MBS high-speed circuit breaker panels for DC traction substations
MBS (ESTRA-MBS) high-speed circuit breaker panels for DC power distribution to overhead lines or third rails. Rated current is up to 8000 A, rated voltage 900 V, 1800 V or 3600 V, and protection degree IP20 or IP42.
- Product type
- DC high-speed circuit breaker panels (ESTRA-MBS)
- DC rated current
- up to 8000 A
- Rated voltage
- 900 V, 1800 V, 3600 V
- Control voltage
- from 24 to 220 VDC, 230 VAC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
MBS high-speed circuit breaker panels belong to the ESTRA range and form part of DC switchgear. This switchgear controls DC power distribution to overhead lines or third rails. The panels serve trolleybuses, tramways, metros, monorails, commuter trains and main line railway vehicles, and they are also listed for e-mining truck electrification.
Configurations are virtually unlimited. Panel duties include line feeder, rectifier breaker, inverter breaker and interconnecting breaker. Options include by-pass, isolating or earthing switches and a line test function at full or reduced voltage. Short-time withstand currents of the main and earthing circuits are adapted to the application.
The DC rated current is up to 8000 A and the rated voltage is 900 V, 1800 V or 3600 V. Control voltage runs from 24 to 220 VDC or 230 VAC. The arc voltage is constant and limited during current interruption. The protection degree is IP20 or IP42, panel depth can be adapted to a specific configuration, and the insulating shutters can be locked independently.
Three versions are offered: MBS Heavy Duty to EN/IEC standards, MBS Heavy Duty to IEEE/ANSI standards and MBS-SECUB for light rail. Reference standards are EN 50123 and IEC 61992, plus IEEE ANSI C37.20.1 and C37.14. Type tests against internal arcs were carried out to EN 50123-6/A1:2015.
The panels offer high mechanical and electrical durability, low maintenance and easy access to parts. They can be installed against a wall. A motorised withdrawable circuit breaker is available as an option for remote isolation.
Technical specifications
| Product type | DC high-speed circuit breaker panels (ESTRA-MBS) |
|---|---|
| DC rated current | up to 8000 A |
| Rated voltage | 900 V, 1800 V, 3600 V |
| Control voltage | from 24 to 220 VDC, 230 VAC |
| Protection degree | IP20 or IP42 |
| Duties | line feeder, rectifier breaker, inverter breaker, interconnecting breaker |
| Options | by-pass, isolating or earthing switches, line test at full or reduced voltage |
| Versions | MBS Heavy Duty (EN/IEC), MBS Heavy Duty (IEEE/ANSI), MBS-SECUB for light rail |
| Standards | EN 50123, IEC 61992, IEEE ANSI C37.20.1, C37.14 |
| Internal arc type test | to EN 50123-6/A1:2015 |
How it compares with similar models
| Parameter | MBS high-speed circuit breaker panels for DC traction substations | PADS disconnect switch panels for DC traction substations | PALB load break switch panels for DC traction substations | VGUARD voltage limiting devices for railway DC traction |
|---|---|---|---|---|
| Product type | DC high-speed circuit breaker panels (ESTRA-MBS) | DC disconnect switch panels (ESTRA-PADS) | DC load break switch panels (ESTRA-PALB) | Voltage limiting device for railway DC traction (ESTRA-VGUARD) |
| DC rated current | up to 8000 A | up to 8000 A | up to 6000 A | — |
| Rated voltage | 900 V, 1800 V, 3600 V | 900 V, 1800 V, 3600 V | 900 V, 1800 V, 3600 V | up to 3600 V |
| Control voltage | from 24 to 220 VDC, 230 VAC | from 24 to 220 VDC, 230 VAC | from 24 to 220 VDC | from 24 to 220 VDC, 230 VAC |
| Standards | EN 50123, IEC 61992, IEEE ANSI C37.20.1, C37.14 | EN 50123-3, IEC 61992-3, IEEE ANSI C37.20.1 | EN 50123-3, IEC 61992-3 | EN 50122-1, EN 50526-2 |
Request a price and lead time
MBS high-speed circuit breaker panels for DC traction substations. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What are the rated current and voltage of the MBS panels?
The DC rated current is up to 8000 A and the rated voltage is 900 V, 1800 V or 3600 V.
Which versions of the MBS panel exist?
MBS Heavy Duty to EN/IEC standards, MBS Heavy Duty to IEEE/ANSI standards and MBS-SECUB for light rail.
Are the panels tested against internal arcs?
Yes, they are type-tested to EN 50123-6/A1:2015. The protection degree is IP20 or IP42.