Series 8146 lighting and heating circuit distribution boards, Ex db eb, 230–400 V, 32–80 A, IP66
Series 8146 are modular distribution boards for lighting and heating circuits in a polyester resin enclosure, IP66, for Zones 1, 2, 21 and 22. Standard versions are rated 32, 48, 64 and 80 A and carry 16 A type C breakers or 16 A+N / 30 mA residual current breakers.
- Series
- 8146
- Explosion protection marking
- Ex db eb IIC T4 Gb, Ex db eb IIC T6 Gb, Ex tb IIIC T130 °C Db, Ex tb IIIC T80 °C Db
- Installation zones
- 1, 2, 21, 22
- AC rated operational voltage
- 230 - 400 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Series 8146 boards are built from modules, which is why a large number of standard variants exists; customer-specific options are also possible. The moulded case circuit breakers sit beneath a hinged inspection glass and can be operated from outside, even when live. The switching position is visible at all times.
Lighting circuit boards carry 6, 12, 18 or 24 single-pole 16 A breakers with tripping characteristic C and 6 kA, temperature class T6. Heating circuit boards carry 8, 12 or 24 single-pole 16 A+N / 30 mA residual current breakers with overcurrent release, characteristic B or C and 6 kA, temperature class T4. The series covers nominal currents of 10, 16, 20 and 25 A per circuit; board ratings are 32 A, 48 A, 64 A or 80 A at 230 - 400 V AC.
Explosion protection markings are Ex db eb IIC T4 Gb, Ex db eb IIC T6 Gb, Ex tb IIIC T130 °C Db and Ex tb IIIC T80 °C Db, for installation in Zones 1, 2, 21 and 22. The polyester resin enclosure is rated IP66, ambient temperature is -20 °C to +40 °C and dimensions are 684 x 629.5 x 190 mm.
Cable entries are designated by type 8161/7 (for example M40, M25, M16), their number depending on the layout. Certificates are ATEX (PTB), IECEx (PTB), USA (FM), India (PESO), Korea (KGS), China (NEPSI) and Taiwan (ITRI). Enclosure material requirements refer to UL 94, IEC/EN 60695 and ASTM D635.
Technical specifications
| Series | 8146 |
|---|---|
| Explosion protection marking | Ex db eb IIC T4 Gb, Ex db eb IIC T6 Gb, Ex tb IIIC T130 °C Db, Ex tb IIIC T80 °C Db |
| Installation zones | 1, 2, 21, 22 |
| AC rated operational voltage | 230 - 400 V |
| Rated operational current | 32 A, 48 A, 64 A, 80 A |
| Breakers in lighting boards | 6, 12, 18 or 24 x 1-pole 16 A / C / 6 kA (T6) |
| Residual current breakers in heating boards | 8, 12 or 24 x 1-pole 16 A+N / 30 mA / B or C / 6 kA (T4) |
| Nominal currents of the series | 10, 16, 20, 25 A |
| Enclosure material | polyester resin |
| Degree of protection | IP66 |
| Ambient temperature | -20 °C ... +40 °C |
| Dimensions | 684 x 629.5 x 190 mm |
| Standards | IEC 60529, IEC 60079, IEC/EN 60695, UL 94, ASTM D635 |
| Certificates | ATEX (PTB), IECEx (PTB), USA (FM), India (PESO), Korea (KGS), China (NEPSI), Taiwan (ITRI) |
| Types (examples) | 8146/5-ExV-01-06L16C1P-T, 8146/5-ExV-02-08H16B1N-T, 8146/5-ExV-05-24H16C1N-T |
How it compares with similar models
| Parameter | Series 8146 lighting and heating circuit distribution boards, Ex db eb, 230–400 V, 32–80 A, IP66 | CUBEx 8264/-ExV lighting and heating circuit distribution boards, Ex d, 230–400 V, 100 A | CUBEx Series 8264/5 standard motor control units, Ex db IIB+H2 T6 Gb, 400 V, IP66 | Series 8150/5-V37 stainless steel safety switches, 16–125 A, 690 V, Ex db eb IIC T6 Gb |
|---|---|---|---|---|
| Rated operational current | 32 A, 48 A, 64 A, 80 A | 100 A | — | 16 A, 25 A, 40 A, 63 A, 125 A |
| Enclosure material | polyester resin | aluminium | copper-free aluminium, seawater-resistant | stainless steel 1.4404 |
| Degree of protection | IP66 | IP65 | IP66 | IP66 |
| Ambient temperature | -20 °C ... +40 °C | -20 °C ... +40 °C | -20 °C ... +40 °C | -40 °C to +50 °C |
| Standards | IEC 60529, IEC 60079, IEC/EN 60695, UL 94, ASTM D635 | IEC 60529, IEC 60079 | IEC 60529 | IEC/EN 62626-1, class 1 |
| Certificates | ATEX (PTB), IECEx (PTB), USA (FM), India (PESO), Korea (KGS), China (NEPSI), Taiwan (ITRI) | ATEX (DEK), IECEx (DEK), Canada / USA (UL), India (PESO), Korea (KGS), Brazil (ULB), China (NEPSI), Taiwan (ITRI) | ATEX (DEK), IECEx (DEK), India (PESO), Canada / USA (UL), Korea (KGS), Taiwan (ITRI), China (NEPSI), China (CCC) | ATEX (PTB), IECEx (PTB), India (PESO), China (NEPSI) |
Request a price and lead time
Series 8146 lighting and heating circuit distribution boards, Ex db eb, 230–400 V, 32–80 A, IP66. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which devices are fitted in the 8146 boards?
Lighting boards carry single-pole 16 A type C breakers at 6 kA; heating boards carry single-pole 16 A+N / 30 mA residual current breakers, type B or C, at 6 kA.
What current ratings are available?
32 A, 48 A, 64 A or 80 A at 230 - 400 V AC, depending on the version.
Can the breakers be operated without opening the board?
Yes. They sit beneath a hinged inspection glass and are operated from outside, even when live, with the switching position always visible.
Similar equipment from other manufacturers