International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

РДЦ-01-055 and РДЦ-01-205 motor protection relays, 0.4 kV, 0.55 to 450 kW

The РДЦ-01-055 and РДЦ-01-205 protect three-phase asynchronous motors, 3x380 V, 50 Hz: 0.55 to 2.2 kW and 2.2 to 9.0 kW on direct connection. With current transformers the РДЦ-01-055 serves motors of 9.0 to 450 kW. Settings and indication are digital.

Type
Microprocessor motor protection relay
Motor voltage
3х380 V, 50 Hz
Motor power, direct connection
РДЦ-01-055: 0.55 to 2.2 kW; РДЦ-01-205: 2.2 to 9.0 kW
Motor power via current transformers
(9.0...450) kW (РДЦ-01-055)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Two relays make up this range, РДЦ-01-055 and РДЦ-01-205. Both protect three-phase asynchronous motors on 3x380 V, 50 Hz, submersible pumps included. The РДЦ-01-055 is rated for 0.55 to 2.2 kW on direct connection, the РДЦ-01-205 for 2.2 to 9.0 kW. Fed through current transformers, the РДЦ-01-055 covers motors of 9.0 to 450 kW.

The relay trips on overcurrent, rotor lock, short circuit (instantaneous overcurrent), load asymmetry, running under low load, supply overvoltage and undervoltage, reversed phase sequence at power-up, and low insulation resistance before the start. The output contact operates when a monitored value reaches its programmed level. Each of these functions can be switched off: maximum voltage, minimum voltage, idle or dry running, current asymmetry, instantaneous overcurrent, rotor lock, phase sequence and insulation resistance.

Settings and displayed values are digital. The relay can be set to watch the currents of phases A, B and C, or of phases A and C only. Besides protection it displays the current of each phase, the mains voltage of each phase, insulation resistance before the start, mains frequency and motor running hours. Rated input current is 1 to 5 A on the РДЦ-01-055 and 5 to 20 A on the РДЦ-01-205; the current measurement range is 0.2 to 50 A and 0.8 to 200 A respectively. Mains frequency is measured from 49.5 to 50.5 Hz with an error of ±0.1 Hz.

There is one normally open output contact with an AC-22 switching capacity of approx. 250 VA. Mechanical and switching endurance is at least 500000 cycles, readiness time is up to 2 s and power consumption is up to 9 VA. The case measures 140x70x137 mm and weighs up to 0.7 kg.

Two climatic versions exist: У category 3 to ГОСТ 15150-69 for temperate and cold climates, and Т category 3 for export to tropical regions. The relay is intended for closed unheated rooms. For motors above 9.0 kW, current transformers of 20-50, 40-100, 80-200, 160-400 or 240-600 A are selected.

Technical specifications

TypeMicroprocessor motor protection relay
Motor voltage3х380 V, 50 Hz
Motor power, direct connectionРДЦ-01-055: 0.55 to 2.2 kW; РДЦ-01-205: 2.2 to 9.0 kW
Motor power via current transformers(9.0...450) kW (РДЦ-01-055)
Rated input currentРДЦ-01-055: (1…5) A; РДЦ-01-205: (5…20) A
Current measurement rangeРДЦ-01-055: (0.2…50) A; РДЦ-01-205: (0.8…200) A
Mains frequency measurement range49.5 to 50.5 Hz, error ±0.1 Hz
Insulation resistance measurement range(0.3…3.0) MOhm
Voltage measurement error± 2.5 %
Output contacts1 normally open
Switching capacity AC-22approx. 250 VA
Power consumptionmax. 9 VA
Mechanical and switching enduranceat least 500000 cycles
Readiness timemax. 2 s
Dimensions140х70х137 mm
Weightmax. 0.7 kg
Climatic versionУ category 3, Т category 3 (ГОСТ 15150-69)

Part numbers

Show all part numbers (2)

РДЦ-01-055, РДЦ-01-205

How it compares with similar models

European equivalents

Series 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

РДЦ-01-055 and РДЦ-01-205 motor protection relays, 0.4 kV, 0.55 to 450 kW. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which motors do the РДЦ-01-055 and РДЦ-01-205 protect?

Three-phase asynchronous motors, 3x380 V, 50 Hz. The РДЦ-01-055 covers 0.55 to 2.2 kW on direct connection and the РДЦ-01-205 covers 2.2 to 9.0 kW; with current transformers the РДЦ-01-055 handles motors of 9.0 to 450 kW.

Does the relay check insulation resistance?

Yes. It measures insulation resistance before the motor starts, over a range of 0.3 to 3.0 MOhm. This protection function can be switched off.

Which protection functions can be disabled?

Maximum and minimum voltage, idle or dry running, current asymmetry, instantaneous overcurrent, rotor lock, phase sequence and insulation resistance.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides