W0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 A

The W0-S20…W5-S210 and W10/600 transformers are highly sensitive devices that turn residual currents up to 100 A into RCM or EDS signals. Inside diameters run from 10 to 210 mm and the evaluator may be up to 40 m away.

Type
Measuring current transformer
Inside diameter
10, 20, 35, 70, 105, 140, 210 mm
Residual currents
up to 100 A
Rated transformation ratio
600/1

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Seven sizes of toroidal transformer cover residual currents up to 100 A and pass them as evaluable signals to RCM or EDS devices. Two wires join the transformer to the evaluator, and depending on the lead used the distance may reach 40 m.

The transformers serve residual current monitors (RCM), residual current monitoring systems (RCMS) and EDS insulation fault locators in AC and DC systems. Every current-carrying conductor must pass through the opening without shielding. A PE conductor must never pass through it.

The types are defined by inside diameter: W10/600 (10 mm), W0-S20 (20 mm), W1-S35 (35 mm), W2-S70 (70 mm), W3-S105 (105 mm), W4-S140 (140 mm) and W5-S210 (210 mm). Rated transformation ratio is 600/1, rated burden 180 Ω (18 Ω at 100 A), nominal power 50 mVA, rated frequency 15…400 Hz, internal resistance 5…8 Ω and accuracy class 3.

Rated continuous thermal current is 100 A, short-time 14 kA 1 s and dynamic 35 kA 30 ms. Highest system voltage Um is AC 720 V and rated impulse withstand voltage Uisol 3 kV. A P6KE6V8CP suppressor diode protects the secondary circuit. Ambient temperature is -10…+ 50 °C in operation and -40…+ 70 °C in storage, climatic class 3K22 to IEC 60721-3-3.

Terminals are screw-type, protection is IP40 for internal components and IP20 for terminals, and flammability class is UL94 V-0. Fix the transformer in any position with M5 screws. The series complies with IEC 61869-1.

Technical specifications

TypeMeasuring current transformer
Inside diameter10, 20, 35, 70, 105, 140, 210 mm
Residual currentsup to 100 A
Rated transformation ratio600/1
Rated burden180 Ω (18 Ω at 100 A)
Nominal power50 mVA
Rated frequency15…400 Hz
Internal resistance5…8 Ω
Accuracy class3
Rated continuous thermal current100 A
Rated short-time thermal current14 kA 1 s
Rated dynamic current35 kA 30 ms
Highest system voltage UmAC 720 V
Rated impulse withstand voltage Uisol3 kV
Ambient temperature (operation / storage)-10…+ 50 °C / -40…+ 70 °C
Degree of protectionIP40 (internal components), IP20 (terminals)
MountingAny position, M5 screws
Cable length to evaluator0…1 m single wire, 0…10 m twisted, 0…40 m shielded

Part numbers

Show all part numbers (7)

B911761 (W10/600), B911787 (W0-S20), B911731 (W1-S35), B911732 (W2-S70), B911733 (W3-S105), B911734 (W4-S140), B911735 (W5-S210)

How it compares with similar models

ParameterW0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 AWS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 AWR70x175S(P)…WR200x500S(P) rectangular measuring current transformersLINETRAXX® CTAC20, CTAC35, CTAC60, CTAC120 and CTAC210 measuring current transformers
TypeMeasuring current transformerSplit-core measuring current transformerRectangular measuring current transformerMeasuring current transformer
Rated burden180 Ω (18 Ω at 100 A)180 Ω180 Ω—
Rated frequency15…400 Hz50…400 Hz50…400 Hz—
Accuracy class355—
Rated short-time thermal current14 kA 1 s14 kA/1 s14 kA/1 s—

Request a price and lead time

W0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which inside diameters does the series offer?

10 mm (W10/600), 20 mm (W0-S20), 35 mm (W1-S35), 70 mm (W2-S70), 105 mm (W3-S105), 140 mm (W4-S140) and 210 mm (W5-S210).

How far can the evaluator be from the transformer?

Up to 40 m depending on the lead: 0…1 m single wire, 0…10 m twisted, 0…40 m shielded.

Which conductors pass through the transformer?

All current-carrying conductors, unshielded. A PE conductor must never pass through it.