TDOK C Oil-Filled Shunt Compensation Reactor with Cooler, 10–25 MVAr, up to 36 kV

The TDOK C is an oil-filled reactor with an oil cooler that offsets capacitive currents on medium voltage networks. It is rated 10 MVAr – 25 MVAr at up to 36 kV, with OFAF or KFAF cooling and Y or YN connection.

Rated power
10 MVAr – 25 MVAr
Rated voltage
up to 36 kV
Cooling
OFAF or KFAF
Insulation class
according to N-EN 60085

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Long cable lines on wind farms, in urbanised and industrial distribution networks and on railway networks generate capacitive current. The TDOK C reactor compensates it and is connected in parallel with the MV network. Its characteristic stays fully linear whatever the supply voltage.

Rated power is 10 MVAr – 25 MVAr and rated voltage is up to 36 kV, at 50 or 60 Hz. Connection is Y or YN, cooling is OFAF or KFAF, and the insulation class follows N-EN 60085. Maximum operating altitude is 1000 m above sea level, and ambient temperature ranges from -25 to 40 °C.

The core is cold-rolled transformer steel with inorganic insulation. Windings are round or profiled wire with class H insulation, in copper or aluminium. The tank carries an oil cooler and is made of powder-painted sheet steel with a C4 or C5 anticorrosion system, finished in RAL 7033. It stands on a wheeled chassis whose wheels can be reset for longitudinal or transverse travel. The cooler and its pump are selected according to the unit's power.

Standard fittings are porcelain HV bushings to DIN 42531 or EN 50180:2010 (or connector bushings), oil level indicator, Buchholz relay, drain valve to EN 50216-4 or DIN 42551, earthing terminals on the chassis, rating plate, dehydrating breather, contact thermometer, conservator with drain and filler, filler on the cover, lifting lugs, off-circuit tap changer, pressure relief valve and a protection box.

Options include a 7-position tap changer for current adjustment (other adjustment on request), surge arresters and anti-vibration pads. An additional auxiliary supply winding can be made once technical feasibility has been confirmed with the manufacturer. Manufacture, testing and tolerances follow PN EN 60076-1 and PN EN 60076-6. Units with other parameters are built by individual agreement.

Technical specifications

Rated power10 MVAr – 25 MVAr
Rated voltageup to 36 kV
CoolingOFAF or KFAF
Insulation classaccording to N-EN 60085
Connection schemeY or YN
Rated frequency50 or 60 Hz
Max. operating altitude1000 m above sea level
Ambient temperature range-25 to 40 °C
Corecold-rolled transformer steel with inorganic insulation
Windingsround or profiled wire with class H insulation, copper or aluminium
Tankwith oil cooler, powder-painted sheet steel, C4 or C5 anticorrosion system
Finish colourRAL 7033

How it compares with similar models

ParameterTDOK C Oil-Filled Shunt Compensation Reactor with Cooler, 10–25 MVAr, up to 36 kVTDOK Oil-Immersed Compensation Reactor, 40 kVAr to 10 MVAr, up to 36 kVTDOK Oil-Immersed Compensation Reactor, 150 kVAr to 13 MVAr, up to 36 kVTDOK RO Oil-Immersed Compensation Reactor with On-Load Tap Changer, 546 kVAr – 15 MVAr
Rated power10 MVAr – 25 MVAr40 kVAr to 10 MVAr150 kVAr to 13 MVAr (with on-load tap changer)546 kVAr – 15 MVAr
CoolingOFAF or KFAFONAN, KNANONAN, KNANONAN or KNAN (does not apply to the oil in the on-load tap changer)
Windingsround or profiled wire with class H insulation, copper or aluminiumcoppercopperround or profiled wire with class H insulation, copper
Tankwith oil cooler, powder-painted sheet steel, C4 or C5 anticorrosion systemhermetic (no conservator) or with conservator, powder-painted or hot-dip galvanisedhermetic (no conservator) or with conservator, powder-painted or hot-dip galvanisedradiator tank, powder-painted sheet steel, C4 or C5 anticorrosion system

Request a price and lead time

TDOK C Oil-Filled Shunt Compensation Reactor with Cooler, 10–25 MVAr, up to 36 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which networks is the TDOK C reactor intended for?

It compensates capacitive currents in long cable lines, including those on wind farms, in urbanised and industrial distribution networks and on railway networks. It is connected in parallel with the MV network.

Can the compensating current be adjusted?

Yes. A 7-position tap changer for current adjustment is available as an option, and other adjustment can be made on request. The standard set includes an off-circuit tap changer.

What cooling and winding materials are used?

Cooling is OFAF or KFAF, with an oil cooler and pump on the tank. Windings are copper or aluminium, in round or profiled wire with class H insulation.

Similar equipment from other manufacturers