Oil-filled earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11

Three-phase oil-filled earthing transformers create an artificial neutral point in resistor-earthed and compensated networks. Rated power is 150 kVA to 4 MVA, voltage up to 36 kV, connection group ZNyn11.

Rated power
150 kVA to 4 MVA
Rated voltage
up to 36 kV
Connection group
ZNyn11
Max. operating altitude
1000 m above sea level

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

An earthing transformer provides an artificial neutral point in networks earthed through a resistor and in compensated networks. These are three-phase transformers which, while there is no earth fault, also supply the station auxiliaries.

The characteristic connection group of an earthing transformer is ZNyn11. In a fault (earth fault) it spreads the fault current across all phases and so reduces its value in the faulty line. The secondary winding can run continuously at rated conditions even when the primary winding carries a compensation current.

In resistor-earthed networks the neutral point of the unit is connected to an earthed resistor that forces the active component. In compensated networks it is normally connected to an arc suppression reactor, which adds the reactance needed to extinguish the arc and compensate earth fault currents.

The production range is 150 kVA to 4 MVA at rated voltage up to 36 kV. Maximum operating altitude is 1000 m above sea level, ambient temperature is from -25 to 40 °C, and rated frequency is 50 Hz. The core is cold-rolled electrical steel with inorganic insulation, and the windings are round or profiled wire with class H varnish insulation, copper or aluminium.

The tank is hermetic (without conservator) or fitted with a conservator, made of powder-painted or hot-dip galvanised sheet steel, on a wheeled chassis whose wheels can be turned to the travel direction. A radiator tank is also possible. Standard fittings include a 5-position manual tap changer drive, porcelain HV bushings to DIN 42531 or EN 50180:2010 and LV bushings to DIN 42530 or EN 50386:2010, an oil level gauge, a thermometer pocket, an oil filler, a drain valve to EN 50216-4 or DIN 42551, and RAL 7033 finish. Options are a 7-position drive, DGPT2 or DMCR2 protection, surge arresters, a dial thermometer, anti-vibration pads and a cable box. Versions with a conservator add a Buchholz relay, an oil level indicator on the conservator, a dehydrating breather and a drain plug. Design, tests and tolerances follow PN EN 60076-1 and PN EN 60289.

Technical specifications

Rated power150 kVA to 4 MVA
Rated voltageup to 36 kV
Connection groupZNyn11
Max. operating altitude1000 m above sea level
Ambient temperature range-25 to 40 °C
Rated frequency50 Hz
Corecold-rolled electrical steel with inorganic insulation
Windingsround or profiled wire with class H varnish insulation, copper or aluminium
Tankhermetic (without conservator) or with conservator; radiator tank possible
Tap changermanual drive, 5 positions (7 positions optional)
Bushingsporcelain, HV to DIN 42531 or EN 50180:2010, LV to DIN 42530 or EN 50386:2010
Finish colourRAL 7033
StandardsPN EN 60076-1, PN EN 60289

How it compares with similar models

ParameterOil-filled earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11Dry-type earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11Dry arc suppression reactors (Petersen coils) 150 kVAr to 4 MVAr, up to 36 kVBDGO oil-immersed Petersen coil, 150 kVA to 4 MVA, up to 36 kV
Rated power150 kVA to 4 MVA150 kVA to 4 MVA150 kVAr to 4 MVAr150 kVA to 4 MVA
Rated voltageup to 36 kVup to 36 kVup to 36 kVUp to 36 kV
Rated frequency50 Hz50 or 60 Hz50 Hz50 Hz
Corecold-rolled electrical steel with inorganic insulationcold-rolled electrical steel with inorganic insulationcold-rolled electrical steel with inorganic insulationCold-rolled transformer sheet steel, inorganic insulation
Windingsround or profiled wire with class H varnish insulation, copper or aluminiumcopper or aluminium, vacuum technology or roving with glass fibrecopper or aluminium, vacuum technology or roving with glass fibreRound or profiled wire, class H lacquer insulation, copper or aluminium
StandardsPN EN 60076-1, PN EN 60289PN EN 60076-1, PN EN 60076-11, PN EN 60076-6PN EN 60076-1, PN EN 60076-11—

Request a price and lead time

Oil-filled earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is an oil-filled earthing transformer used for?

It creates an artificial neutral point in resistor-earthed and compensated networks. While there is no earth fault it also supplies the station auxiliaries.

What connection group does it have and why?

ZNyn11. In an earth fault it spreads the fault current across all phases and reduces its value in the faulty line.

Which tank versions are possible?

Hermetic tank without conservator, tank with conservator, or radiator tank. The tank is powder-painted or hot-dip galvanised sheet steel.