CTBC17 AC/DC sensitive measuring current transformers, 17 mm aperture
The CTBC17 series measures differential current in supply networks up to 600 V and 80 A where converters can cause DC fault currents. The internal diameter is 17 mm, and versions for PCB mounting and with a cable are listed.
- Type
- AC/DC sensitive measuring current transformer
- Rated voltage
- 230/400 V (серія / series: 600 V)
- Rated current
- 32 A (80 A)
- Internal diameter
- 17 mm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
CTBC17 transformers measure differential current with sensitivity to AC and DC. They are meant for supply networks up to a rated voltage of 600 V and a rated current of 80 A, where converters in the installation can produce DC fault currents.
They can be used in earthed and unearthed DC, AC and 3(N)AC systems. An integrated magnetic shield keeps external magnetic fields from affecting the measurement. The internal diameter is 17 mm.
For mounting there are upright PCB versions (CTBC17P-03, CTBC17P-04, CTBC17P-13, CTBC17P-14) and cable versions: CTBC17P-03-K0325, plus a cable of 325 mm or 600 mm with a tolerance of ±25 mm. The PCB versions work with the RCMB104 and RDC104 evaluation modules.
The primary conductor must be a cable that at least meets the requirements for basic insulation in the application. Further details of intended use are in the manuals of the evaluators.
Electrical data: rated current 32 A (80 A for the series), rated voltage 230/400 V (600 V for the series), rated primary residual current 1000 mA and rated DC residual operating current 6 mA. Continuous thermal current is 35 A, short-time thermal current 2400 A and dynamic current 6000 A. Rated impulse voltage is 6 kV and rated insulation voltage 300 V.
Conditions: overvoltage category III, pollution degree 2, altitude up to 4000 m AMSL. Housing is IP40, connection IP30, flammability class UL94V-0, weight under 60 g.
Technical specifications
| Type | AC/DC sensitive measuring current transformer |
|---|---|
| Rated voltage | 230/400 V (серія / series: 600 V) |
| Rated current | 32 A (80 A) |
| Internal diameter | 17 mm |
| Rated continuous thermal current | 35 A |
| Rated short-time thermal current | 2400 A |
| Rated dynamic current | 6000 A |
| Rated impulse voltage | 6 kV |
| Rated insulation voltage | 300 V |
| Operating temperature | -35…+85 °C |
| Operating altitude | up to 4000 m AMSL |
| Degree of protection / connection | IP40 / IP30 |
| Flammability class | UL94V-0 |
| Weight | < 60 g |
| Versions | CTBC17P-03, CTBC17P-03-K0325, CTBC17P-04, CTBC17P-13, CTBC17P-14 |
Part numbers
Show all part numbers (9)
B98080070, B98080071, B98080074, B98080077, B98080076, B98080540, B98080541, B98080542, B98080543
Request a price and lead time
CTBC17 AC/DC sensitive measuring current transformers, 17 mm aperture. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What voltage and current can the CTBC17 handle?
The series is rated for 600 V and 80 A; the 230/400 V rating is listed with 32 A.
Which versions are available?
PCB versions CTBC17P-03, -04, -13 and -14, and cable versions with 325 mm or 600 mm leads.
What are the temperature range and protection class?
Operating temperature is -35 to +85 °C, with IP40 for the housing and IP30 at the connection.