UR DC circuit breakers for traction substations to IEEE standards, 800–1600 VDC
UR-type DC high-speed circuit breakers (HSCB) built to IEEE standards for DC traction power substations. Rated voltage is 800 VDC and 1600 VDC (1200 VDC for UR80), the current range is 2000 A to 8000 A, and control voltage is 110 VDC or 125 VDC.
- Type
- IEEE DC high-speed circuit breaker
- Rated voltage
- 800 VDC and 1600 VDC (1200 VDC for UR80)
- Current range
- 2000 A - 8000 A
- Control voltage
- 110 VDC or 125 VDC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This is the IEEE version of the UR breaker for DC traction power substations feeding overhead lines and third rails of metro, light rail, tramway, EMU and DC railway systems. The range is designed to IEEE C37.14 and IEEE C.37.16 and can be used for Light Rail and Heavy Rail Transit Systems in North America.
A breaker can be integrated into DC switchgear or a metal-clad enclosure configured as a line feeder panel, a rectifier breaker panel or an interconnecting breaker panel.
Rated voltage is 800 VDC and 1600 VDC, or 1200 VDC for the UR80, and the current range is 2000 A to 8000 A. The device is bi-directional or uni-directional, trip free and direct acting; making and breaking capacity matches operational needs and closing is electromagnetic. Control voltage is 110 VDC or 125 VDC.
Auxiliary contacts indicate the main contact position, and arc voltage during current interruption is constant and limited. The insulation level is high, OV4, and the ambient temperature range is – 25 °C to +40 °C.
Reference standards are IEEE C37.16 and IEEE C37.14; the insulation material follows EN 45545-2. A UR26-80S IEEE version exists.
Technical specifications
| Type | IEEE DC high-speed circuit breaker |
|---|---|
| Rated voltage | 800 VDC and 1600 VDC (1200 VDC for UR80) |
| Current range | 2000 A - 8000 A |
| Control voltage | 110 VDC or 125 VDC |
| Insulation level | OV4 |
| Ambient temperature | – 25 °C - +40 °C |
| Reference standards | IEEE C37.16; IEEE C37.14 |
| Insulation material | according to EN 45545-2 |
How it compares with similar models
| Parameter | UR DC circuit breakers for traction substations to IEEE standards, 800–1600 VDC | UR DC circuit breakers for traction substations to EN/IEC standards, 900–3600 VDC | UR DC circuit breakers for industry, 900–3600 VDC, up to 8000 A | SW disconnectors for fixed DC installations, 2000–8000 A |
|---|---|---|---|---|
| Type | IEEE DC high-speed circuit breaker | DC high-speed circuit breaker for traction substations | Industrial DC high-speed circuit breaker | Off-load disconnector for fixed installation |
| Rated voltage | 800 VDC and 1600 VDC (1200 VDC for UR80) | 900 VDC, 1800 VDC, 3600 VDC | 900 VDC, 1800 VDC, 3600 VDC | — |
| Current range | 2000 A - 8000 A | 1000 A - 8000 A | 1000 A - 8000 A | 2000 A - 8000 A |
| Control voltage | 110 VDC or 125 VDC | 24 - 220 VDC or rectified 230 VAC | 24 - 220 VDC or rectified 230 VAC | 24 - 220 VDC or 230 VAC |
| Reference standards | IEEE C37.16; IEEE C37.14 | EN 50123-2; IEC 61992-2 | IEC 60947-2; EN 50123-2; IEC 61992-2; GB 14048-2; ANSI C37.16; ANSI C37.14 | EN 50123-3; IEC 61992-3 |
Request a price and lead time
UR DC circuit breakers for traction substations to IEEE standards, 800–1600 VDC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which voltages does the IEEE version cover?
800 VDC and 1600 VDC, and 1200 VDC for the UR80.
What control voltage applies?
110 VDC or 125 VDC.
Which IEEE standards apply?
IEEE C37.16 and IEEE C37.14.