MCS air insulated metal clad switchgear for railway traction
MCS air insulated metal clad switchgear feeds the overhead line and is placed trackside, in an indoor substation or in a container. Versions MCS15-1P, MCS25-1P and MCS25-2P cover 15 kV and 27.5 kV.
- Product type
- Air insulated metal clad switchgear (MCS)
- Rated voltage, kV
- 15 / 27.5 / 27.5
- Rated frequency, Hz
- 16.7 / 50/60 / 50/60
- Number of phases
- 1 / 1 / 2
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The MCS air insulated metal clad switchgear is designed to feed the overhead line. It is usually placed trackside, in an indoor substation or in a container. It switches and protects the main railway traction circuits, including the overhead line. The manufacturer produces both the bus duct and the switchgear, so components integrate efficiently on site.
Three versions are available. MCS15-1P is a single-phase system for 15 kV and 16.7 Hz, up to 2500 A, with 40 kA breaking current. MCS25-1P is single-phase for 27.5 kV and 50/60 Hz, up to 2000 A, with 25 kA. MCS25-2P is two-phase for 27.5 kV and 50/60 Hz, up to 2000 A, with 25 kA. Rated duration of short circuit is 1 s and the operating sequence is O-0.3-CO-60-CO.
Internal arc classification is AFLR40/0.5 for MCS15-1P and AFLR25/1 for the other two. Service continuity is LSC2B, protection degree is IP3x and the temperature class is -5 / +40 °C. Dimensions (W x D x H) are 800x1600x2300 mm, 800x2000x2400 mm and 1300x2000x2400 mm respectively.
Insulation is air, so the switchgear is 100% SF6-free and environmentally friendly. The design is compact for indoor installation, with limited maintenance and easy access to all parts. The main control unit includes extended diagnostic functions, and the operating mechanism is driven by a variable speed magnetic actuator. The internal arc design is classified IAC AFLR.
The units comply with IEC and EN standards: IEC 62271, IEC 62271-1, IEC 62271-100, IEC 62271-200, IEC 62505-1 and IEC 62505-2. Application is AC power electrification.
Technical specifications
| Product type | Air insulated metal clad switchgear (MCS) |
|---|---|
| Rated voltage, kV | 15 / 27.5 / 27.5 |
| Rated frequency, Hz | 16.7 / 50/60 / 50/60 |
| Number of phases | 1 / 1 / 2 |
| Rated lightning impulse withstand voltage, kV | 125 / 200 / 200 (phase to ground, pole to pole for 2P) |
| Rated power frequency withstand voltage, kV | 50 / 95 / 95 |
| Rated normal current, A | ≤ 2500 / ≤ 2000 / ≤ 2000 |
| Rated duration of short circuit, s | 1 |
| Rated short-circuit breaking current, kA | 40 / 25 / 25 |
| Rated operating sequence, s | O-0.3-CO-60-CO |
| Internal arc classification, kA/s | AFLR40/0.5 / AFLR25/1 / AFLR25/1 |
| Service continuity | LSC2B |
| Temperature class, °C | -5 / +40 |
| Protection degree | IP3x |
| Dimensions (W x D x H), mm | 800x1600x2300 / 800x2000x2400 / 1300x2000x2400 |
| Standards | IEC 62271, IEC 62271-1, IEC 62271-100, IEC 62271-200, IEC 62505-1, IEC 62505-2 |
Part numbers
Show all part numbers (3)
MCS15-1P, MCS25-1P, MCS25-2P
How it compares with similar models
| Parameter | MCS air insulated metal clad switchgear for railway traction | VGUARD voltage limiting devices for railway DC traction | MBS high-speed circuit breaker panels for DC traction substations | EFFICIENT-REC air cooled rectifiers for DC traction substations |
|---|---|---|---|---|
| Product type | Air insulated metal clad switchgear (MCS) | Voltage limiting device for railway DC traction (ESTRA-VGUARD) | DC high-speed circuit breaker panels (ESTRA-MBS) | Air cooled traction rectifiers (EFFICIENT-REC) |
| Protection degree | IP3x | IP42 for indoor, IP65 for outdoor | IP20 or IP42 | IP2x or IP32 |
| Standards | IEC 62271, IEC 62271-1, IEC 62271-100, IEC 62271-200, IEC 62505-1, IEC 62505-2 | EN 50122-1, EN 50526-2 | EN 50123, IEC 61992, IEEE ANSI C37.20.1, C37.14 | IEC 60146-1-1, IEC 60747, EN 50328, IEEE ANSI C34.2 |
Request a price and lead time
MCS air insulated metal clad switchgear for railway traction. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which MCS versions exist and how do they differ?
MCS15-1P is 15 kV, 16.7 Hz, 1 phase, 40 kA. MCS25-1P and MCS25-2P are 27.5 kV, 50/60 Hz, 1 and 2 phases respectively, 25 kA.
What is the internal arc classification?
AFLR40/0.5 for MCS15-1P and AFLR25/1 for MCS25-1P and MCS25-2P.
Does the switchgear use SF6?
No, insulation is air and the switchgear is 100% SF6-free.