WR70x175S(P)…WR200x500S(P) rectangular measuring current transformers
WR…S and WR…SP rectangular transformers turn AC currents into evaluable signals for RCM and RCMS monitors and EDS insulation fault locators. The SP types carry integrated screening for busbar systems.
- Type
- Rectangular measuring current transformer
- Without screening (S)
- WR70x175S, WR115x305S, WR150x350S, WR200x500S
- With screening (SP)
- WR70x175SP, WR115x305SP, WR150x350SP, WR200x500SP
- Rated transformation ratio
- 600/1
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Highly sensitive rectangular transformers of the WR…S series work with RCM and RCMS residual current monitors and evaluators. Combined with EDS insulation fault location systems in IT systems, they measure the locating current from a PGH injector or an ISOMETER® IRDH. A two-wire cable runs to the connected device.
Compatible devices are RCMS460/490 and RCMS470 systems, RCM420, RCM460 and RCM470 monitors, and EDS440, EDS460/490 and EDS470 locators in AC and DC systems. The WR…SP types have integrated screening, which prevents false tripping of connected RCM… or EDS… devices when high load or inrush currents occur. They suit busbar systems and are intended for load currents ≥ 500 A.
Four opening sizes are made: WR70x175, WR115x305, WR150x350 and WR200x500, each without screening (S) or with it (SP). The rated transformation ratio is 600/1, rated burden 180 Ω, nominal power 50 mVA, rated frequency 50…400 Hz, internal resistance 5…8 Ω and accuracy class 5.
Rated continuous thermal current is 100 A, short-time 14 kA/1 s and surge 50 kA/50 ms. Highest system voltage Um is AC 720 V and rated impulse withstand voltage Uisol 3 kV. A P6KE6V8CP suppressor diode protects the secondary side. Ambient temperature in operation is - 10 °C…+ 50 °C, climatic class 3K22 to IEC 60721-3-3.
Terminals are screw-type, protection is IP40 for internal components and IP20 for terminals, and flammability class is UL94 V-0. Any mounting position is allowed. The transformers comply with DIN EN 60044-1. Only qualified electricians should install them.
Technical specifications
| Type | Rectangular measuring current transformer |
|---|---|
| Without screening (S) | WR70x175S, WR115x305S, WR150x350S, WR200x500S |
| With screening (SP) | WR70x175SP, WR115x305SP, WR150x350SP, WR200x500SP |
| Rated transformation ratio | 600/1 |
| Rated burden | 180 Ω |
| Rated primary current | ≤ 10 A (100 A) / ≥ 10 mA |
| Nominal power | 50 mVA |
| Rated frequency | 50…400 Hz |
| Internal resistance | 5…8 Ω |
| Accuracy class | 5 |
| Rated continuous thermal current | 100 A |
| Rated short-time thermal current | 14 kA/1 s |
| Rated surge current | 50 kA/50 ms |
| Highest system voltage Um | AC 720 V |
| Rated impulse withstand voltage Uisol | 3 kV |
| Ambient temperature (operation) | - 10 °C…+ 50 °C |
| Degree of protection | IP40 (internal components), IP20 (terminals) |
| Flammability class | UL94 V-0 |
Part numbers
Show all part numbers (8)
B911738, B911739, B911740, B911763, B911790, B911791, B911792, B911793
How it compares with similar models
| Parameter | WR70x175S(P)…WR200x500S(P) rectangular measuring current transformers | WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A | W0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 A | LINETRAXX® CTAC20, CTAC35, CTAC60, CTAC120 and CTAC210 measuring current transformers |
|---|---|---|---|---|
| Type | Rectangular measuring current transformer | Split-core measuring current transformer | Measuring current transformer | Measuring current transformer |
| Rated burden | 180 Ω | 180 Ω | 180 Ω (18 Ω at 100 A) | — |
| Rated frequency | 50…400 Hz | 50…400 Hz | 15…400 Hz | — |
| Accuracy class | 5 | 5 | 3 | — |
| Rated short-time thermal current | 14 kA/1 s | 14 kA/1 s | 14 kA 1 s | — |
Request a price and lead time
WR70x175S(P)…WR200x500S(P) rectangular measuring current transformers. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the difference between S and SP types?
SP types have integrated screening, which prevents false tripping of RCM… or EDS… devices at high load and inrush currents. They are used in busbar systems for load currents ≥ 500 A.
Which devices do the WR…S(P) transformers work with?
RCMS460/490, RCMS470, RCM420, RCM460, RCM470, and EDS440, EDS460/490 and EDS470. A two-wire cable makes the connection.
Which opening sizes are available?
70 x 175 mm, 115 x 305 mm, 150 x 350 mm and 200 x 500 mm, each as an S and an SP type.