LINETRAXX® WF… flexible measuring current transformers with RCC420 signal converter

Each WF… set pairs a flexible measuring current transformer with an RCC420 signal converter. It works with RCMS460/490 and RCM420-D9 residual current monitors, measures 100 mA…20 A and comes in lengths from 170 to 1800 mm.

Measuring range
100 mA…20 A
Rated frequency
42…2000 Hz
Loop length
170, 250, 500, 800, 1200, 1800 mm
Supply voltage (-1)
DC 9.6…94 V / AC 16…72 V, 42…460 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

A WF… set measures AC currents for RCMS460/490 and RCM420-D9 residual current monitors. It consists of one flexible WF… transformer and one RCC420 signal converter, joined to the monitor by a two-wire cable. The measuring range is 100 mA…20 A at a rated frequency of 42…2000 Hz.

Typical duties are residual, fault and nominal current monitoring of loads and systems that cannot be switched off. The series also serves for EMC monitoring of TN-S systems for stray currents and additional N-PE connections at the central earthing point, and for checking that PE and equipotential bonding conductors carry no current.

The flexible loop is made in lengths of 170, 250, 500, 800, 1200 and 1800 mm. It goes round the conductors without disconnecting them, which suits retrofitting in existing installations. Pass the conductors centrally and at a right angle through the opening, and keep the transformer away from strong magnetic fields. The transformer connects to the converter through a PS/2 plug on a 2 m cable, and its connection is monitored.

Every length comes in two supply versions: -1 for DC 9.6…94 V / AC 16…72 V and -2 for DC 70…300 V / AC 70…300 V, both at 42…460 Hz. The RCC420 mounts on a DIN rail to IEC 60715 or on 2 x M4 screws with a mounting clip. The enclosure is polycarbonate rated UL94V-0 and the terminals are push-wire. Permitted cable between the monitor and the RCC420 is 0…1 m single wire, 0…10 m twisted or 0…40 m shielded. Only qualified electricians should install, connect and commission the set.

Technical specifications

Measuring range100 mA…20 A
Rated frequency42…2000 Hz
Loop length170, 250, 500, 800, 1200, 1800 mm
Supply voltage (-1)DC 9.6…94 V / AC 16…72 V, 42…460 Hz
Supply voltage (-2)DC 70…300 V / AC 70…300 V, 42…460 Hz
Rated transformation ratio (U - I)100 mV / A
Rated transformation ratio (k - l)1.67 mA / A
Rated burden (signal output k, l)68 Ω
Power consumption≤ 3 VA
Rated insulation voltage (CAT III)1000 Vrms or DC
Rated insulation voltage (RCC420)250 V
Operating temperature- 25 °C…+ 55 °C
Degree of protectionIP 30 (internal components), IP 20 (terminal)
RCC420 mountingDIN rail to IEC 60715, 2 x M4 screws with mounting clip
Transformer connectionPS/2 plug, WF… cable 2 m
Weight RCC420≤ 160 g
Weight WF170…WF1800≤ 160 g (WF170) … ≤ 430g (WF1800)

Part numbers

Show all part numbers (5)

B78080201…B78080210, B78080221, B78080222, B98060008, B990994

How it compares with similar models

ParameterLINETRAXX® WF… flexible measuring current transformers with RCC420 signal converterLINETRAXX® CTAC20, CTAC35, CTAC60, CTAC120 and CTAC210 measuring current transformersWR70x175S(P)…WR200x500S(P) rectangular measuring current transformersW0-S20…W5-S210 and W10/600 measuring current transformers for residual currents up to 100 A
Rated frequency42…2000 Hz—50…400 Hz15…400 Hz
Degree of protectionIP 30 (internal components), IP 20 (terminal)IP40 (internal components), IP20 (terminals)IP40 (internal components), IP20 (terminals)IP40 (internal components), IP20 (terminals)

Request a price and lead time

LINETRAXX® WF… flexible measuring current transformers with RCC420 signal converter. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which monitors work with the WF… series?

Residual current monitors of the RCMS460/490 series and the RCM420-D9. The RCC420 converts the signal and a two-wire cable links it to the monitor.

How long may the cable between the RCM(S) and the RCC420 be?

Single wire from 0.75 mm2 up to 1 m, twisted up to 10 m, shielded from 0.5 mm2 up to 40 m. The recommended cable is J-Y(ST)Y min. 2 x 0.8.

Must conductors be disconnected for installation?

No. The transformer is fitted without disconnecting the conductors, which makes retrofitting simple.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides