International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Series 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66

Series 8146/5-V27-7-MCP protects Ex e and Ex d motors together with their conductors and systems. It has an adjustable thermal overcurrent release up to 32 A, an electromagnetic release at 12.5 x Ie, a glass fibre reinforced polyester resin enclosure, IP66 and Ex db eb IIC T4 Gb.

Series
8146/5-V27-7-MCP
Explosion protection marking
Ex db eb IIC T4 Gb; Ex tb IIIC T130 °C Db
Current-setting range
0.25 A ... 32 A (0,16 ... 32,00 A)
Electromagnetic tripping
12.5 x Ie

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Series 8146/5-V27 motor protection circuit breakers protect Ex e and Ex d motors as well as the associated conductors and systems. Standard versions feature an adjustable, phase-sensitive thermal overcurrent release up to 32 A and an electromagnetic quick-tripping mechanism. The range also includes breakers solely for short circuit protection and transformer breakers up to 25 A.

The current-setting range is 0.16 ... 32 A (0.25 A ... 32 A in the listed versions). Electromagnetic tripping is at 12.5 x Ie, there are 3 poles, the rated surge voltage is 6 kV and the degree of pollution is 3. Electrical service life is 50000 operating cycles and mechanical service life 100000. The DC rated operational voltage is 250 V and the connection cross-section 0.5 … 4 mm².

A wide selection of undervoltage releases is available, for 230 V, 240 V and 400.00 V. A shunt trip, an auxiliary contact 1 NC & 1 NO, a trip indicator and a short-circuit signalling contact are optional. Every breaker has an N rail and a PE rail. The enclosure is polyester resin reinforced with glass fibre, rated IP66, in a standardised size.

Markings are Ex db eb IIC T4 Gb and Ex tb IIIC T130 °C Db, with certificates IECEx (PTB) and ATEX (PTB). Cable entries are 1 - 3 x M25 (Ø 7 ... 17 mm) or 2 x M32 (Ø 9 ... 21 mm), chosen for the application. The handle and protective collar are black, red or yellow, and weight is 2.5 kg.

Technical specifications

Series8146/5-V27-7-MCP
Explosion protection markingEx db eb IIC T4 Gb; Ex tb IIIC T130 °C Db
Current-setting range0.25 A ... 32 A (0,16 ... 32,00 A)
Electromagnetic tripping12.5 x Ie
No. of poles3
Releaseundervoltage release, 230 V, 240 V, 400.00 V
DC rated operational voltage250 V
Rated surge voltage6 kV
Degree of pollution3
Connection cross-section0.5 … 4 mm²
Electrical service life50000 operating cycles
Mechanical service life100000 operating cycles
Enclosure materialpolyester resin, glass fibre reinforced polyester resin
Degree of protectionIP66
Cable entries1 x M25 ... 3 x M25 Ø 7 … 17 mm; 2 x M32 Ø 9 ... 21 mm
Handle colourblack, red, yellow
Weight2.5 kg
CertificatesIECEx (PTB), ATEX (PTB)

Part numbers

Show all part numbers (13)

344967, 345111, 345110, 345109, 345108, 345102, 345100, 345099, 345095, 345094, 345093, 345091, 345087

How it compares with similar models

ParameterSeries 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66Series 8150/5-V37 stainless steel safety switches, 16–125 A, 690 V, Ex db eb IIC T6 GbSeries 8537 safety switch, 250 A, 690 V / 500 V, Ex db eb IIC T5 Gb, IP65NEC/IEC Series 8146/2 Ex i Terminal Boxes, Ex ia ib IIC T6 Gb, 60 V, IP66
Explosion protection markingEx db eb IIC T4 Gb; Ex tb IIIC T130 °C DbEx db eb IIC T6 Gb; Ex tb IIIC T80 °C DbEx db eb IIC T5 Gb; Ex tb IIIC T95 °C Db—
Enclosure materialpolyester resin, glass fibre reinforced polyester resinstainless steel 1.4404sheet steel, paintedPolyester resin, glass fibre reinforced
Degree of protectionIP66IP66IP65—
Weight2.5 kg3.25 kg ... 25.6 kg55 kg2.2 ... 10.49 lb
CertificatesIECEx (PTB), ATEX (PTB)ATEX (PTB), IECEx (PTB), India (PESO), China (NEPSI)IECEx (PTB), ATEX (PTB)UL, ATEX, IECEx, PESO, NEPSI, KGS, ITRI, ULB, BVIS

Request a price and lead time

Series 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which motors do the 8146/5-V27 breakers protect?

Ex e and Ex d motors together with their conductors and systems. Short-circuit-only breakers and transformer breakers up to 25 A also exist.

What is the current-setting range?

0.16 ... 32 A depending on the version, with electromagnetic tripping at 12.5 x Ie.

Which options can be added?

An undervoltage release, shunt trip, auxiliary contact 1 NC & 1 NO, trip indicator and short-circuit signalling contact.