ESTRA-VM isolated amplifiers (VM10, VM12) for voltage measurement
The ESTRA-VM amplifier measures high DC voltages in power distribution systems for public transport networks, connected directly to the high-voltage circuit. Rated voltage is up to 3600 V, with outputs of ±5 V, ±20 mA or 4 … 20 mA.
- Product type
- Isolated amplifier for voltage measurement (ESTRA-VM)
- Rated voltage
- up to 3600 V
- Test voltage
- up to 10 kV AC (15 kV for the fixed setting version)
- Application
- voltage measurement up to 3600 V, directly connected to the high-voltage circuit
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ESTRA-VM measures high DC voltages in power distribution systems for public transportation networks. Voltage up to 3600 V is measured with the unit connected directly to the high-voltage circuit. High-voltage isolation protects people and property, and protection against electric shock comes from protective separation between input, output and power supply.
The bipolar voltage input is settable from 750 to 2000 Vdc, or fixed at 3000 Vdc. A special version for the return circuit is fixed at 150 Vdc. The output signal is settable to ±5 V, ±20 mA or 4 … 20 mA. The supply voltage runs from 24 to 230 VDC/VAC.
Rated voltage is up to 3600 V. Test voltage is up to 10 kV AC, or 15 kV for the fixed setting version. Protective separation reaches 1800 V AC/DC according to EN 61140. The unit is designed to withstand permanent voltages up to 3600 V AC/DC and fast transients up to 20 kV. Galvanic isolation reaches 15 kV, and immunity is high enough that no fuse is required.
Reference standards are EN 50121-5 when mounted in a cubicle and EN 61326 class B (the standard for isolators). Versions are VM10 and VM12. The unit is intended for DC traction power supply and is designed to work with SEPCOS. It is compact and accepts a wide supply voltage range.
Technical specifications
| Product type | Isolated amplifier for voltage measurement (ESTRA-VM) |
|---|---|
| Rated voltage | up to 3600 V |
| Test voltage | up to 10 kV AC (15 kV for the fixed setting version) |
| Application | voltage measurement up to 3600 V, directly connected to the high-voltage circuit |
| Input (bipolar voltages) | settable from 750 to 2000 Vdc or 3000 Vdc (fixed setting) |
| Special version for return circuit | 150 Vdc (fixed setting) |
| Output signals | ±5 V, ±20 mA or 4 … 20 mA |
| Power supply voltage | from 24 to 230 VDC/VAC |
| Protective separation | up to 1800 V AC/DC according to EN 61140 |
| Permanent voltage / fast transients | up to 3600 V AC/DC / up to 20 kV |
| Standards | EN 50121-5 (in a cubicle), EN 61326 class B, EN 61140 |
Part numbers
Show all part numbers (2)
VM10, VM12
How it compares with similar models
| Parameter | ESTRA-VM isolated amplifiers (VM10, VM12) for voltage measurement | ESTRA-MIU isolated amplifier for current measurement | ESTRA-VP20 isolated relay for voltage presence detection | VGUARD voltage limiting devices for railway DC traction |
|---|---|---|---|---|
| Product type | Isolated amplifier for voltage measurement (ESTRA-VM) | Isolated amplifier for current measurement (ESTRA-MIU10) | Isolated relay for voltage presence detection (ESTRA-VP20) | Voltage limiting device for railway DC traction (ESTRA-VGUARD) |
| Test voltage | up to 10 kV AC (15 kV for the fixed setting version) | up to 10 kV AC (15 kV for the fixed setting version) | up to 10 kV AC | — |
| Application | voltage measurement up to 3600 V, directly connected to the high-voltage circuit | current measurement through a shunt resistor | voltage measurement up to 3600 V, directly connected to the high-voltage circuit | limitation of dangerous touch voltages |
| Power supply voltage | from 24 to 230 VDC/VAC | from 24 to 230 VDC/VAC | 3 ranges covering 24 to 230 VDC | — |
| Standards | EN 50121-5 (in a cubicle), EN 61326 class B, EN 61140 | EN 50121-5 (in a cubicle), EN 61326 class B, EN 61140 | EN 50121-5 (in a cubicle), EN 50124-1, EN 61000-6-2, EN 61000-6-4 | EN 50122-1, EN 50526-2 |
Request a price and lead time
ESTRA-VM isolated amplifiers (VM10, VM12) for voltage measurement. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What input range does the amplifier have?
The input is settable from 750 to 2000 Vdc or fixed at 3000 Vdc. A special version for the return circuit is fixed at 150 Vdc.
Is an input fuse needed?
No, immunity is high and no fuse is required. Voltage up to 3600 V is measured with a direct connection.
Which outputs and supply does it use?
The output is settable to ±5 V, ±20 mA or 4 … 20 mA. The supply runs from 24 to 230 VDC/VAC.