LINETRAXX® CTAS50, CTAS80, CTAS120 and CTAS…/01 divisible measuring current transformers
CTAS transformers open with a locking button and close around the conductors of an installation that stays in service. They work with RCM, RCMS and EDS devices, with internal diameters of 50, 80 or 120 mm.
- Type
- Divisible measuring current transformer
- Versions
- CTAS50, CTAS80, CTAS120; CTAS50/01, CTAS80/01, CTAS120/01 (for EDS441)
- Internal diameter
- 50 mm (CTAS50), 80 mm (CTAS80), 120 mm (CTAS120)
- Rated current In
- 85 A (CTAS50), 160 A (CTAS80), 250 A (CTAS120)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A locking button opens the divisible CTAS transformer so that it can be placed around the conductors to be monitored, which makes retrofitting in existing systems easy. With RCM monitors and RCMS systems the highly sensitive transformers turn AC currents into an evaluable signal. In IT systems they also measure the locating current from a PGH injector or an ISOMETER® iso685.
Three internal diameters are made: CTAS50 (50 mm, rated current In 85 A), CTAS80 (80 mm, 160 A) and CTAS120 (120 mm, 250 A). The CTAS…/01 types are for EDS441 locators, while the others work with RCMS, RCM420 and EDS440 in AC and DC systems. A two-wire cable makes the connection.
Rated transformation ratio Kr is 600 / 1, and 8000 / 1 for the /01 types. The frequency range is 42 Hz…3 kHz, rated continuous thermal current Icth 125 A, short-time Ith 2.4 kA / 1 s and dynamic Idyn 50 kA / 50 ms. Rated voltage is 500 V for CTAS50(/01) and 630 V for CTAS80(/01) and CTAS120(/01), 720 V to IEC 61869-1, with overvoltage category III, rated impulse voltage 8 kV and pollution degree 3.
Operating temperature is -25…+70 °C. Protection is IP40 for internal components and IP20 for terminals, flammability class UL94 V-0. Screw-type terminals take 0.34…2.5 mm² (AWG 22…12), with a stripping length of 8…9 mm and a tightening torque of 0.5 Nm. The core may be opened max. 10 times.
The devices are intended for control cabinets or similarly protected environments. Fix them by screws or on a DIN rail, with a mounting clip recommended for CTAS50 and CTAS80. A clip (B98110015) and a mounting bracket (B98110016) are listed as accessories. The series meets IEC 61869-1 and IEC 60664-1.
Technical specifications
| Type | Divisible measuring current transformer |
|---|---|
| Versions | CTAS50, CTAS80, CTAS120; CTAS50/01, CTAS80/01, CTAS120/01 (for EDS441) |
| Internal diameter | 50 mm (CTAS50), 80 mm (CTAS80), 120 mm (CTAS120) |
| Rated current In | 85 A (CTAS50), 160 A (CTAS80), 250 A (CTAS120) |
| Rated transformation ratio Kr | CTAS… 600 / 1, CTAS…/01 8000 / 1 |
| Rated voltage | 500 V (CTAS50(/01)), 630 V (CTAS80(/01), CTAS120(/01)) |
| Rated voltage (IEC 61869-1) | 720 V |
| Rated impulse voltage / pollution degree | 8 kV / 3 |
| Frequency range | 42 Hz…3 kHz |
| Rated continuous thermal current Icth | 125 A |
| Rated short-time thermal current Ith | 2.4 kA / 1 s |
| Rated dynamic current Idyn | 50 kA / 50 ms |
| Operating temperature | -25…+70 °C |
| Degree of protection | IP40 (internal components), IP20 (terminals) |
| Flammability class | UL94 V-0 |
| Terminals | Screw-type, 0.34…2.5 mm² (AWG 22…12) |
| Opening cycles | max. 10 |
Part numbers
Show all part numbers (8)
B98110009, B98110012, B98110010, B98110013, B98110011, B98110014, accessories B98110015, B98110016
How it compares with similar models
| Parameter | LINETRAXX® CTAS50, CTAS80, CTAS120 and CTAS…/01 divisible measuring current transformers | LINETRAXX® CTAC20, CTAC35, CTAC60, CTAC120 and CTAC210 measuring current transformers | WS… and WS…-8000 split-core measuring current transformers for residual current monitoring | WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A |
|---|---|---|---|---|
| Type | Divisible measuring current transformer | Measuring current transformer | Split-core measuring current transformer | Split-core measuring current transformer |
| Rated impulse voltage / pollution degree | 8 kV / 3 | 8 kV/3 | 8 kV/3 | — |
| Frequency range | 42 Hz…3 kHz | 15 Hz…100 kHz | 42 Hz…3 kHz | — |
| Operating temperature | -25…+70 °C | -25…+70 °C (standard); -40…+70 °C (B781100xxMIL) | -25…+70 °C | — |
Request a price and lead time
LINETRAXX® CTAS50, CTAS80, CTAS120 and CTAS…/01 divisible measuring current transformers. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What separates CTAS… from CTAS…/01?
The transformation ratio Kr: 600 / 1 for CTAS… and 8000 / 1 for CTAS…/01. The /01 types are meant for EDS441 locators.
Which diameters and rated currents are available?
CTAS50: 50 mm, 85 A. CTAS80: 80 mm, 160 A. CTAS120: 120 mm, 250 A.
How many times can the transformer be opened?
At most 10 times (max. 10 opening cycles).