws. The transformers comply with IEC 60044-1.

Technical specifications

TypeSplit-core measuring current transformer
Internal dimensions50 x 80 mm; 80 x 80 mm; 80 x 120 mm; 80 x 160 mm
Residual current range10 mA…100 A
Rated transformation ratio600/1
Rated burden180 Ω
Rated primary current≤ 10 A (100 A) / ≥ 10 mA
Nominal power50 mVA
Rated frequency50…400 Hz
Internal resistance5…8 Ω
Accuracy class5
Highest system voltage UmAC 720 V
Rated impulse withstand voltage Uisol3 kV
Rated continuous thermal current100 A
Rated short-time thermal current14 kA/1 s
Rated dynamic current35 kA/30 ms
Ambient temperature (operation)-10…+50 °C
Degree of protectionIP40 (internal components), IP20 (terminals)
Weight900 g (WS50x80S), 1050 g (WS80x80S), 1250 g (WS80x120S), 2550 g (WS80x160S)

Part numbers

Show all part numbers (4)

B911741 (WS50x80S), B911742 (WS80x80S), B911743 (WS80x120S), B911755 (WS80x160S)

How it compares with similar models

ParameterWS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 AWR70x175S(P)…WR200x500S(P) rectangular measuring current transformersW0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 ALINETRAXX® CTAS50, CTAS80, CTAS120 and CTAS…/01 divisible measuring current transformers
TypeSplit-core measuring current transformerRectangular measuring current transformerMeasuring current transformerDivisible measuring current transformer
Rated burden180 Ω180 Ω180 Ω (18 Ω at 100 A)—
Rated frequency50…400 Hz50…400 Hz15…400 Hz—
Accuracy class553—
Rated short-time thermal current14 kA/1 s14 kA/1 s14 kA 1 s—

Request a price and lead time

WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How far may the transformer be from the evaluator?

Up to 40 m, depending on the lead used. Two wires make the connection.

Which conductors go through the transformer?

All live conductors, unshielded. A PE conductor is never routed through it.

What internal openings does the series offer?

50 x 80 mm, 80 x 80 mm, 80 x 120 mm and 80 x 160 mm for the WS50x80S, WS80x80S, WS80x120S and WS80x160S.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides