РДЦ-01-053 and РДЦ-01-203 motor protection relays for isolated-neutral networks, 0.4 kV
The РДЦ-01-053 and РДЦ-01-203 protect three-phase asynchronous motors on 0.4 kV isolated-neutral networks. Motor rated current is 1 to 500 A and 1 to 20 A respectively, with digital settings, a four-digit display and up to 5 auto-reclosing attempts.
- Type
- Microprocessor motor protection relay for isolated-neutral networks
- Rated voltage
- 220 V, 380 V; frequency 50 Hz
- Motor rated current
- РДЦ-01-053: 1...500 A; РДЦ-01-203: 1...20 A
- Maximum voltage setting
- (110…125)% UНОМ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
These microprocessor relays, with digital settings and display of the monitored values, protect 0.4 kV motors in networks with an isolated neutral. They are used at mining and processing plants, in quarries and in metro networks. Three-phase asynchronous motors, submersible pumps included, on 3x127/220 V or 3x220/380 V are covered.
The relay monitors phase currents, voltages and mains frequency. It trips on overload, load asymmetry, underload, supply overvoltage and undervoltage, and on a drop of motor winding insulation resistance (threshold 500±100 kOhm). It also shows the current of each phase, the supply voltage, mains frequency and motor running hours, counted in steps of 1 min. Settings are password-protected and the memory is non-volatile.
Settings: maximum voltage (110 to 125)% UНОМ, minimum voltage (70 to 95)% UНОМ, hysteresis 5 %, voltage step 1 V. Overload is set from 1.1 to 2.0 IНОМ in steps of 0.1, underload from 20 to 85% IНОМ, current asymmetry from 20 to 55% IНОМ and motor start time from 1 to 25 s. Auto-reclosing is adjustable from 0 to 5 attempts at an interval of (15±3) s. The display has four digits (1 for mode, 3 for value) and six LEDs.
The РДЦ-01-053 is built for a motor rated current of 1 to 500 A with a 5 A internal CT and an external CT ratio of 1 to 100. The РДЦ-01-203 is built for 1 to 20 A with a 20 A internal CT. External current transformers of 20-50, 40-100, 80-200, 160-400 and 240-600 A are available.
The output is one normally open contact with an AC-22 switching capacity of approx. 250 VA. Endurance is at least 500000 cycles, power consumption up to 5 VA, service life at least 8 years and weight up to 0.5 kg. The У3 and УХЛ2 versions operate from -40 to +55 °C, the Т3 version from -10 to +55 °C.
Technical specifications
| Type | Microprocessor motor protection relay for isolated-neutral networks |
|---|---|
| Rated voltage | 220 V, 380 V; frequency 50 Hz |
| Motor rated current | РДЦ-01-053: 1...500 A; РДЦ-01-203: 1...20 A |
| Maximum voltage setting | (110…125)% UНОМ |
| Minimum voltage setting | (70…95)% UНОМ |
| Overload setting | (1.1 to 2.0) IНОМ, step 0.1 |
| Underload threshold | (20...85)% IНОМ |
| Load current asymmetry setting | (20...55)% IНОМ |
| Motor start time setting | (1...25) s |
| Underload delay | РДЦ-01-053: (0...255) s; РДЦ-01-203: (1...255) s |
| Auto-reclosing | (0 to 5) attempts, interval (15±3) s |
| Output contacts | 1 normally open |
| Switching capacity AC-22 | approx. 250 VA |
| Power consumption | max. 5 VA |
| Winding insulation resistance threshold | 500±100 kOhm |
| Mechanical and switching endurance | at least 500000 cycles |
| Service life | at least 8 years |
| Operating temperature | У3, УХЛ2: -40…+55 °С; Т3: -10…+55 °С |
| Weight | max. 0.5 kg |
Part numbers
Show all part numbers (2)
РДЦ-01-053, РДЦ-01-203
How it compares with similar models
| Parameter | РДЦ-01-053 and РДЦ-01-203 motor protection relays for isolated-neutral networks, 0.4 kV | РДЦ-01-055 and РДЦ-01-205 motor protection relays, 0.4 kV, 0.55 to 450 kW | РДЦ-01-057-4 and РДЦ-01-057-5 microprocessor protection relays for 6/10 kV motors | РДЦ-01-057-1, РДЦ-01-057-2 and РДЦ-01-057-3 microprocessor protection relays for 0.4 kV motors |
|---|---|---|---|---|
| Maximum voltage setting | (110…125)% UНОМ | — | (110...125) % Uном | (110...125) % Uном |
| Minimum voltage setting | (70…95)% UНОМ | — | (70...95) % Uном | (70...95) % Uном |
| Power consumption | max. 5 VA | max. 9 VA | max 5 VA | max 5 VA |
Request a price and lead time
РДЦ-01-053 and РДЦ-01-203 motor protection relays for isolated-neutral networks, 0.4 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the РДЦ-01-053 and РДЦ-01-203 differ?
The РДЦ-01-053 handles a motor rated current of 1 to 500 A with a 5 A internal CT; the РДЦ-01-203 handles 1 to 20 A with a 20 A CT. The underload delay is 0 to 255 s on the first and 1 to 255 s on the second.
Can the relay be used in an isolated-neutral network?
Yes. The relays are made for 0.4 kV motors in isolated-neutral networks, such as mining and processing plants, quarries and metro networks.
What is the operating temperature range?
-40 to +55 °C for the У3 and УХЛ2 versions, and -10 to +55 °C for the Т3 version.