Series 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66
Series 8146/5-V27-7-MCP protects Ex e and Ex d motors together with their conductors and systems. It has an adjustable thermal overcurrent release up to 32 A, an electromagnetic release at 12.5 x Ie, a glass fibre reinforced polyester resin enclosure, IP66 and Ex db eb IIC T4 Gb.
- Series
- 8146/5-V27-7-MCP
- Explosion protection marking
- Ex db eb IIC T4 Gb; Ex tb IIIC T130 °C Db
- Current-setting range
- 0.25 A ... 32 A (0,16 ... 32,00 A)
- Electromagnetic tripping
- 12.5 x Ie
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Series 8146/5-V27 motor protection circuit breakers protect Ex e and Ex d motors as well as the associated conductors and systems. Standard versions feature an adjustable, phase-sensitive thermal overcurrent release up to 32 A and an electromagnetic quick-tripping mechanism. The range also includes breakers solely for short circuit protection and transformer breakers up to 25 A.
The current-setting range is 0.16 ... 32 A (0.25 A ... 32 A in the listed versions). Electromagnetic tripping is at 12.5 x Ie, there are 3 poles, the rated surge voltage is 6 kV and the degree of pollution is 3. Electrical service life is 50000 operating cycles and mechanical service life 100000. The DC rated operational voltage is 250 V and the connection cross-section 0.5 … 4 mm².
A wide selection of undervoltage releases is available, for 230 V, 240 V and 400.00 V. A shunt trip, an auxiliary contact 1 NC & 1 NO, a trip indicator and a short-circuit signalling contact are optional. Every breaker has an N rail and a PE rail. The enclosure is polyester resin reinforced with glass fibre, rated IP66, in a standardised size.
Markings are Ex db eb IIC T4 Gb and Ex tb IIIC T130 °C Db, with certificates IECEx (PTB) and ATEX (PTB). Cable entries are 1 - 3 x M25 (Ø 7 ... 17 mm) or 2 x M32 (Ø 9 ... 21 mm), chosen for the application. The handle and protective collar are black, red or yellow, and weight is 2.5 kg.
Technical specifications
| Series | 8146/5-V27-7-MCP |
|---|---|
| Explosion protection marking | Ex db eb IIC T4 Gb; Ex tb IIIC T130 °C Db |
| Current-setting range | 0.25 A ... 32 A (0,16 ... 32,00 A) |
| Electromagnetic tripping | 12.5 x Ie |
| No. of poles | 3 |
| Release | undervoltage release, 230 V, 240 V, 400.00 V |
| DC rated operational voltage | 250 V |
| Rated surge voltage | 6 kV |
| Degree of pollution | 3 |
| Connection cross-section | 0.5 … 4 mm² |
| Electrical service life | 50000 operating cycles |
| Mechanical service life | 100000 operating cycles |
| Enclosure material | polyester resin, glass fibre reinforced polyester resin |
| Degree of protection | IP66 |
| Cable entries | 1 x M25 ... 3 x M25 Ø 7 … 17 mm; 2 x M32 Ø 9 ... 21 mm |
| Handle colour | black, red, yellow |
| Weight | 2.5 kg |
| Certificates | IECEx (PTB), ATEX (PTB) |
Part numbers
Show all part numbers (13)
344967, 345111, 345110, 345109, 345108, 345102, 345100, 345099, 345095, 345094, 345093, 345091, 345087
How it compares with similar models
| Parameter | Series 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66 | Series 8150/5-V37 stainless steel safety switches, 16–125 A, 690 V, Ex db eb IIC T6 Gb | Series 8537 safety switch, 250 A, 690 V / 500 V, Ex db eb IIC T5 Gb, IP65 | NEC/IEC Series 8146/2 Ex i Terminal Boxes, Ex ia ib IIC T6 Gb, 60 V, IP66 |
|---|---|---|---|---|
| Explosion protection marking | Ex db eb IIC T4 Gb; Ex tb IIIC T130 °C Db | Ex db eb IIC T6 Gb; Ex tb IIIC T80 °C Db | Ex db eb IIC T5 Gb; Ex tb IIIC T95 °C Db | — |
| Enclosure material | polyester resin, glass fibre reinforced polyester resin | stainless steel 1.4404 | sheet steel, painted | Polyester resin, glass fibre reinforced |
| Degree of protection | IP66 | IP66 | IP65 | — |
| Weight | 2.5 kg | 3.25 kg ... 25.6 kg | 55 kg | 2.2 ... 10.49 lb |
| Certificates | IECEx (PTB), ATEX (PTB) | ATEX (PTB), IECEx (PTB), India (PESO), China (NEPSI) | IECEx (PTB), ATEX (PTB) | UL, ATEX, IECEx, PESO, NEPSI, KGS, ITRI, ULB, BVIS |
Request a price and lead time
Series 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which motors do the 8146/5-V27 breakers protect?
Ex e and Ex d motors together with their conductors and systems. Short-circuit-only breakers and transformer breakers up to 25 A also exist.
What is the current-setting range?
0.16 ... 32 A depending on the version, with electromagnetic tripping at 12.5 x Ie.
Which options can be added?
An undervoltage release, shunt trip, auxiliary contact 1 NC & 1 NO, trip indicator and short-circuit signalling contact.
Similar equipment from other manufacturers