W0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 A
The W0-S20…W5-S210 and W10/600 transformers are highly sensitive devices that turn residual currents up to 100 A into RCM or EDS signals. Inside diameters run from 10 to 210 mm and the evaluator may be up to 40 m away.
- Type
- Measuring current transformer
- Inside diameter
- 10, 20, 35, 70, 105, 140, 210 mm
- Residual currents
- up to 100 A
- Rated transformation ratio
- 600/1
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Seven sizes of toroidal transformer cover residual currents up to 100 A and pass them as evaluable signals to RCM or EDS devices. Two wires join the transformer to the evaluator, and depending on the lead used the distance may reach 40 m.
The transformers serve residual current monitors (RCM), residual current monitoring systems (RCMS) and EDS insulation fault locators in AC and DC systems. Every current-carrying conductor must pass through the opening without shielding. A PE conductor must never pass through it.
The types are defined by inside diameter: W10/600 (10 mm), W0-S20 (20 mm), W1-S35 (35 mm), W2-S70 (70 mm), W3-S105 (105 mm), W4-S140 (140 mm) and W5-S210 (210 mm). Rated transformation ratio is 600/1, rated burden 180 Ω (18 Ω at 100 A), nominal power 50 mVA, rated frequency 15…400 Hz, internal resistance 5…8 Ω and accuracy class 3.
Rated continuous thermal current is 100 A, short-time 14 kA 1 s and dynamic 35 kA 30 ms. Highest system voltage Um is AC 720 V and rated impulse withstand voltage Uisol 3 kV. A P6KE6V8CP suppressor diode protects the secondary circuit. Ambient temperature is -10…+ 50 °C in operation and -40…+ 70 °C in storage, climatic class 3K22 to IEC 60721-3-3.
Terminals are screw-type, protection is IP40 for internal components and IP20 for terminals, and flammability class is UL94 V-0. Fix the transformer in any position with M5 screws. The series complies with IEC 61869-1.
Technical specifications
| Type | Measuring current transformer |
|---|---|
| Inside diameter | 10, 20, 35, 70, 105, 140, 210 mm |
| Residual currents | up to 100 A |
| Rated transformation ratio | 600/1 |
| Rated burden | 180 Ω (18 Ω at 100 A) |
| Nominal power | 50 mVA |
| Rated frequency | 15…400 Hz |
| Internal resistance | 5…8 Ω |
| Accuracy class | 3 |
| Rated continuous thermal current | 100 A |
| Rated short-time thermal current | 14 kA 1 s |
| Rated dynamic current | 35 kA 30 ms |
| Highest system voltage Um | AC 720 V |
| Rated impulse withstand voltage Uisol | 3 kV |
| Ambient temperature (operation / storage) | -10…+ 50 °C / -40…+ 70 °C |
| Degree of protection | IP40 (internal components), IP20 (terminals) |
| Mounting | Any position, M5 screws |
| Cable length to evaluator | 0…1 m single wire, 0…10 m twisted, 0…40 m shielded |
Part numbers
Show all part numbers (7)
B911761 (W10/600), B911787 (W0-S20), B911731 (W1-S35), B911732 (W2-S70), B911733 (W3-S105), B911734 (W4-S140), B911735 (W5-S210)
How it compares with similar models
| Parameter | W0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 A | WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A | WR70x175S(P)…WR200x500S(P) rectangular measuring current transformers | LINETRAXX® CTAC20, CTAC35, CTAC60, CTAC120 and CTAC210 measuring current transformers |
|---|---|---|---|---|
| Type | Measuring current transformer | Split-core measuring current transformer | Rectangular measuring current transformer | Measuring current transformer |
| Rated burden | 180 Ω (18 Ω at 100 A) | 180 Ω | 180 Ω | — |
| Rated frequency | 15…400 Hz | 50…400 Hz | 50…400 Hz | — |
| Accuracy class | 3 | 5 | 5 | — |
| Rated short-time thermal current | 14 kA 1 s | 14 kA/1 s | 14 kA/1 s | — |
Request a price and lead time
W0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which inside diameters does the series offer?
10 mm (W10/600), 20 mm (W0-S20), 35 mm (W1-S35), 70 mm (W2-S70), 105 mm (W3-S105), 140 mm (W4-S140) and 210 mm (W5-S210).
How far can the evaluator be from the transformer?
Up to 40 m depending on the lead: 0…1 m single wire, 0…10 m twisted, 0…40 m shielded.
Which conductors pass through the transformer?
All current-carrying conductors, unshielded. A PE conductor must never pass through it.