AL-4-1, AL-4-2 earth-fault current relays (АЛ-4-1, АЛ-4-2), 0.02-0.2 A
АЛ-4-1 and АЛ-4-2 (AL-4-1, AL-4-2) are single-circuit earth-fault current relays with settings from 0.02 to 0.2 A. The АЛ-4-1 has an adjustable delay, the АЛ-4-2 operates with no delay and takes an auxiliary supply.
- Rated supply voltage
- DC 110 V; 220 V, AC 110 V; 220 V
- Rated input current
- 0.16 A, 50 Hz
- Trip setting range
- 0.02 to 0.2 A
- Setting step
- 0.002 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
These relays monitor earth-fault current through one current circuit and are highly sensitive. They work with a zero-sequence current transformer in earth-fault protection schemes, and also in other protection, emergency and industrial automation schemes.
The АЛ-4-1 corresponds fully to the АЛ-4 but adds an adjustable operate delay of 0.1-10 s or 0.3-30 s. The АЛ-4-2 is an instantaneous relay with an auxiliary supply. Supply voltage is DC 110 V or 220 V, or AC 110 V or 220 V.
Rated input current is 0.16 A at 50 Hz and the trip setting runs from 0.02 to 0.2 A in 0.002 A steps. Operate time at 3 times the setting is not more than 0.04 s. Reset ratio is not less than 0.9 and accuracy class is 5.
Contacts switch 0.02 to 2 A at 24 to 250 V. DC power is up to 60 W at τ = 0.005 s and up to 30 W at τ = 0.02 s; AC power is up to 300 VA at cosφ = 0.5. Continuous contact current is not more than 4 A. Mechanical life is not less than 100000 cycles, switching life not less than 20000 cycles, and mean service life is 12 years.
Install the relay indoors at minus 40 to plus 55 °C and 80% relative humidity at 25 °C, in a non-explosive atmosphere free of dust and gases that attack insulation. Mounting-point vibration must not exceed 3g up to 15 Hz and 1g up to 100 Hz. The case is IP40, the terminals IP20, and the mass is not more than 0.8 kg. Fix it on a DIN rail or on a flat surface.
Technical specifications
| Rated supply voltage | DC 110 V; 220 V, AC 110 V; 220 V |
|---|---|
| Rated input current | 0.16 A, 50 Hz |
| Trip setting range | 0.02 to 0.2 A |
| Setting step | 0.002 A |
| Operate time at 3 times the setting | not more than 0.04 s |
| Adjustable delay, АЛ-4-1 | 0.1-10 s or 0.3-30 s |
| Reset ratio | not less than 0.9 |
| Accuracy class | 5 |
| Contact current | 0.02 to 2 A |
| Contact voltage | 24 to 250 V |
| Contact power, DC | up to 60 W at τ = 0.005 s; up to 30 W at τ = 0.02 s |
| Contact power, AC | up to 300 VA at cosφ = 0.5 |
| Continuous contact current | not more than 4 A |
| Mechanical life | not less than 100000 cycles |
| Switching life | not less than 20000 cycles |
| Mean service life | 12 years |
| Protection degree, case / terminals | IP40 / IP20 |
| Mass | not more than 0.8 kg |
Part numbers
Show all part numbers (2)
АЛ-4-1, АЛ-4-2
How it compares with similar models
| Parameter | AL-4-1, AL-4-2 earth-fault current relays (АЛ-4-1, АЛ-4-2), 0.02-0.2 A | AL-4 earth-fault current relay (АЛ-4), settings 0.005-0.150 A | АЛ-1 AC overcurrent relay, settings 0.05-100 A in five ranges | ВЛ-50 time relay for railway rolling stock, 2–200 s settings, 27–110 V DC supply |
|---|---|---|---|---|
| Rated supply voltage | DC 110 V; 220 V, AC 110 V; 220 V | DC 110 V; 220 V, AC 110 V; 220 V (by version) | =110, 220 V; ~100, 220 V | DC 27, 50, 75, 110 V |
| Setting step | 0.002 A | 0.0015 A | 0.005; 0.0125; 0.05; 0.25; 1.25 A | — |
| Reset ratio | not less than 0.9 | not less than 0.93 | not less than 0.9 | — |
| Accuracy class | 5 | 5 | 5 | 4/0.1 |
European equivalents
Earth Fault Locator selective detection of the feeder with an earth fault, Earth 4.0 / Earth Zero / Earth Zero Flag earth fault indicators with a sum current sensor
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
AL-4-1, AL-4-2 earth-fault current relays (АЛ-4-1, АЛ-4-2), 0.02-0.2 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the АЛ-4-1 and АЛ-4-2 differ?
The АЛ-4-1 has an adjustable delay of 0.1-10 s or 0.3-30 s; the АЛ-4-2 operates instantaneously and takes an auxiliary supply.
What is the current setting range?
From 0.02 to 0.2 A in steps of 0.002 A.
What sensor does the relay work with?
A zero-sequence current transformer in earth-fault protection schemes.