SEPCOS control and protection relays for DC traction substations
SEPCOS (STELLA-SEPCOS) control and protection relays guard DC panels and contact lines against short circuits and other electrical faults. The relays are modular, with 4 analogue inputs and 16 digital inputs and 8 digital outputs per module.
- Product type
- Control and protection relays for DC traction (STELLA-SEPCOS)
- Voltage range
- Low Voltage 24-48 VDC, High Voltage 60-220 VDC
- Microprocessor
- 32 bit
- Analogue-to-digital converter
- 16 bit
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
SEPCOS relays handle protection, control and measurement of DC traction equipment. They protect DC panels and contact lines from electrical faults, above all short circuits. The line is designed with connectivity and ease of use in mind.
The devices are modular, so the solution is easy to expand or configure. The integrated programmable logic controller sets the operating logic to suit the supervised equipment, and programming conforms to IEC61131-3. The voltage range is Low Voltage (24-48 VDC) or High Voltage (60-220 VDC).
The control processing unit module carries a 32 bit microprocessor with a 16 bit analogue-to-digital converter. There are 4 analogue inputs and 1 analogue output, with a sampling rate of 20 µs per input. The relay keeps the last 5000 events and 1000 curves, memorised per detection of I, U and di/dt. Each module has 16 digital inputs and 8 digital outputs.
Communication covers IEC61850, IEC60870-5-104(101), DNP3, Modbus TCP, Profinet and a serial bus. Network redundancy follows IEC62439-3 (PRP/HSR), and the IEC 61850 server level A is KEMA certified. External synchronisation uses NTP. From 1 up to 3 RJ45 network ports and 2 optical fibre ports are possible. A 7″ colour touch screen and an embedded web server serve maintenance, parametrisation and analysis. The relays comply fully with the IEC-60255 series.
The line comes as SEPCOS, SEPCOS PLC, SEPCOS RTU, SEPCOS Gateway and SEPCOS Compact. Application is DC traction power supply for railways. Accuracy and noise immunity are high.
Technical specifications
| Product type | Control and protection relays for DC traction (STELLA-SEPCOS) |
|---|---|
| Voltage range | Low Voltage 24-48 VDC, High Voltage 60-220 VDC |
| Microprocessor | 32 bit |
| Analogue-to-digital converter | 16 bit |
| Analogue inputs / outputs | 4 / 1 |
| Analogue sampling rate | 20 µs per input |
| Event storage | last 5000 events |
| Curve storage | 1000 curves (per detection I, U, di/dt) |
| Digital inputs / outputs per module | 16 / 8 |
| Protocols | IEC61850, IEC60870-5-104(101), DNP3, Modbus TCP, Profinet, serial bus |
| Network ports | 1 up to 3 RJ45, 2 optical fibre |
| Network redundancy | IEC62439-3 (PRP/HSR) |
| Display | 7″ colour touch screen |
| Programming | IEC61131-3 |
| Standards | IEC-60255 series, IEC 61850 |
| Versions | SEPCOS, SEPCOS PLC, SEPCOS RTU, SEPCOS Gateway, SEPCOS Compact |
How it compares with similar models
| Parameter | SEPCOS control and protection relays for DC traction substations | MBS high-speed circuit breaker panels for DC traction substations | PALB load break switch panels for DC traction substations | KEOPS control command and local SCADA for traction substations |
|---|---|---|---|---|
| Product type | Control and protection relays for DC traction (STELLA-SEPCOS) | DC high-speed circuit breaker panels (ESTRA-MBS) | DC load break switch panels (ESTRA-PALB) | Local SCADA and control system for traction (STELLA-KEOPS) |
| Standards | IEC-60255 series, IEC 61850 | EN 50123, IEC 61992, IEEE ANSI C37.20.1, C37.14 | EN 50123-3, IEC 61992-3 | — |
Request a price and lead time
SEPCOS control and protection relays for DC traction substations. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which communication protocols do the relays support?
IEC61850, IEC60870-5-104(101), DNP3, Modbus TCP, Profinet and a serial bus. Network redundancy is per IEC62439-3 (PRP/HSR).
How many events and curves are stored?
The last 5000 events and 1000 curves, memorised per detection of I, U and di/dt.
Which versions of the line are available?
SEPCOS, SEPCOS PLC, SEPCOS RTU, SEPCOS Gateway and SEPCOS Compact.
Similar equipment from other manufacturers