РДЦ-01-057-1, РДЦ-01-057-2 and РДЦ-01-057-3 microprocessor protection relays for 0.4 kV motors
The РДЦ-01-057-1, РДЦ-01-057-2 and РДЦ-01-057-3 protect three-phase 0.4 kV induction motors against overload, asymmetry, rotor lock, earth faults and voltage deviations. All are digitally set, rated 5 A, with up to 5 automatic restarts.
- Versions
- РДЦ-01-057-1, РДЦ-01-057-2, РДЦ-01-057-3
- Auxiliary supply
- AC/DC 100, 110, 220 V (except РДЦ-01-057-2)
- Rated frequency
- 50 Hz
- Power consumption
- max 5 VA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The РДЦ-01-057-1, РДЦ-01-057-2 and РДЦ-01-057-3 protect three-phase induction motors on 0.4 kV. Settings are entered digitally and the monitored parameters are shown on the relay.
Protection covers current overload, load asymmetry (phases A and C, or A, B and C), underload, rotor lock, single-phase earth faults via the zero-sequence current 3Io, motor supply overvoltage and undervoltage, and wrong phase sequence. The relays track current, voltage, frequency and motor life, and when a threshold is exceeded they disconnect the motor through a contactor.
The РДЦ-01-057-1 runs from a single-phase AC/DC 100, 110, 220 V, 50 Hz supply and does not monitor line voltage, so its maximum voltage, minimum voltage and phase sequence protections are disabled; it watches the currents of phases A and C, or 3I0 through an external CT. The РДЦ-01-057-2 has no external supply: it is powered from the monitored voltage and watches the currents of phases A, B and C. The РДЦ-01-057-3 is supplied from AC/DC 100, 110, 220 V, monitors line voltage and watches phases A and C, or 3I0 through an external CT.
Rated phase current is 5 A, the 3I0 current is 1 A, frequency is 50 Hz and consumption is up to 5 VA. Motor rated current is set at (1...990) A with an external phase CT ratio of (1...200). Rotor lock is set at (1,1...6,0) Iном, asymmetry at (20...55) % Iраб, no-load at (20...85) % Iном and instantaneous trip at (6...10) IН, with a current hysteresis of 5%. Motor start time is (1...25) s, and automatic restarts after a current trip can be set at (0...5).
Voltage settings are maximum (110...125) % Uном and minimum (70...95) % Uном with a delay of (1...999) s. Voltage is measured to an error of 2.5 % and current to ±2.5 % / 5 %. Two output relays, each with one changeover contact, serve current and voltage protections separately. Climatic versions У and Т to ГОСТ 15150-69 are offered; the relay mounts on a front panel with front wiring in a case of 85 х 140 х 137 mm.
Technical specifications
| Versions | РДЦ-01-057-1, РДЦ-01-057-2, РДЦ-01-057-3 |
|---|---|
| Auxiliary supply | AC/DC 100, 110, 220 V (except РДЦ-01-057-2) |
| Rated frequency | 50 Hz |
| Power consumption | max 5 VA |
| Rated phase current | 5 A |
| Rated 3I0 current | 1 A |
| Rated line voltage | 100 V, 300 V |
| Voltage measurement error | 2.5 % |
| Current measurement error | ±2.5 % / 5 % |
| Maximum voltage setting | (110...125) % Uном |
| Minimum voltage setting | (70...95) % Uном |
| Motor rated current setting | (1...990) A |
| No-load threshold | (20...85) % Iном |
| Load current asymmetry | (20...55) % Iраб |
| Rotor lock current | (1.1...6.0) Iном |
| Instantaneous trip setting | (6...10) IН |
| Motor start time | (1...25) s |
| Automatic restart attempts | (0...5) |
| Dimensions (HxWxD) | 85 х 140 х 137 mm |
Part numbers
Show all part numbers (3)
РДЦ-01-057-1, РДЦ-01-057-2, РДЦ-01-057-3
How it compares with similar models
| Parameter | РДЦ-01-057-1, РДЦ-01-057-2 and РДЦ-01-057-3 microprocessor protection relays for 0.4 kV motors | РДЦ-01-057-4 and РДЦ-01-057-5 microprocessor protection relays for 6/10 kV motors | РДЦ-01-053 and РДЦ-01-203 motor protection relays for isolated-neutral networks, 0.4 kV | РДЦ-01-055 and РДЦ-01-205 motor protection relays, 0.4 kV, 0.55 to 450 kW |
|---|---|---|---|---|
| Power consumption | max 5 VA | max 5 VA | max. 5 VA | max. 9 VA |
| Maximum voltage setting | (110...125) % Uном | (110...125) % Uном | (110…125)% UНОМ | — |
| Minimum voltage setting | (70...95) % Uном | (70...95) % Uном | (70…95)% UНОМ | — |
European equivalents
Series 8146/5-V27-7-MCP motor protection circuit breakers, up to 32 A, Ex db eb IIC T4 Gb, IP66
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
РДЦ-01-057-1, РДЦ-01-057-2 and РДЦ-01-057-3 microprocessor protection relays for 0.4 kV motors. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the РДЦ-01-057-1, -2 and -3 differ?
The -1 is supplied from AC/DC 100, 110, 220 V without line voltage monitoring; the -2 is powered from the monitored voltage and watches phases A, B and C; the -3 is supplied from AC/DC 100, 110, 220 V and monitors line voltage.
How many automatic restarts can be set?
Automatic restarts after an emergency trip on current are adjustable from 0 to 5.
What is the setting range of motor rated current?
(1...990) A, with an external phase CT ratio of (1...200).