РДЦ-01-057-4 and РДЦ-01-057-5 microprocessor protection relays for 6/10 kV motors
The РДЦ-01-057-4 and РДЦ-01-057-5 protect 6/10 kV induction motors against short circuits, overload, asymmetry, rotor lock, earth faults and voltage deviations. Auxiliary supply is AC/DC 100, 220 V, consumption 5 VA, with digital setting of all parameters.
- Versions
- РДЦ-01-057-4 (no voltage monitoring), РДЦ-01-057-5 (voltage monitoring 3x100 V, 50 Hz)
- Auxiliary supply
- AC/DC 100, 220 V
- Rated frequency
- 50 Hz
- Power consumption
- max 5 VA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РДЦ-01-057-4 and РДЦ-01-057-5 are motor protection relays for 6/10 kV induction motors. They run from AC or DC auxiliary power, are set digitally and display the monitored parameters.
They guard against short circuits (instantaneous trip), current overload, load asymmetry (phases A and C), underload, rotor lock and single-phase earth faults detected through the zero-sequence current 3Io. The РДЦ-01-057-5 also monitors voltage for excess, drop and wrong phase rotation; the РДЦ-01-057-4 has no voltage monitoring.
The relay measures the currents of phases A and C and the 3I0 current. When a threshold is exceeded it energises an output relay with one changeover contact for current protections, or a second one for voltage protections, and these act on the high-voltage circuit breaker. Motor resource and network frequency are monitored too, and phase currents can be watched on A and C or on A, B and C.
Rated phase A and C current is 5 A, the 3I0 current is 1 A, the monitored line voltage is 100 V and frequency is 50 Hz. Motor rated current is set at (1...990) A with an external phase CT ratio of (1...200). Instantaneous trip is set at (6...10) IН with a delay of (50...100) ms, rotor lock at (1,1...6,0) Iном, asymmetry at (20...55) % Iраб, no-load at (20...85) % Iном and earth fault at (0,02...1) Kт 3Io, with a current hysteresis of 5%.
Voltage settings are maximum (110...125) % Uном and minimum (70...95) % Uном with a delay of (1...999) s. Motor start time is (1...99) s. Auxiliary supply is AC/DC 100, 220 V and consumption is up to 5 VA. Climatic versions У and Т to ГОСТ 15150-69 are offered. The relay mounts on a front panel with wiring connected from the front, in a case of 85 х 140 х 137 mm.
Technical specifications
| Versions | РДЦ-01-057-4 (no voltage monitoring), РДЦ-01-057-5 (voltage monitoring 3x100 V, 50 Hz) |
|---|---|
| Auxiliary supply | AC/DC 100, 220 V |
| Rated frequency | 50 Hz |
| Power consumption | max 5 VA |
| Rated phase A and C current | 5 A |
| Rated 3I0 current | 1 A |
| Rated line voltage | 100 V |
| External phase CT ratio | (1...200) |
| Motor rated current setting | (1...990) A |
| Maximum voltage setting | (110...125) % Uном |
| Minimum voltage setting | (70...95) % Uном |
| No-load threshold | (20...85) % Iном |
| Load current asymmetry | (20...55) % Iраб |
| Rotor lock current | (1.1...6.0) Iном |
| Earth fault current setting (primary) | (0.02...1) Kт 3Io |
| Instantaneous trip setting | (6...10) IН |
| Motor start time | (1...99) s |
| Instantaneous trip delay | (50...100) ms |
| Output relays for current / voltage protection | 1 changeover contact each |
| Dimensions (HxWxD) | 85 х 140 х 137 mm |
Part numbers
Show all part numbers (2)
РДЦ-01-057-4, РДЦ-01-057-5
How it compares with similar models
| Parameter | РДЦ-01-057-4 and РДЦ-01-057-5 microprocessor protection relays for 6/10 kV motors | РДЦ-01-057-1, РДЦ-01-057-2 and РДЦ-01-057-3 microprocessor protection relays for 0.4 kV motors | РДЦ-01-053 and РДЦ-01-203 motor protection relays for isolated-neutral networks, 0.4 kV | РДЦ-01-055 and РДЦ-01-205 motor protection relays, 0.4 kV, 0.55 to 450 kW |
|---|---|---|---|---|
| Power consumption | max 5 VA | max 5 VA | max. 5 VA | max. 9 VA |
| Maximum voltage setting | (110...125) % Uном | (110...125) % Uном | (110…125)% UНОМ | — |
| Minimum voltage setting | (70...95) % Uном | (70...95) % Uном | (70…95)% UНОМ | — |
European equivalents
Series 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РДЦ-01-057-4 and РДЦ-01-057-5 microprocessor protection relays for 6/10 kV motors. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the РДЦ-01-057-4 and РДЦ-01-057-5 differ?
The РДЦ-01-057-4 has no voltage monitoring; the РДЦ-01-057-5 monitors 3x100 V, 50 Hz for excess, drop and phase sequence.
Which faults do the relays protect against?
Short circuits (instantaneous trip), overload, load asymmetry, underload, rotor lock and earth faults through the 3Io current.
What auxiliary supply is required?
AC/DC 100 or 220 V at 50 Hz, with consumption up to 5 VA.
Similar equipment from other manufacturers