TDOK Oil-Immersed Compensation Reactor, 40 kVAr to 10 MVAr, up to 36 kV
The TDOK is an oil-immersed reactor that compensates capacitive currents in long cable lines. It covers 40 kVAr to 10 MVAr at up to 36 kV with ONAN or KNAN cooling, in a hermetic or conservator version.
- Rated power
- 40 kVAr to 10 MVAr
- Auxiliary power
- according to customer requirements, up to 250 kVA
- Rated voltage
- up to 36 kV
- Cooling
- ONAN, KNAN
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
TDOK reactors compensate capacitive current, for example in the long cable lines of wind farms and on railway lines. They are connected to the network in three phases. A reactor may carry an on-load or off-load tap changer so that its operating parameters can be matched to the compensating current.
Additional windings can supply the auxiliary needs of a substation or switchgear. The auxiliary power is set to the customer's requirements, and a value of up to 250 kVA is also given. A further function is compensation of the short-circuit current, as with an earthing transformer. Combining reactor and auxiliary transformer duties allows the unit to be installed in a substation, for instance in place of an auxiliary transformer, without extending the substation. Combining a regulated reactor, an auxiliary transformer and an earthing transformer also simplifies the management of substations that include an earthing point of the medium voltage network.
Rated power runs from 40 kVAr to 10 MVAr and rated voltage is up to 36 kV. Cooling is ONAN or KNAN, the insulation class follows N-EN 60085 and rated frequency is 50 or 60 Hz. Maximum operating altitude is 1000 m above sea level; ambient temperature is -25 to 40 °C.
Two versions are built: hermetic, without a conservator, and with a conservator. The core is cold-rolled transformer steel with inorganic insulation and the windings are copper. The tank is sheet steel, powder-painted or hot-dip galvanised, mounted on a wheeled chassis; a radiator tank is also possible. The finish is RAL 7033.
Standard fittings include an off-load or on-load tap changer, porcelain HV bushings to DIN 42531 or EN 50180:2010, LV bushings to DIN 42530 or EN 50386:2010, oil level indicator, rating plate, earthing terminals on the chassis, lifting and transport lugs, thermometer pocket, oil filler and a drain valve to EN 50216-4 or DIN 42551. Options are DGPT2 or DMCR2 protection, surge arresters, a dial thermometer, anti-vibration pads, a cable box and connector bushings. The conservator version adds a Buchholz relay, a conservator oil level indicator, a dehydrating breather and a drain plug. Manufacture, testing and tolerances follow PN EN 60076-1 and PN EN 60076-6.
Technical specifications
| Rated power | 40 kVAr to 10 MVAr |
|---|---|
| Auxiliary power | according to customer requirements, up to 250 kVA |
| Rated voltage | up to 36 kV |
| Cooling | ONAN, KNAN |
| Insulation class | according to N-EN 60085 |
| Max. operating altitude | 1000 m above sea level |
| Ambient temperature range | -25 to 40 °C |
| Rated frequency | 50 or 60 Hz |
| Core | cold-rolled transformer steel with inorganic insulation |
| Windings | copper |
| Tank | hermetic (no conservator) or with conservator, powder-painted or hot-dip galvanised |
| Finish colour | RAL 7033 |
How it compares with similar models
| Parameter | TDOK Oil-Immersed Compensation Reactor, 40 kVAr to 10 MVAr, up to 36 kV | TDOK Oil-Immersed Compensation Reactor, 150 kVAr to 13 MVAr, up to 36 kV | TDOK C Oil-Filled Shunt Compensation Reactor with Cooler, 10–25 MVAr, up to 36 kV | TDOK RO Oil-Immersed Compensation Reactor with On-Load Tap Changer, 546 kVAr – 15 MVAr |
|---|---|---|---|---|
| Rated power | 40 kVAr to 10 MVAr | 150 kVAr to 13 MVAr (with on-load tap changer) | 10 MVAr – 25 MVAr | 546 kVAr – 15 MVAr |
| Cooling | ONAN, KNAN | ONAN, KNAN | OFAF or KFAF | ONAN or KNAN (does not apply to the oil in the on-load tap changer) |
| Windings | copper | copper | round or profiled wire with class H insulation, copper or aluminium | round or profiled wire with class H insulation, copper |
| Tank | hermetic (no conservator) or with conservator, powder-painted or hot-dip galvanised | hermetic (no conservator) or with conservator, powder-painted or hot-dip galvanised | with oil cooler, powder-painted sheet steel, C4 or C5 anticorrosion system | radiator tank, powder-painted sheet steel, C4 or C5 anticorrosion system |
Request a price and lead time
TDOK Oil-Immersed Compensation Reactor, 40 kVAr to 10 MVAr, up to 36 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
In which versions is the TDOK reactor built?
In two: hermetic, without a conservator, and with a conservator. The tank can also be made as a radiator tank.
Can the reactor supply a substation's auxiliary needs?
Yes. Additional windings can be added, with the auxiliary power set to customer requirements and a value of up to 250 kVA given. A short-circuit current compensation function, as with an earthing transformer, is also possible.
Which tap changer is fitted?
The standard fittings list an off-load or on-load tap changer. It lets the operating parameters be matched to the compensating current.